ADC RF Wofx User Manual Download Page 15

ADCP-61-813 • Issue 2 • February 2005

Page 9

© 2005, ADC Telecommunications, Inc.

5. Connect two 22–26 AWG wires to the alarm terminals at the rear panel labeled ALARM

NO (normally open) and C (common). (See 

Figure 11

.) The other ends of the wires can be

connected to the user's alarm panel at the installation location.

Figure 11. Terminal Block for Alarm and DC Power Connections

6. Using a modular power cord, connect the switch to a convenient source of AC input

voltage, or (if it is to be powered by direct current) connect the DC terminal block
(

Figure 11

) to –48 V battery power.

7. Check that the front panel (green) NORMAL and (red) FAILURE LEDs are lit, indicating

that the internal power supply is operational. Then proceed to 

Section 5

 to set up and

operate the switch.

4.1

Configuring the RDS-AS for 100 to 120 VAC Operation

The RDS-AS is factory set for –48 VDC or 240 VAC operation, with “230V” showing as the
voltage setting in the power inlet module window (

Figure 12

). To configure the RDS-AS for

100 to 120 VAC operation, perform the following:

1. Make sure the power cord is removed from the power inlet module before continuing.

2. Pry open the power inlet module door from the right side using a small screwdriver or

equivalent.

3. Remove the fuse module using a small screwdriver or equivalent.

4. Rotate the fuse module 180º so that the text “115V” will show through the power inlet

module window when the door is closed.

Note: 

If the total cable length exceeds 1,000 feet, termination per requirements of the

RS485 Card Adapter Specification may be required.

Note: 

The OUT A and OUT B –48 VDC and VAC outlet connectors are not used in this

RDS version. They are left unpowered in all modes of operation.

Warning: 

The RDS-AS is factory set for –48 VDC or 240 VAC operation. For 100/120 VAC

operation, refer to 

Section 4.1

, Configuring The RDS-AS for 100 to 120 VAC Operation.

Note: 

The RDS-AS is supplied with a detachable power cord for 120 VAC operation. For

240 VAC operation, consult your local electrical code for the correct type or style of power
cords required.

12363-A

1A  MAX

 

48DC

IN         OUT   A    OUT  B

ALARM

NO

C

Summary of Contents for RF Wofx

Page 1: ...Worx Dual A B Switch with Automatic Switchback User Manual OPERATING CALIBRATION NORM AL SW ITCHING THRESHOLD R B A MANUAL FAILURE SELECT SELECT STATUS 12213 A 2A 24 0V V 38 4 5 7 6 VD C 10 0 12 0 24...

Page 2: ...use or loss of profits and ADC further disclaims any and all liability for indirect incidental special consequential or other similar damages This disclaimer of liability applies to all products publi...

Page 3: ...al Configuration 2 3 SPECIFICATIONS 5 4 INSTALLATION 6 4 1 Configuring the RDS AS for 100 to 120 VAC Operation 9 5 SETUP AND OPERATION 10 5 1 Setup 10 5 1 1 Calibration 11 5 1 2 Setting The Threshold...

Page 4: ...ADCP 61 813 Issue 2 February 2005 Preface Page iv 2005 ADC Telecommunications Inc TABLE OF CONTENTS Content Page Blank...

Page 5: ...ts in the form of Dangers Warnings and Cautions must be followed at all times These warnings are flagged by use of the triangular alert icon seen below and are listed in descending order of severity o...

Page 6: ...ADCP 61 813 Issue 2 February 2005 Preface Page vi 2005 ADC Telecommunications Inc Blank...

Page 7: ...ear panel All operating controls and indicators are on the front panel Figure 1 Automatic Redundant Switch RDS AS 1 1 Graphical User Interface SWatch Switch Monitoring Software Optional A SWatch GUI s...

Page 8: ...m for Dual A B Switch Mode Operation 2 1 Atypical Configuration Figure 3 details a split system on the A side with one receiver carrying the lower frequency CATV signals and the other receiver carryin...

Page 9: ...which each port 1 or 2 will switch Displays the start up sequence status B SWITCHING THRESHOLD toggle switch Selects the port that will be used Adjusts threshold for the active port C CHANNEL A LED Wh...

Page 10: ...ng LED Serves no purpose with this model L FAILURE LED When lit shows that channel A is below thresholdWhen blinking shows that the signal has returned from a failed state and the unit is waiting 15 s...

Page 11: ...al at 750 MHz Composite Triple Beat CTB 67dBc min 110 channels Composite Second Order CSO 67dBc min 110 channels Dynamic Range 20 dB Narrowcast 28 to 47 34 to 46 Port 1 8 channels Port 2 8 channels 25...

Page 12: ...lay contacts normally open ENVIRONMENTAL Temperature Operating 0 C to 50 C 32 F to 122 F Temperature Storage 40 C to 70 C 40 F to 158 F Humidity Operating 10 to 90 No condensation Humidity Storage 5 t...

Page 13: ...rack with four 12 24 screws See Figure 8 Figure 8 Installing Redundant Switch in Rack 2 Using AWG 18 or larger stranded wire connect frame ground to the frame ground screw in the lower left corner of...

Page 14: ...personal computer PC with switch monitoring software to the RS 485 IN and OUT connectors on the rear panel of the switch This connection can be via a daisy chain to from other switch panels See Figure...

Page 15: ...Figure 12 To configure the RDS AS for 100 to 120 VAC operation perform the following 1 Make sure the power cord is removed from the power inlet module before continuing 2 Pry open the power inlet mod...

Page 16: ...a lower case C will be displayed for one minute The C will immediately disappear if communication with the Swatch switch monitoring software is established In rare instances an A or B may show continu...

Page 17: ...oggle switch The threshold set in this mode of operation will be the level below which the calibrated signal must drop before switching from the primary to standby receiver amplifier For example if re...

Page 18: ...ry input channel A is detected the system monitors that signal for a full 15 seconds before switching back to channel A During this time the red FAILURE LED on the front panel will blink to indicate t...

Page 19: ...es described in Section 5 6 MAINTENANCE Maintenance requirements of the redundant amplifier switch are minimal consisting merely of periodic cleaning 6 1 Preventive Maintenance The outside of the redu...

Page 20: ...reless Extension 73476 ASIA PACIFIC Sales Administration 65 6294 9948 Technical Assistance 65 6393 0739 ELSEWHERE Sales Administration 1 952 938 8080 Technical Assistance 1 952 917 3475 Italy 0800 782...

Page 21: ......

Page 22: ...i www adc com...

Reviews: