Fresh Air Supply Requirements _______

This appliance may only be installed in a room that meets
the appropriate ventilation requirements specified in the
national installation regulations.
When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of the
building.  Therefore, the room air must be continually
replenished from the outdoors.  If the make-up air is
inadequate, drying time and drying efficiency will be adversely
affected.  Ignition problems and sail switch “fluttering”
problems may result, as well as premature motor failure from
overheating.  The dryer must be installed with provisions for
adequate combustion and make-up air supply.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  Fresh air
ventilation openings shall not be blocked and/or sealed.  As
a general rule, an unrestricted air entrance from the outdoors
of 105 inch

2

 (678 cm

2

).  (Based on 1 inch

2

 [6.5 cm

2

] per 1,000

Btu [252 kcal].)
It is not necessary to have a separate make-up air opening
for each dryer.  Common make-up air openings are
acceptable.  However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.

Exhaust Requirements ________________

Exhaust ductwork should be designed and installed by a
qualified professional.  Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airflow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat.  The dryer must be installed with a proper
exhaust duct connection to the outside.

CAUTION: This dryer produces combustible lint and must
be exhausted to the outdoors.
Improperly sized or installed exhaust ductwork can
create a potential fire hazard.

The ductwork should be laid out in such a way that the
ductwork travels as directly as possible to the outdoors with
as few turns as possible.  There should be a minimum
6-inch (15.24 cm) clearance between the back guard and the
first bend in the ductwork for ease of servicing.  Single or
independent dryer venting is recommended.  It is suggested
that the use of 90° turns be avoided; use 30° and/or 45°
bends instead.  The radius of the elbows should preferably
be 1-1/2 times the diameter of the duct.  All ductwork should
be smooth inside with no projections from sheet metal
screws or other obstructions, which will collect lint.  When
adding ducts, overlap the duct being connected.  All ductwork
joints must be taped to prevent moisture and lint from
escaping into the building.  Back draft dampers must be
installed in all commonly ducted systems.  Inspection doors
should be installed at strategic points in the exhaust ductwork
for periodic inspection and cleaning of lint from the ductwork.

IMPORTANT: 

It is recommended that exhaust or booster

fans not be used in the exhaust ductwork system.
Exhaust back pressure measured by a manometer/
magnehelic in the exhaust duct must be no less than 0 and
must not exceed 0.6 in WC (1.48 mb).

NOTE:

 When the exhaust ductwork passes through a wall,

ceiling, or roof made of combustible materials, the opening
must be 2-inches (5.08 cm) larger than the duct (all the way
around).  The duct must be centered within this opening.
As per the National Fuel Gas Code, “Exhaust ducts for type
2 clothes dryers shall be constructed of sheet metal or
other noncombustible material.  Such ducts shall be
equivalent in strength and corrosion resistance to ducts
made of galvanized sheet steel not less than 26 gauge
(0.0195-inches [0.50 mm]) thick.”

The ductwork for this appliance must be suitable for the
appliance category in accordance with national installation
regulations of the country of destination.

A = 14-inches (35.56 cm)

B = 15-inches (38.1 cm)

EXAMPLE: For a bank of 4 dryers, 2 unrestricted openings
measuring 14-inches by 15-inches (35.56 cm by 38.1 cm)
are acceptable.
To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%.  Make-up air openings should not be located in an area
directly near where exhaust vents exit the building.
Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.

IMPORTANT: 

Make-up air must be free of dry cleaning

solvent fumes.  Make-up air that is contaminated by dry
cleaning solvent fumes will result in irreparable damage to
the motors and other dryer components.

NOTE:

 Component failure due to dry cleaning solvent

fumes will void the warranty.

Summary of Contents for ES30/30

Page 1: ...urnisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incendies L installation et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explo...

Page 2: ...____________________________________________________ _______________________________________________________________________________________________________ Replacement parts can be obtained from your reseller or the ADC factory When ordering replacement parts from the factory you can FAX your order toADC at 1 508 678 9447 or telephone your order directly to theADC Parts Department at 1 508 678 90...

Page 3: ...cleaning fumes The dryers must not be installed or stored in an area where it will be exposed to water and or weather Thewiringdiagramforthedryerislocatedbehindthecontrol panel List of Acronyms _______________________ HVAC Heating Ventilating and Air Conditioning in WC Inches of Water Column L C D Liquid Crystal Display L P Liquid Propane OSHA Occupational Safety and Health Administration R M A Re...

Page 4: ...that contain plastic foam sponge rubber or similarly textured rubber materials Drying in a heated tumbler may damage plastics or rubber and also may be a fire hazard The possible presence of residual quantities of aggressive or decomposed chemicals in the load may produce damage to the machine and harmful fumes A program should be established for the inspection and cleaning of lint in the burner a...

Page 5: ...____________________________________________________________ _____________________________________________________________ _____________________________________________________________ _____________________________________________________________ _____________________________________________________________ The cool down cycle of tumble dryers should be used to reduce the temperature of the items ...

Page 6: ...6 15 24 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T 3 8 M B S P T CE and Australia Only VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW PER POCKET EXHAUST CONNECTION DIAMETER PER POCKET COMPRESSED AIR CONNECTION COMPRESSED AIR VOLUME OVEN SIZE PER POCKET kW Btu hr kcal hr VOLTAGE AVAILABLE N A APPROXIMATE ...

Page 7: ...claundry com 7 Specifications _______________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Page 8: ... venting can be achieved as noted in this manual refer to Exhaust Requirements section IMPORTANT The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber CAUTION This dryer produces combustible lint and must be exhausted to the outdoors Every 6 months inspect the exhaust ...

Page 9: ...ested that the use of 90 turns be avoided use 30 and or 45 bends instead The radius of the elbows should preferably be 1 1 2 times the diameter of the duct All ductwork should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint When adding ducts overlap the duct being connected All ductwork joints must be taped to prevent moisture and lint fro...

Page 10: ... this ductwork must be at least 8 inches 20 32 cm even though the dryer exhaust duct connection is smaller Including tumbler dryer elbow connections or elbows used for outside protection from the weather no more than four 90 elbows should be used in the exhaust duct run If more than the equivalent of four 90 elbows are used the cross sectional area of the ductwork must be increased Multiple Dryer ...

Page 11: ...lation If the nominal voltage is outside of the medium tolerances shown on the diagram below adjust the autotransformers located near the burner TERM LINE VOLTAGE 50 Hz 60 Hz HIGH 260 226 283 249 MED 239 208 260 230 LOW 217 189 236 208 10 20 14 Electric Models Only All electrically heated dryers must be connected to the electric service shown on the dryer s data label The connecting wires must be ...

Page 12: ...ded in this box To gain access the service box cover must be removed Gas and Steam Models Only 120 240V Application with Neutral Input connection wiring must be sized properly to handle the dryer s current draw This information is printed on the dryer s data label IMPORTANT A strain relief must be used where the input wiring enters the oven assembly Electrically Heated Models Only The electrical i...

Page 13: ...d If this information does not agree with the type of gas available do not operate the dryer Contact the reseller who sold the dryer or contact the manufacturer The input ratings shown on the data label are for elevations up to 2 000 feet 610 meters unless elevation requirements of over 2 000 feet 610 meters were specified at the time the dryer order was placed with the factory The adjustment or c...

Page 14: ... liquid detergent works well Warning Never test for leaks with a flame Converting from One Family of Gas to Another ______________________ Warning CE Dryers This appliance must only be operated with the gas type indicated on the dryer s data plate If the appliance is converted gas type changed a data plate amendment must be obtained from American Dryer Corporation dryer s serial number is required...

Page 15: ...he cap with blocking pin and install the regulator vent cap from the kit ADC P N 140415 Converting from unregulated L P to unregulated natural gas no change to the regulator is required Converting from regulated L P to regulated natural gas remove the white plastic regulator adjustment screw under vent cap Remove spring under screw and replace with spring from kit ADC P N 140415 Replace regulator ...

Page 16: ... steam will cause water hammer and subsequent heat exchanger failure The steam supply connection must be taken from the top of a well dripped steam main If the supply run out to the dryer exceeds 25 feet 7 6 meters it should be dripped just before the control valve with a proper trap and dirt pocket IMPORTANT Failure to comply with the requirements stipulated in this manual can result in component...

Page 17: ...ryer must include a 12 inch 30 48 cm riser along with a drip trap and check valve This will prevent any condensate from entering the steam coil Flexible hoses or couplings must be used The dryer vibrates slightly when it runs and this will cause the steam coil connections to crack if they are hard piped to the supply and return mains Shutoff valves for each dryer should be installed in the supply ...

Page 18: ...e at the cross or four way fitting located in the outlet supply side of the water solenoid valve The manual ball cock shutoff valve must be located outside of the dryer at a distance from the dryer where it is easily accessible The use and connection of this manual bypass is at the option or discretion of the owner The water connection for the manual bypass is made to the cross or four way fitting...

Page 19: ...rt XX XX amount to Start Insert coin s Once the correct Amount to Start has been inserted the L C D will display Select Temperature Select temperature by pressing HI MED or LO The cycle will start and the L C D will display the Dry Cycle selected and the remaining time The dryer will continue through the drying and cooling cycles until the vended time has expired NOTE To stop the dryer open main d...

Page 20: ...e factory for warranty information be sure to have the dryer s model number and serial number available so that your inquiry can be handled in an expeditious manner Returning Warranty Parts All dryer or parts warranty claims or inquiries should be addressed to the Warranty Parts Department To expedite processing the following procedures must be followed No parts are to be returned without prior wr...

Page 21: ...eekly Clean lint accumulation from lint chamber thermostat and microprocessor temperature sensor area Warning To avoid the hazard of electrical shock discontinue electrical supply to the dryer Steam Dryers Clean the steam coil fins It is suggested that compressed air and a vacuum cleaner with brush attachment be used Warning When cleaning steam coil fins be careful not to bend the fins If fins are...

Page 22: ...l Number Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular dryer gas either natural gas or L P gas electric or steam 4 Heat Input For Gas Dryers This describes the heat input in British thermal units per hour Btu hr or kilowatts kW 5 Orifice Size For Gas Dryers Gives the number drill size used 6 Electric Servic...

Page 23: ...oin 1 input E8 This indicates a bad coin pulse was detected on coin 2 input E9 EB Upper Lower forward pocket rotation fault count EA EC Upper Lower reverse rotation fault count ED S A F E DISABLED Water not connected Factory Settings Definitions RADIANT TIMEOUT During an attempt to start the burner this parameter sets the maximum wait time for the radiant sensor to cool and close circuit A failure...

Page 24: ...ADC Part No 112809 6 10 21 14 ...

Reviews: