ADC ES35/35 Installation & Operator'S Manual Download Page 18

18

American Dryer Corp.

WFR 112807 - 15

Gas Pressure Testing _________________

For proper operation, the gas pressure must be correct,
consistent and maintained at the gas pressure rates shown
on page

 

14.  Provisions are made at the gas valve for taking

gas pressure readings.

There are two types of devices used to measure gas
pressure.  They are the spring/mechanical type gauge and
the manometer.  The use of the spring/mechanical type
gauge is not recommended because they are very easily
damaged and are not always accurate.  The preferred type
of gauge is the manometer because it is a simple device to
use and is highly accurate.  A manometer is simply a glass
or transparent plastic tube with a scale graduated in inches
or millibars.  When it is filled with water and pressure is
applied, the water in the tube rises, showing the exact gas
pressure.

Gas Pressure Test Procedure

Turn gas cock in gas supply line to “OFF” position.

60 Hz dryers: Install pressure tap and attach manometer
(refer to the illustration on page

 

16).

Turn gas cock to “ON” position.

Start the dryer in Heat Mode and wait for ignition.  Gas
manifold pressure should be as shown on page

 

14.

If the gas pressure needs to be adjusted, refer to “Gas
Pressure Adjustment” on page

 

17.

Once test is complete, turn gas cock to “OFF” position.
Remove manometer.  Tighten screw inside the pressure
tap or install plug.

Turn gas cock to “ON” position and check for leaks with
soap solution with main burner “ON.”

Water Information ____________________

Before You Start

Check Local Codes and Permits

Call your local water company or the proper municipal
authority for information regarding local codes.

IMPORTANT: 

It is your responsibility to have all plumbing

connections made by a qualified professional to ensure
that the plumbing installation is adequate and conforms to
local, state, and federal regulations or codes.

It is the installer’s or owner’s responsibility to see that the
required water pressure, pipe size, or connections are
provided.  The manufacturer assumes no responsibility if
the fire suppression system is not connected, installed, or
maintained  properly.

Installation
Water Supply

The fire suppression system must be supplied with a
minimum water pipe size of 1/2-inch (12.7 mm) and be
provided with 40 psi +/- 20 psi (2.75 bar +/- 1.37 bar) of
pressure.

If the rear area of the dryer or the water supply is located in
an area where it will be exposed to cold/freezing
temperatures, provisions must be made to protect these
water lines from freezing.

!

 WARNING

If the water in the supply line or water solenoid valve
freezes, the fire suppression system will be
inoperative!!

Water Connections

The water connection is made to the 3/4”-11.5 NH hose
adaptor, which is shipped in the tumbler and must be
installed to the 1/2” N.P.T. water connection, located at the
upper rear of the dryer.  A flexible supply line/coupling must
be used in an effort to avoid damaging the electric water
solenoid valve.

NOTE: 

The 3/4”-11.5 NH is a standard hose coupling

screw thread.  It is not to be confused with 3/4” N.P.T.  The
sealing of an NH connection is made with a washer
opposed to the mating threads of an N.P.T. assembly.  The
2 thread designs are not compatible.

It is recommended that a filter or strainer be installed in the
water supply line.

IMPORTANT: 

Flexible supply line/coupling must be used.

Solenoid valve failure due to hard plumbing connections
will void warranty.

The dryer is to be connected to the water mains using a
new hose set and the old hose set should not be reused.

Optional Manual Bypass

Provisions are made in the dryer’s fire suppression system
for the installation of an optional manual bypass.  The
connections for the manual bypass are made at the “cross”
or “four way” fitting located in the outlet supply side of the
water solenoid valve.  The manual ball cock shutoff valve
must be located outside of the dryer at a distance from the
dryer where it is easily accessible.  The use and connection
of this manual bypass is at the option or discretion of the
owner.

The water connection for the manual bypass is made to the
“cross” or “four way” fitting, which has a 3/8” F.N.P.T. and a
coupling must be used to provide the minimum 1/2-inch
(12.7 mm) supply (feed) line.

Electrical Requirements

No independent external power source or supply connection
is necessary.  The 24-volt power to operate the fire
suppression system is accomplished internally in the dryer
(from the dryer controls).

!

 WARNING

Electrical power must be provided to the dryer at all
times.  If the main electrical power supply to the dryer
is disconnected, the fire suppression system is
inoperative!!

Summary of Contents for ES35/35

Page 1: ...rnisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incendies L installation et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explos...

Page 2: ...t your order is processed accurately and promptly These instructions are only valid if the following country code is on the appliance If this code is not present on the appliance it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of the appliance to the condition of use for the country In accordance with EN ISO 3166 1 the...

Page 3: ...oor switch es lint door drawer switch es or heat safety circuit s ever be disabled DO NOT MODIFY THIS APPLIANCE The dryer must never be operated with any of the back guards outer tops or service panels removed Personal injury or fire could result The dryer must never be operated without the lint filter screen in place even if an external lint collection system is used If the hi limit switch trips ...

Page 4: ...oil constitute a fire hazard and should not be placed in a tumble dryer Do not dry mop heads Contamination by wax or flammable solvents will create a fire hazard WARNING Do not use heat for drying articles that contain plastic foam sponge rubber or similarly textured rubber materials Drying in a heated tumbler may damage plastics or rubber and also may be a fire hazard The possible presence of res...

Page 5: ...4 C and 130 F 54 44 C The operation of this appliance may affect the operation of other types of gas appliances which take their air for safe combustion from the same room If in doubt consult the appliance manufacturer s Use this dryer only for its intended purpose drying fabrics The cool down cycle of tumble dryers should be used to reduce the temperature of the items They should not be removed f...

Page 6: ...ION PER POCKET 1 2 M N P T 3 8 M B S P T CE and Australia Only VOLTAGE AVAILABLE 200 416V 1 3ø 2 3 4w 50 60 Hz APPROXIMATE NET WEIGHT 600 lb 272 16 kg APPROXIMATE SHIPPING WEIGHT 630 lb 285 76 kg AIRFLOW PER POCKET 60 Hz 380 cfm 10 76 cmm 50 Hz 320 cfm 9 06 cmm EXHAUST CONNECTION DIAMETER PER POCKET 6 15 24 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE PER POCKET kW Btu hr k...

Page 7: ... adclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Page 8: ... exhaust venting can be achieved as noted in this manual refer to Exhaust Requirements section IMPORTANT The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber CAUTION This dryer produces combustible lint and must be exhausted to the outdoors Every 6 months inspect the ...

Page 9: ...30 and or 45 bends instead The radius of the elbows should preferably be 1 1 2 times the diameter of the duct All ductwork should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint When adding ducts overlap the duct being connected All ductwork joints must be taped to prevent moisture and lint from escaping into the building Back draft damper...

Page 10: ... A 12 feet 3 66 meters B 8 inches 20 32 cm The length of the ductwork from the dryer to the outside exhaust outlet must not exceed 12 feet 3 66 meters The minimum diameter of this ductwork must be at least 8 inches 20 32 cm even though the dryer exhaust duct connection is smaller Including tumbler dryer elbow connections or elbows used for outside protection from the weather no more than 4 90 elbo...

Page 11: ... one of two power sources supplying a dryer The dryer must be connected to the electric supply shown on the data label In the case of 208 VAC or 230 240 VAC the supply voltage must match the electric service specifications of the data label exactly The wire size must be properly sized to handle the related current WARNING 208 VAC and 230 240 VAC are not the same Any damage done to dryer components...

Page 12: ...20 1ø 2 11 3 54 2 70 230 1ø 2 8 3 41 3 60 230 1ø 2 12 4 59 1 80 240 1ø 2 9 0 42 7 60 240 1ø 2 13 5 61 5 61 3 80 208 3ø 3 13 5 43 3 60 220 3ø 3 11 3 35 3 50 230 3ø 3 12 4 36 5 50 240 3ø 3 13 5 37 7 50 380 3ø 4 11 3 22 8 30 380 3ø 3 4 11 3 22 6 30 400 3ø 3 4 12 4 23 1 30 416 3ø 3 4 13 5 23 7 30 CAUTION The dryer must be grounded A ground lug has been provided for this purpose Input connection wiring...

