18 of 49
SECTION
8
: AIR SUPPLY
8
.1 Separated Combustion Installation
When installed as a separated com
bu
stion heater
(UHA[X]S), the air for com
bu
stion is dra
w
n in from
o
u
tside the
bu
ilding. It is important to ens
u
re that
there is adeq
u
ate space aro
u
nd heater to provide air
for the axial air distri
bu
tion fan.
8
.2 Unvented Installation
It is important to ens
u
re that there is adeq
u
ate fresh
air s
u
pply at all times for
b
oth com
bu
stion and
heating req
u
irements in accordance
w
ith local and
national codes.
8
.3 Buildin
g
Ventilation
Where ventilation is req
u
ired, air m
u
st
b
e taken from
an o
u
tside point
w
here it is not likely to
b
e
contaminated or o
b
str
u
cted.
8
.4 Outside Combustion Air Supply
If o
u
tside com
bu
stion air s
u
pply is req
u
ired,
separated com
bu
stion model (UHA[X]S) heaters
m
u
st
b
e
u
sed.
Caution:
If the
bu
ilding has a slight negative
press
u
re or corrosive contaminants s
u
ch as
halogenated hydrocar
b
ons are present in the air, an
o
u
tside com
bu
stion air s
u
pply to the heater is
req
u
ired. Seal all com
bu
stion air pipe joints.
The flexi
b
le air d
u
ct may have to
b
e ins
u
lated to
prevent condensation on the o
u
ter s
u
rface. The
o
u
tside air terminal m
u
st not
b
e more than 1' (31
cm) a
b
ove the vent terminal.
8
.4.1 Len
g
th Re
q
uirements
Follo
w
the constraints listed
on Page 12, Section 7.6
.
WARNING
Explosion Hazard
Equipment must have access to
uncontaminated air at all times.
Failure to follow these instructions can result
in death, injury or property damage.
Summary of Contents for UHA 150
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 44: ...UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 36 of 49 14 1 General...
Page 55: ...SECTION 16 SPECIFICATIONS 47 of 49 SECTION 16 SPECIFICATIONS 16 1 Dimension Data...
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......