background image

24

LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4

LST700 SERIES FIRE ALARM PANEL

LST700 SERIES CONVENTIONAL FIRE ALARM PANEL

technical specifications

POWER SUPPLY SPECIFICATION

Mains supply voltage

230V 50/60Hz

Mains rated current

350mA maximum

Internal power supply

19V - 28.5V (27 V Nominal).  Ripple 7V maximum (battery fault)

Total output current limited to

1.5A @ 230 Va.c.

Supply and battery charger monitored for failure

YES (battery charger is also temperature compensated)

Batteries monitored for disconnection & failure

YES

Batteries protected against deep discharge

YES (Deep discharge cut off approx. 21 Volts)

Max. battery size and type

2 x 12V 3.3AHr VRLA (Valve Regulated Lead Acid) connected in series

Mains fuse

240V 1A HRC ceramic 20mm compliant with IEC (EN60127 PT2)

Battery fuse

1.6A F 20mm compliant with IEC (EN60127 PT2)

Current draw from battery (Mains failed)

1.5A maximum

DETECTOR CIRCUIT SPECIFICATION

Number of circuits

2,4 or 8 depending on version purchased

Max cable length per circuit

500metres

Line monitored for open circuit and short circuit

YES

End of line

0.68

µ

F, 50V Capacitor

Maximum allowable impedance (each conductor)

20Ω

Maximum cable capacitance

0.27

µ

F

Call point resistor value

470 to 680Ω

Max. number of smoke/heat detectors per zone

40

Compatible detectors

Honeywell TC800 Series Smoke & TC5151 Series Heat Detectors

SOUNDER CIRCUIT SPECIFICATION

Number of circuits

4

End of line resistor value

6800Ω 5% Tol. 0.25W (blue, grey, red, gold)

Each circuit monitored for open and short circuit

YES - indicated by common fault.

Alarm voltage

27V maximum, 20V minimum (final battery voltage)

Sounder circuit fuses

Each circuit protected by resetable fuses (200mA min. hold current; 400mA
max. trip current; Approx. 50mA when tripped. Reset when faults removed)

Maximum total sounder output current to all outputs

4 x 200mA = 800mA

Maximum No. of Bells @ 25 mA

32

Maximum No. of electronic sounders @ 20 mA

40 (Sounders must be polarised)

AUXILIARY OUTPUTS

Type

Non monitored open collector transistor.

Max. sink current

30mA each

Max open circuit voltage

27Vd.c.

Reset output

Active during reset cycle

Remote output

Active during any unsilenced fire condition (provided all relevant delays have expired)

Auxiliary output

Active during any fire condition (provided all relevant delays have expired)

Fault output

Active when no faults are present - failsafe to open circuit

24V aux power output (for use with the above)

This output is protected by a resetable fuse (100mA min. hold current).
Fuse resets when fault removed.

AUXILIARY INPUTS

Class Change (makes sounders sound continuously) Connect to 0V to trigger.  Max input voltage 27V.  (Non-latching).

Alert (makes sounders pulse intermittently)

Connect to 0V to trigger.  Max input voltage 27V.  (Non-latching).

DIMENSIONS

Physical size and weight

Size = 380 x 235 x 96mm appox;  Weight = 1.75kg (without batteries)

OPERATING CONDITIONS

The components are selected to operate within their specification when the environmental conditions outside the enclosure comply
with class 3k5 of IEC  721-3-3 : 1978.   Temperature Range: -5 to +40

0

C.  Maximum relative humidity: 95%

Summary of Contents for LST700 Series

Page 1: ...ES INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002012 Rev 4 LST700 SERIES FIRE ALARM PANEL LST700 SERIES FIRE ALARM CONTROL PANEL installation maintenance manual approved document no DFU7...

Page 2: ...nputs and outputs 13 Programming the Panel 14 An overview of the panel s controls 14 Engineer functions 14 Accessing the engineer controls 16 Programming Coincidence Non latching Zones Delays and Zone...

Page 3: ...tem functions as specified in EN54 A common negative volt line allowing optional three wire connection of detectors and sounders a useful retrofit solution when replacing many older mains based system...

Page 4: ...system design is beyond the scope of this document A basic understanding of general fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent...

Page 5: ...ro static handling precautions are taken immediately prior to handling the panel s PCBs or any other static sensitive components Before handling any static sensitive items operators should rid themsel...

Page 6: ...iver Use of excessive force will damage the enclosure around the knock out Do not drill any additional holes for cable entry in this shaded area as this is where the PCBs and backup batteries will be...

Page 7: ...e standby time of the system and this should be taken into consideration when selecting the standy battery See page 23 for more information Figure 4 Typical detector circuit wring An end of line capac...

Page 8: ...ounder circuits share a common 0V return wire Figure 6 Typical three wire detector sounder circuit wiring The advantages of the three wire method are that it utilises standard system components can so...

Page 9: ...the panel is reset This output does not turn on if the Class Change or Alert inputs are asserted or if the panel s Silence Activate Sounders button is pressed to manually evacuate the building unless...

Page 10: ...gure 9 on page 11 The incoming mains cable should be brought into the panel at the top right hand side of the enclosure and terminated at the connector block CONN1 on the Power Supply PCB Make sure th...

Page 11: ...tery leads supplied in the Panel s accessory pack See below for connection details Battery fuse F2 20 x 5mm 1A6 F to IEC 127 EN60127 Part 2 Do not use any other type or size of fuse in this position P...

Page 12: ...ULT ALERT REM CONN5 CONN6 CONN7 CONN8 CONN9 Z1 DETECTOR CIRCUITS Installing the Main Control PCB The panel s Main Control PCB provides all the connections for the system s detector circuits sounder ci...

Page 13: ...insulated and connected between the nut and washers on the base earth post see inset using eyed crimp connectors as per the detector and sounder circuit examples shown in Figure 12 For a full descript...

Page 14: ...ed information on how to use the general and authorised user controls please refer to the User Manual Log Book Engineer controls access level three The following controls are available to competent se...

Page 15: ...m to be investigated by the user During the delay period the output delays light on the front of the panel pulses to indicate the delay is operative Pressing the SILENCE RESOUND SOUNDERS button will o...

Page 16: ...S LEVEL THREE FUNCTIONS button is pressed for the first time the accessed light will be lit steady and the first function coincidence will be selected and indicated by its yellow light flashing see ri...

Page 17: ...t the Remote Output for editing The output s current status will be shown by the Remote Output Status light in the same way as for the zones 7 If required toggle between the two states by pressing the...

Page 18: ...oms and advice on how to correct the above see page 19 section 1 2 Sounder Fault All sounder circuits are monitored periodi cally for open and short circuit faults unless disabled or in an alarm condi...

Page 19: ...t the Panel If the fault condition clears this confirms there is a wiring fault b Double check and refit the wiring and the end of line capacitor on the zone Trace the fault with consideration for the...

Page 20: ...omatically turn off to avoid damaging the batteries by allowing them to deep discharge The panel will not restart unless fresh fully charged batteries are connected or the mains supply is restored If...

Page 21: ...rol A common symptom of this is the panel s controls locking up Suggested action Press the panel s RESET button and if still in access level three the ESCAPE ACCESS button This should clear the fault...

Page 22: ...he two wires A good circuit will present only the end of line resistor value Any other resistance value shows a fault b If the readings from all sounder circuits are correct take their End of Line res...

Page 23: ...ideline the quiescent current of most modern detectors is typically 0 00005A 50 A and that of manual call points is zero To obtain accurate figures consult the device manufacturers own specifications...

Page 24: ...lue 6800 5 Tol 0 25W blue grey red gold Each circuit monitored for open and short circuit YES indicated by common fault Alarm voltage 27V maximum 20V minimum final battery voltage Sounder circuit fuse...

Reviews: