AMR PULSE W-Mbus- Mode d’emploi / User guide version V1.3.1
35
Page
of 44
3.4. Configuring the AMR PULSE
Your AMR PULSE product is supplied with the following factory settings: WMBUS T1 radio mode, transmission frequency of 10 seconds.
Your AMR PULSE is configured via the combination of switches. The following settings can be changed:
• The meter type
• The pulse weight
• The transmission frequency
Note:
configuration via switches lets you use 2 meters of the same type (2 water, 2 gas, …).
CONFIGURATION TABLE:
Parameter
Value
SW1
SW2
SW3
SW4
SW5
SW6
Meter type
Electricity
ON
OFF
Water
OFF
OFF
Gas
OFF
ON
Heat
ON
ON
Pulse weight
1L / 10dm
3
/ 1Wh
OFF
OFF
10L / 10dm
3
/ 10Wh
OFF
ON
100L / 100dm
3
/ 100Wh
ON
OFF
1000L / 1m
3
/ 1000Wh
ON
ON
Transmission frequency
10 seconds
OFF
OFF
10 minuts
OFF
ON
1 hour
ON
OFF
12 hours
ON
ON
PLEASE NOTE
: you must set your switches before activating the meters. Once the fraud wire for each of the meters has been installed and the
AMR PULSE has been started via a magnet, the configuration can no longer be changed.
If you change the switch configuration after activation, the product will transmit a switch consistency error frame. This consistency verification is
carried out every minute.
3.5. Closure of the case
Once steps 3.2, 3.3 and 3.4 have been completed, you can close the AMR PULSE’s case.
Procedure:
• Make sure the seal is installed correctly on the case plate.
• Clip the electronic board to the case plate. Make sure the clip is fully engaged in the lug in the board.
Seal