Page 13: ...s indicated on the data label and pressure must be confirmed If this information does not agree with the type of gas available do not operate the dryer Contact the reseller who sold the dryer or contact the manufacturer The input ratings shown on the data label are for elevations up to 2 000 feet 610 meters unless elevation requirements of over 2 000 feet 610 meters were specified at the time the ...

Page 14: ...Propane I3P 2 500 28 30 50 55 000 16 12 1 161 kg H 44 2 184 1 24 9 Heat Input Gas Consumption Orifice Injector Data Shaded areas are stated in metric equivalents Gas valve s internal regulator disabled Information is per pocket tumbler Consult factory for elevations over 2 000 feet 610 meters for correct orifice size WARNING CE Dryers Only This appliance must only be operated with the gas type ind...

Page 15: ... vary depending on the distance this line travels from the gas meter or in the case of propane gas the supply tank other gas operated appliances on the same line etc Specific information regarding supply line size should be determined by the gas supplier NOTE Undersized gas supply piping can create a low or inconsistent pressure which will result in erratic operation of the burner ignition system ...

Page 16: ...disconnect the union three electrical plugs and the gas train mounting screws from the burner Carefully slide the gas train out of the gas train enclosure The carbon ignitor located at the far end of the gas train is very fragile Remove two burner tube mounting screws and remove burner tube in order to gain access to the orifice Using a 3 8 wrench or socket remove the existing orifice and replace ...

Page 17: ...move the white plastic regulator adjustment screw under vent cap Remove spring under screw and replace with spring from kit ADC P N 140415 Replace regulator adjustment screw Install the gas train back into the dryer gas train enclosure Be sure the tab at the rear of the gas train engages into the mounting slot Connect the union and the three electrical plugs Repeat these steps for the other burner...

Page 18: ...ater pipe size of 1 2 inch 12 7 mm and be provided with 40 psi 20 psi 2 75 bar 1 37 bar of pressure If the rear area of the dryer or the water supply is located in an area where it will be exposed to cold freezing temperatures provisions must be made to protect these water lines from freezing WARNING If the water in the supply line or water solenoid valve freezes the fire suppression system will b...

Page 19: ...NG When a gas dryer is first started during initial start up it has a tendency not to ignite on the first ignition attempt This is because the gas supply piping is filled with air so it may take a few minutes for the air to be purged from the lines NOTE During the purging period check to be sure that all gas shutoff valves are open A gas pressure test should be taken at the gas valve pressure tap ...

Page 20: ...e dryer s model number and serial number available so that your inquiry can be handled in an expeditious manner Returning Warranty Parts All dryer or parts warranty claims or inquiries should be addressed to the Warranty Parts Department To expedite processing the following procedures must be followed Select temperature by pressing HI MED or LO The cycle will start and the L C D will display the D...

Page 21: ...ing and removal of lint from various areas of the dryer as well as throughout the ductwork system The frequency of cleaning can best be determined from experience at each location Maximum operating efficiency is dependent upon proper airflow The accumulation of lint can restrict this airflow If the guidelines in this section are met the dryer will provide many years of efficient trouble free and m...

Page 22: ...he lint drawer holding down the lint drawer catch brackets which must be removed Once they are removed the drawer will be able to be pulled completely out of the machine To reinstall put the lint drawer back into the machine line up the lint drawer catch brackets with the screws and tighten them down The accumulation of lint in the exhaust ductwork can create a potential fire hazard Do not obstruc...

Page 23: ...coin 1 input E8 This indicates a bad coin pulse was detected on coin 2 input E9 EB Upper Lower forward pocket rotation fault count EA EC Upper Lower reverse rotation fault count ED S A F E DISABLED Water not connected Factory Settings Definitions RADIANT TIMEOUT During an attempt to start the burner this parameter sets the maximum wait time for the radiant sensor to cool and close circuit A failur...

Page 24: ...WFR112807 15 06 05 18 ...

Reviews: