c) Flame Failure “Reignition”

If the established flame signal is lost while the burner is operating, the HSI module
(controller) will respond within 0.8 seconds.  The gas valve will be de-energized, the
HSI module resets and starts a new ignition sequence in an attempt to relight the
burner.  If the burner 

does not

 light, the HSI module will de-energize the gas valve.

The HSI module will make two (2) more attempts to relight the burner.  If the burner

does not

 relight the HSI module will go into the LOCKOUT MODE.  If the flame is

reestablished, normal operation resumes.

d ) Fault Conditions

The “

red

” L.E.D. (light emitting diode) will flash on for a 1/4 second, then off for a

1/4 second during a fault condition.  The pause between the fault codes is three (3)
seconds.

NOTE

: To reset the HSI MODULE if it is in the LOCKOUT MODE or the FLAME

SENSOR FAULT MODE, open and close the main door then restart the dryer.

3) HSI (Hot Surface Ignition) Module

The HSI module (controller) utilizes a microprocessor to continually and safely
monitor , analyze, and control the proper operation of the gas burner.  Additional
features consist of L.E.D. diagnostics, automatic one (1) hour reset, multiple tries, and
flame current testing pins highlight the HSI module benefits.

The terminal designation that are listed below correspond to the designations on the
bottom portion of the HSI module (as shown from left to right).

TERMINAL DESIGNATIONS

FC1/FC2 ......... F

LAME

  S

ENSOR

  C

URRENT

  C

HECK

 P

OINTS

S1 .................... I

GNITOR

L1 .................... 24 V

OLT

 I

NPUT

 (HOT)

L2 .................... NOT USED (N

EUTRAL

 - 120

V

 I

NPUT

  O

NLY

)

S2 .................... I

GNITOR

 R

EMOTE

  S

ENSOR

/F

LAME

  S

ENSOR

W ..................... T

HERMOSTAT

 I

NPUT

MV1 ................ M

AIN

 V

ALVE

 P

OWER

GND ............... System Ground

FAULT CONDITION INDICATIONS

E

RROR

  M

ODE

L.E.D. I

NDICATION

I

NTERNAL

 HSI  M

ODULE

 F

AILURE

S

TEADY

  O

N

F

LAME

  S

ENSOR

 F

AULT

2 F

LASHES

I

GNITION

 LOCKOUT

3 F

LASHES

Summary of Contents for ADG-530

Page 1: ...ace Ignition System Technical Manual American Dryer Corporation 88 Currant Road Fall River MA 02720 4781 USA Telephone 1 508 678 9000 Fax 1 508 678 9447 e mail techsupport amdry com www amdry com ADC...

Page 2: ...evices ever be disabled WARNING The dryer must never be operated with any of the back guards outer tops or service panels removed PERSONAL INJURY or FIRE COULD RESULT NOTE The wiring diagram for the d...

Page 3: ...ation contained herein may have been up dated ADC RESERVES THE RIGHT TO MAKE CHANGES FROM TIME TO TIME WITHOUT NOTICE or OBLIGATION IN PRICES SPECIFICATIONS COLORS and MATERIALS and TO CHANGE or DISCO...

Page 4: ...I system When activated by the dryer s controls this module constantly monitors and controls the functions of the 1 Failure To Light LOCKOUT a Should the main burner fail to light or if a flame is not...

Page 5: ...go into LOCKOUT If flame is reestablished normal operation resumes IMPORTANT The HSI MODULE is a precision instrument and should be handled carefully ROUGH HANDLINGor DISTORTINGCOMPONENTS COULD CAUSE...

Page 6: ...mbly c The HOT SURFACE IGNITOR FLAME SENSOR ASSEMBLY is located in the burner flame area and is used to ignite the gas by the use of a HOT SURFACE IGNITOR To provide feedback information to the HSI mo...

Page 7: ...3 TRIALFORIGNITIONPERIOD 4 seconds INTER PURGE 3 5 seconds C HSI Hot Surface Ignition SYSTEM OPERATION 1 HSI SYSTEM OPERATION a The HSI Module s red indicator light will light for up to approximately...

Page 8: ...nternal Routine Check L E D Indicator Stays On Approx 4 Seconds Hot Surface Ignitor Starts To Glow If L E D Indicator Stays On Continuously Replace HSI Module If L E D Continuously Blinks Twice in Suc...

Page 9: ...the Gas Valve is de energized and the HSI Module controller goes through an inter purge delay before another ignition cycle is attempted The HSI Module will attempt two 2 additional ignition trials b...

Page 10: ...of the system c FLAMEOUT burner flame shut down by the HSI Module due to lack of flame verification This condition occurs only after ignition has been evident but is lost The HSI system will immediat...

Page 11: ...a soapy water solution NEVER TEST FOR LEAKS WITH A FLAME a Connect water column test gauge manometer to the gas valve tap 1 8 N P T f FLAME SENSOR FAULT if there is a problem fault within the flame se...

Page 12: ...HSI Module is equipped with a diagnostic circuit that detects a fault in the Flame Sensor Probe or any related circuits in the internal circuits in the HSI module When a fault is detected the red L E...

Page 13: ...LE if it is in the LOCKOUT MODE or the FLAME SENSOR FAULT MODE open and close the main door then restart the dryer 3 HSI Hot Surface Ignition Module The HSI module controller utilizes a microprocessor...

Page 14: ...ice Department they must be given the correct model number and serial number of the dryer s NOTE Any wiring change s and or conversion s should be by a QUALIFIED ELECTRICAL TECHNICIAN 1 Transformer Wi...

Page 15: ...placed 36E Redundant Gas Valve 4 HSI Hot Surface Ignition 24 VAC Redundant Gas Valve IMPORTANT The HSI 24 VAC Redundant Gas Valve contain no serviceable parts REPLACEMENT COILS ARE NOT AVAILABLE IMPOR...

Page 16: ...promptly The information and illustrations listed here may not depict your particular dryer part exactly This information and or illustrations are a composite of the HSI SYSTEM Be sure to check the p...

Page 17: ...15 HSI Hot Surface Ignition SYSTEM COMPONENTS 24 VAC Transformer Hot Surface Ignition HSI Module 36E 24 VAC Redundant Gas Valve Upshot Burner Tube with Hot Surface Ignitor HSI Flame Sensor Assembly...

Page 18: ...ADC Part No 450401 3 12 15 08 0...

Reviews: