Chapter 2: Installation
LTPH-UM-1261-01
2-9
B
ONDING
(S
AFETY
) G
ROUND
, P
OWER
AND
F
RAME
G
ROUND
, A
LARM
,
AND
O
PTIONAL
F
AN
I
NPUTS
Bonding (safety) ground, power and frame ground, and alarm connections and cabling are marked for ease of
installation [see ground lug location (labeled BONDING WIRE MIN #10 AWG)], TB1, and TB2 on the rear panel of
the HMS-318 List 3 Shelf, and the following procedures for proper safety ground, power, alarm, and optional fan
(alarms) connections (see
Figure 1-2 on page 1-3
).
Bonding (Safety) Ground Procedure
To connect the Bonding (Safety) ground to the HMS-318 List 3 Shelf, complete the following steps:
!
IMPORTANT
Before making connections to the HMS-318 List 3 shelf, ensure that the Main CO power breaker
is off. Otherwise, severe injury to the installer or damage to the unit may result.
Note:
The ground wire exiting the HMS-318 List 3 Shelf is terminated with a ground lug. The lug can be
either a one-hole or two-hole lug. The surface of the lug that connects to the HMS-318 List 3 Shelf should
be cleaned with an antioxidant. The same should also be applied to the surface of the telco-style rack where
the connection is to be made. The #12 Hexhead screw (supplied) is used to connect the grounding lug to
the HMS-318 List 3 Shelf.
Summary of Contents for HiGain HMS-318 List 3
Page 4: ...Table of Contents December 20 2004 iv LTPH UM 1261 01...
Page 6: ...List of Figures December 20 2004 vi LTPH UM 1261 01...
Page 8: ...List of Tables December 20 2004 viii LTPH UM 1261 01...
Page 28: ...Chapter 1 Product Description December 20 2004 1 16 LTPH UM 1261 01...
Page 50: ...Appendix B Standard PIC Color Code December 20 2004 B 2 LTPH UM 1261 01...
Page 56: ...Appendix E Product Support December 20 2004 E 2 LTPH UM 1261 01...