ADCP-80-412 

x

 Issue 1 

x

 April 2000

Page 5

© 2000, ADC Telecommunications, Inc.

a.

Unsnap the top bar of the inductive pick-up coil. Insert the main DSX-1 or DSX-3
–48 Vdc power conductor into the inductive pick-up coil as shown in 

Figure 3

, making

sure that the label side of the coil faces toward the power source. Snap the top bar back
into place after inserting the power feed wire. Anchor the power conductor to the
inductive pick-up coil with a tie wrap or lacing cord in accordance with local practice.

b.

Unsnap the top bar of the inductive pick-up coil. Insert the –48 Vdc conductors for the
DSX-only equipment into the inductive pick-up coil as shown in 

Figure 4

, making sure

that the label side of the coil faces toward the power source. Snap the top bar back into
place after inserting the power feed wire(s). Anchor the power conductor(s) to the
inductive pick-up coil with a tie wrap or lacing cord in accordance with local practice.

Note

: The battery return main conductor, or battery return distribution conductors are not

inserted into the coil and should be routed directly to the DSX-1 or DSX-3 fuse panel.

FILLER

PANEL

SENSOR

ATTACHMENT

INDUCTION

COIL

UPPER CABLE TROUGH

POWER

ATTACHMENT

BAYTRACER

FILLER

PANEL

—48V

—48V

BATTERY

RETURN

BATTERY

RETURN

FUSE PANEL

DSX

PANEL

DSX

PANEL

BATTERY RETURN

—48V

BATTERY RETURN

—48V

REAR VIEW

NOTE: SENSOR AND POWER ATTACHMENT POSITION AND
APPEARANCE SHOWN EXAGGERATED FOR CLARITY.

14088-A

Figure 3. Sensor Cabling Option A

Summary of Contents for ADCP-80-412

Page 1: ...CTION This guide describes the ADC DSX Bay Tracer Illuminator option used in large DSX 1 or DSX 3 environments to enable technicians to locate far end LED tracer lamps more quickly The Bay Tracer Illuminator option consists of a stand alone electronic sensor device that mounts on the top of a DSX 1 or DSX 3 bay and an inductive pick up coil that mounts on one or more 48 Vdc power input conductors ...

Page 2: ...C and ADC Telecommunications are registered trademarks of ADC Telecommunications Inc Admonishments Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided The admonishments in the form of Dangers Warnings and Cautions must be followe...

Page 3: ...able 1 Table 1 Bay Tracer Illuminator PARAMETER SPECIFICATION Electrical Specification Power Voltage 36 Vdc to 75 Vdc Current Consumption 40mA maximum 48Vdc Sensor Interface Two conductor cable with screw connections 22 AWG Light Indicator Off normal On bay current change detected LED Flashing Rate 4 Hz Power Interface Two conductor screw connections for 48 Vdc and battery return 18 20 AWG Heat Di...

Page 4: ...ing 1 Attach the Bay Tracer Electronic Sensor Device mounting bracket to the top cross member or vertical support flange of the DSX 1 or DSX 3 bay using two provided 12 24 rack mounting screws See Figure 2 14001 B Figure 2 Bay Tracer Electronic Sensor Device with Mounting Bracket 2 Two sensor cabling options are provided for detecting a change in current on the 48 Vdc power conductor s feeding the...

Page 5: ...ick up coil as shown in Figure 4 making sure that the label side of the coil faces toward the power source Snap the top bar back into place after inserting the power feed wire s Anchor the power conductor s to the inductive pick up coil with a tie wrap or lacing cord in accordance with local practice Note The battery return main conductor or battery return distribution conductors are not inserted ...

Page 6: ...OSITION AND APPEARANCE SHOWN EXAGGERATED FOR CLARITY 14059 A Figure 4 Sensor Cabling Option B 4 Attach the trailing wires from the inductive pickup coil to the ADC provided sensor connector making sure that the white conductor is routed to the negative pin on the SENSOR receptacle and the black conductor is routed to the positive pin on the receptacle See Figure 5 Caution The sensor and power conn...

Page 7: ... branch circuit on the DSX 1 or DSX 3 fuse panel as shown in Figures 3 and 4 Attach the opposite ends of these wires to the ADC provided power connector on the electronic sensor device making sure that the wire supplying 48 Vdc is routed to the 48V pin on the POWER receptacle and the battery return wire is routed to the RET pin on the receptacle See Figure 5 A reverse blocking diode is incorporate...

Page 8: ...cer electronic sensor device is designed to light whenever an individual jack LED is activated on a DSX bay configured with the device Table 2 provides a description of common error conditions that may occur due to improper installation Table 2 Bay Tracer Troubleshooting CONDITION DESCRIPTION Battery return conductor inserted into coil LED activates when jack is removed Labeled side of coil is fac...

Page 9: ...cific Installation and Operation Assistance Troubleshooting and Repair Product Return Department Extension 3748 E Mail repair return adc com ADC Return Authorization number and instructions must be obtained before returning products Product information may also be obtained using the ADC web site at www adc com or by writing ADC Telecommunications Inc P O Box 1101 Minneapolis MN 55440 1101 U S A Co...

Page 10: ......

Reviews: