2.  Connection

To connect the SVA correctly, we recommend using exclusively Camden CTB922HE/# type connectors.

Measurements may be affected if other connectors are used.

2.1.  Positioning

Position the SVA where it is not affected by direct sunlight or other heat sources. Choose the place of 

installation such that moisture cannot penetrate the device. The SVA can be mounted onto the TS35 rail 

without screws. The permitted ambient temperature range for the electronics is -20°C to +50°C.

The transmission power of the SVA’s internal GSM/4G module is higher than that of a standard mobile 

phone. Under certain conditions this may affect the functioning of surrounding electronic equipment. The 

effects depend upon the distance between the antenna and surrounding equipment.

2.2. 

Affixing and removal: DIN rail

The SVA should be affixed to a DIN rail before connection.

  

• 

Put the SVA onto the DIN rail at an angle [1]. It is important that the SVA’s DIN rail clip is positioned on 

the top of the DIN rail.

  

• 

Tilt the SVA to clip it into place [2]. Then check whether it is securely seated.

The SVA is removed from a DIN rail as follows.

  

• 

Place a screwdriver on the underside of the DIN rail clip [3]. Use this as a lever; after approx. 3 mm the 

SVA can be tilted to release it from the DIN rail.

2.3. 

SIM card

The size of the SIM card is the mini SIM card size. If the SIM card has a PIN code, this should be entered in 

the setup tool SV-prog. The required SIM card is installed as follows:

• 

Switch the SVA off by disconnecting the supply voltage, then press and hold the reset key for 8 seconds 

to switch off the dialler;

• 

The SIM card holder is made accessible by pressing the button next to it using a sharp object. The 

holder is then pushed outwards;

•  Place the SIM card in the holder and slide this back into the SVA;

•  Reconnect the supply voltage to switch the SVA on.

The SVA should be completely switched off before the SIM card is installed. Fitting or removing the SIM 

card with the SVA switched on may damage the SIM card.

Summary of Contents for SVA

Page 1: ...MEASURING ALERTING CONNECTING EN Manual SVA Version 02 2021 ...

Page 2: ...y 6 2 7 Ethernet 6 2 8 2G 4G connection 7 2 9 Inputs and outputs 7 3 SV prog 7 3 1 Installation 7 3 2 Status screen 7 3 3 Call list 7 3 4 I O 7 3 4 1 Input delay 8 3 4 2 Recovery report idle 8 3 4 3 System errors 8 3 5 Connections 8 3 5 1 Checkmyproces com 8 3 5 2 Own server 8 3 6 System 8 3 6 1 Device 8 3 6 2 Ethernet 8 3 6 3 GSM and mobile data 8 3 6 4 Factory reset 9 4 Notification procedure 9 ...

Page 3: ...e placed in an environment protected against electrostatic discharge ESD The SVA is intended for use as a modem or alarm dialler The SVA is not intended for use as part of a critical safety system in a critical process 1 4 Checking the delivery Check the packaging for damage Contact your supplier immediately if the delivery is found to be damaged or incomplete upon receipt The standard delivery in...

Page 4: ...vent damage You should therefore discuss the remaining risk with your insurer 1 8 Identification Figure 1 Identification SVA 1 2 3 4 5 6 7 8 9 10 1 Reset button 2 LED status indicator general status on busy antenna level network error messages error 3 Antenna connection type SMA female 4 SIM card holder 5 Ethernet connection 6 Information sticker 7 Input output connection terminals 8 Supply voltag...

Page 5: ...the SVA onto the DIN rail at an angle 1 It is important that the SVA s DIN rail clip is positioned on the top of the DIN rail Tilt the SVA to clip it into place 2 Then check whether it is securely seated The SVA is removed from a DIN rail as follows Place a screwdriver on the underside of the DIN rail clip 3 Use this as a lever after approx 3 mm the SVA can be tilted to release it from the DIN rai...

Page 6: ...nected internally to the GND connection of the input connector and the COM port If the SVA is connected to an application process controller PLC computer active sensor etc without galvanic isolation and the SVA is connected to the same power supply there is a real chance of earth loops and or short circuits in this power supply 2 6 Reset key The reset key has four functions first of all it is used...

Page 7: ...ing the installation process As soon as the installation process is complete start the program via the shortcut or via the program menu in MS Windows Connect the SVA to a power source and connect the SVA to the PC using the Ethernet cable set supplied The SVA can be connected to the local network or directly to the PC As soon as the SVA has been switched on the tool will display this in the overvi...

Page 8: ...reen and by looking on the side of de dialler Remote configuration It is possible to remotely make changes to the settings of the dialler This is possible by ethernet and by 4G GPRS For using remote configuration it is necessary to have a constant connection When using 4G GPRS keep in mind of the extra cost If the network is secured by use of a firewall Please make the following exceptions Data co...

Page 9: ...ation into an Email message and sends this to the Email address that has been entered The structure of the message is the same as the SMS 4 2 Notification of status changes After input channel 1 has been activated the following can be observed The green LED on busy flashes 1x to indicate that input channel 1 is active After a few seconds the green LED on busy flashes faster to indicate that the SM...

Page 10: ... SMS message The SMS message should be structured as follows Command parameter1 parameter2 Command O Output Parameter1 A Active or I Idle or P switch Pulse default 2 seconds active Parameter2 I O number The output number is not the same as the relay number Relay number 1 is output 5 Figure 3 Connectsticker Example SMS message to relay 1 Output 5 active OA5 Output 5 Idle OI5 Output 5 with default P...

Page 11: ...ched off On SVA is switched on Faster Starting up sending message 1x Input 1 active 2x Input 2 active 3x Input 3 active 4x Input 4 active 5x Input 5 active 6x Input 6 active 7x Input 7 active 8x Input 8 active 7 2 Technical specifications Systeemeigenschappen SVA0000 I Type of detector alarm dialler Weblogger modem Number of digital inputs Number of GPIO inputs Number of PT100 inputs Number of rel...

Page 12: ...tes so that a power failure can still be reported Expected service life Calculated MTBF 88167 hours 10 years according to componentcounting method Enclosure and operating conditions Enclosure DIN rail TS35 mounting enclosure fire retardant UL94 V0 Dimmensions W x H x D 23 x 95 x 102 mm Weight 125gr Operating temperature 20 C 50 C Air humidity 20 85 not condensed IP code IP10 Maximum heigth Up to 2...

Page 13: ... Also available in this SV product line SVL Weblogger SVM 4G modem Checkmyprocess com Industrial 4G Weblogger for sending alerts in relation to limit values being exceeded Industrial 4G modem sms alarm dialler for connection to applications in the field Convenient display of current measured values from your process Version 02 2021 ...

Reviews: