background image

VISTA-20

SE

2-PARTITIONED

SECURITY SYSTEM

PROGRAMMING

FORM

®

Principal changes between the VISTA-20SE and
the former VISTA-20 are indicated by margin lines.

VISTA-20PRV4  8/97 (See Instructions N7526V4)

Previous Menu

Features Q.E.D. programming for quick
enrollment of devices.

Summary of Contents for VISTA-20SE

Page 1: ... SYSTEM PROGRAMMING FORM Principal changes between the VISTA 20SE and the former VISTA 20 are indicated by margin lines VISTA 20PRV4 8 97 See Instructions N7526V4 Previous Menu Features Q E D programming for quick enrollment of devices ...

Page 2: ...27 X 10 HOUSE CODE 0 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 I 9 J 10 K 11 L 12 M 13 N 14 O 15 P 28 PHONE MODULE ACCESS CODE 00 Partition 1 only 1st digit enter 1 9 2nd digit enter 11 for or 12 for Entering 0 for either digit disables code 29 OUTPUT TO LONG RANGE RADIO 0 0 disable enable Trouble code 1 9 B 11 C 12 D 13 E 14 or F 15 The 2nd digit of Trouble Dialer Report is automatically entered from fie...

Page 3: ... clear entries from field press 42 43 PRIMARY SUBS ACCT Part 1 44 SECONDARY SUBS ACCT Part 1 45 PRIMARY SUBS ACCT Part 2 46 SECONDARY SUBS ACCT Part 2 NOTE If using the paging feature do not enter a leading 0 in the subscriber account number and do not use digits A F anywhere in the number Some paging systems provide voice mail capability which is activated by a leading 0 in the message For fields...

Page 4: ...st Code in field 64 Reports with Partition 1 subscriber No 52 TEST REPORT OFFSET 2 0 24 hour 1 6 hours 2 12 hours 3 18 hours Time to 1st report from programming or downloading 53 SESCOA RADIONICS SELECT 0 0 Radionics 0 9 B F reporting 1 SESCOA 0 9 only reporting Select 0 for all other formats Entry of a number other than one specified will give unpredictable results 56 ZONE ASSIGNMENT ALARM REPORT...

Page 5: ... 24 Hr Audible 08 24 Hr Aux 09 Fire 10 Interior w Delay 20 Arm Stay 21 Arm Away 22 Disarm 23 No Alarm Response 24 Silent Burglary ÊÊDEFAULT VALUES Zn 01 02 03 04 ZT 09 01 03 03 Zn 05 06 07 08 99 ZT 03 03 03 03 06 P PARTITION No 1 or 2 Default Values for zones 01 08 1 RC ALARM REPORT CODE Two Hex Digits For each Hex Digit enter 00 09 for 0 9 10 for A 11 for B 12 for C 13 for D 14 for E 15 for F If ...

Page 6: ...ETUP 80 93 80 OUTPUT RELAYS AND POWERLINE CARRIER DEVICES 81 ZONE LISTS FOR OUTPUT DEVICES Program only if Relays and or Powerline Carrier devices are to be used See next page 82 CUSTOM ALPHA EDITING Also entered from field 56 See procedure in instructions 83 SEQUENTIAL LEARN MODE Also entered from field 56 See procedure in instructions 89 EVENT LOG 80 FULL RPT CODE 90 EVENT LOGGING 3 0 None 1 Ala...

Page 7: ... No Response 1 Close for 2 sec 2 Close and stay closed 3 Pulse on and off EVÊ EVENT 0 Not used 1 Alarm 2 Fault 3 Trouble Z L ZONE LIST 1 2 or 3 from Field 81 or 0 Not Used START ZONE LIST Upon alarm fault or trouble of ANY zone on this list device action will START STOP RESTORE of ZONE LIST Upon restore of ALL zones on this list device action will STOP It need not be same list as used for START NO...

Page 8: ...er approximately 4 seconds This will revert to READY in appx 1 minute which allows PIRS etc to stabilize To bypass this delay press 0 If E4 or E8 appears more zones than the expansion units can handle have been programmed Correct the programming and then completely de power and re power the control to clear this indication and remove the disable indication TO ENTER PROGRAMMING MODE 1 POWER UP then...

Reviews: