L120
Issue B
Oct 1999
Page 2 of 2
• Swipe the MAX with Program Master Card — LEDs 6 and 1
switch on indicating Door Unlock Time Mode.
Note:
If the Door Open Time is programmed to zero (0)
seconds, then the alarm does not activate when the door
is forced open or remains open.
7.
Door Unlock Time: This is the period, following the user card
swipe, that the door strike is activated (unlocked) allowing ac-
cess to be gained without creating an alarm (default three sec-
onds).
To program the time, swipe the MAX with any valid user card;
each swipe increases the Door Unlock Time by one second. For
example, 20 swipes sets a Door Unlock Time of 20 seconds.
The Door Unlock Time can be programmed within the range 1
– 255 seconds: the default is set to 2 seconds.
8.
Exit Programming Mode: Swipe the MAX with the Program
Master Card — LED 6 switches off and LED 2 switches on
(normal operating mode).
Note:
While in the Programming Mode, if 60 seconds elapse
without a valid card being presented, then the programming
is aborted and the MAX returns to the normal operating
mode. All programming prior to the abort is retained in the
MAX memory.
Block Deleting All Cards
All of the cards (including the Program Master) can be removed
from the MAX memory in a single operation:.
1.
Swipe the MAX with Void Master Card — LEDs 2 and 4 switch
on.
2.
Swipe the MAX with the Program Master Card — LEDs 2, 4
and 6 switch on.
3.
Swipe the MAX with the Program Master Card — LED 5 flashes
and the buzzer sounds briefly; LEDs 2 to 5 switch on indicating
that the MAX is in Sleep Mode and waiting for a new Program
Master Card to be assigned.
Note:
All of the cards are now voided from the MAX memory.
The first card presented to the MAX is initialised as the
Program Master Card.
4.
Swipe the MAX with any card LEDs 3–6 switch off; LED 2
remains on — indicating normal operating mode. This card is
now the Program Master Card.
Block Deleting All User Cards
All of the user card can be removed from the MAX memory in a
single operation:.
1.
Swipe the MAX with Void Master Card — LEDs 2 and 4 switch
on.
2.
Swipe the MAX with the Program Master Card — LEDs 2, 4
and 6 switch on.
3.
Swipe the MAX with any valid user card — LED 5 flashes and
the buzzer sounds briefly; LEDs 2 switches on indicating that
normal operating mode is restored.
Note:
All of the user cards are now voided from the MAX
memory.
Troubleshooting
Programming Mode cannot be accessed when Program Master
Card is presented:
• Card presented is not the Program Master; a new Program Mas-
ter may have been assigned.
• The MAX is nightlocked; present a Nightlock Master Card to
restore normal operating mode.
Blank card can not be assigned to the system:
• The MAX is not in Programming or Add Card Mode
• The MAX memory is full; 475 cards have been assigned. Use
the Void Master Card or the hand held programmer to remove
cards that are no longer required.
New Programming Card cannot be assigned in Programming
Mode:
• Card has already been assigned to the system as a master; only
blank cards or standard user cards can be assigned as nightlock
access users.
Card cannot be assigned as an Add, Void or Nightlock Master or
as a standard user card:
• Card has already been assigned to the system; only blank cards
can be assigned.
• No valid user cards have been presented to the MAX for 60
seconds; the MAX has timed-out and normal operating mode
has been restored.
Card cannot be voided (removed):
• The card has been assigned as a master card; master cards can
only be removed by completely erasing the MAX program
memory.
• The card is a blank card; only standard user or nightlock access
user cards can be removed.
Card cannot be assigned as a nightlock access user card:
• Card has already been assigned to the system as a master; only
blank cards or standard user cards can be assigned as nightlock
access users.
The user card cannot gain access to the system:
• The card is not a valid user card.
• The system is nightlocked; standard user cards cannot gain ac-
cess.
LED 1 (green) flashes and buzzer is active on power up:
• The contact terminator is not connected to 0 V through the door
contact; the MAX is in an alarm condition.
The alarm is not activated when the door is forced open or is left
open indefinitely following access:
• The Door Open Time is programmed as zero seconds. Repro-
gram the time to at least one second (two swipes of a valid user
card).
Technical Specifications
Physical
Dimensions: 91 (h) × 78 (w) × 36 (d) mm
Material: 3 mm polycarbonate
Recommended Operating Temperature: –10 to +55°C
Electrical
Power: Nominal 12 Vd.c. (± 2 V)
Current Consumption:
Quiescent:
70 mA
Full Load:
115 mA
Relay:
SPCO
Horn O/P:
Open Collector
Egress:
Normally Open switch
Contact:
Normally Closed door contact