6.2 Suspension
For typical suspension,
See Page 10, Figure 6
.
When handling or supporting the heater from below,
ensure that the weight is taken at the support points.
The gas or electrical supply lines must not be used
to support the heater.
Do not locate the gas or electrical supply lines
directly over the path of the flue products from the
heater.
The heater must be installed in a location that is
readily accessible for servicing.
The heater must be installed in accordance with
clearances to combustibles as indicated on the
serial plate, wall tag and throughout the manual.
See Page 7, Section 4
.
Figure 6: Suspension Methods
WARNING
Crush Hazard
Use 3/8" threaded rod
minimum.
Failure to follow these
instructions can result in
death, injury or property
damage.
Nut
Washer
Riv
Nut
Ensure all 3/8"-16 threaded
suspension hardware is
torqued to a minimum of
19 ft lbs. (25.8Nm)
Support Points (for use in handling)
3/8"-16
Threaded
Rod
Cone Point
Set Pin
Window
Clamp
Unistrut
Unistrut
3/8"-16
Threaded
Rod
Washer
Nut
Channel Nut
NOTE:
Four suspension
points located on top
of heater. Duct
supports not shown.
Duct supports and
duct are not provided
by manufacturer.
Summary of Contents for UHD150
Page 2: ......
Page 4: ......
Page 8: ......
Page 27: ...SECTION 9 GAS PIPING 19 of 55 Figure 13 Gas Connection...
Page 47: ...SECTION 14 TROUBLESHOOTING 39 of 55 14 1 General...
Page 62: ...UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL 54 of 55...
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......