background image

16

American Dryer Corp.

112217 - 4

Gas Pressure Adjustment

Disconnect electrical power to the dryer.

IMPORTANT: 

The following procedures must be

performed on both top and bottom tumblers.

To adjust gas valve’s internal regulator, remove the regulator
vent cap, turn the screw clockwise to raise pressure and
counterclockwise to lower pressure.
Gas (burner) pressures are measured with the burner in
operation for all burner adjustment conditions.  Therefore
once the necessary adjustments have been made, the dryer
must be operated in a heating cycle to verify that the pressure
is correct.  If it is not correct, you must discontinue the power
to the unit and make further adjustments.  Repeat these
steps as many times as necessary to achieve the correct
burner pressure.  Once the adjustment of the valve is
complete, the vent cap must be replaced and sealed with,
for example, paint to prevent maladjustment by the user.

!

 WARNING

 

(CE Dryers)

This appliance must only be operated with the gas
type indicated on the dryer’s data plate.  If the
appliance is converted (gas type changed), a data
plate amendment must be obtained from American
Dryer Corporation.
Conversions done improperly can result in a fire or
explosion!

Gas Pressure Testing

For proper operation, the gas pressure must be correct,
consistent and maintained at the gas pressure rates shown
on page

 

14.  Provisions are made at the gas valve for taking

gas pressure readings.
There are two types of devices used to measure gas
pressure.  They are the spring/mechanical type gauge and
the manometer.  The use of the spring/mechanical type
gauge is not recommended because they are very easily
damaged and are not always accurate.  The preferred type
of gauge is the manometer because it is a simple device to
use and is highly accurate.  A manometer is simply a glass
or transparent plastic tube with a scale graduated in inches
or millibars.  When it is filled with water and pressure is
applied, the water in the tube rises, showing the exact gas
pressure.

Gas Pressure Test Procedure

Turn gas cock in gas supply line to “OFF” position.
60 Hz dryers: Install pressure tap and attach manometer
(refer to the illustration on page

 

15).

Turn gas cock to “ON” position.
Start the dryer in Heat Mode and wait for ignition.  Gas
manifold pressure should be as shown on page

 

14.

If the gas pressure needs to be adjusted, refer to “Gas
Pressure Adjustment” on this page.
Once test is complete, turn gas cock to “OFF” position.
Remove manometer.  Tighten screw inside the pressure
tap or install plug.
Turn gas cock to “ON” position and check for leaks with
soap solution with main burner “ON.”

Preparation for Operation / Start-Up__

The following items should be checked before attempting
to operate the dryer:
• Read all “CAUTION,” “WARNING,” and “DIRECTION”

labels attached to the dryer.

• Check incoming supply voltage to be sure that it is the

same as indicated on the data label.  In the case of 208
VAC or 230/240 VAC, the supply voltage must match the
electric service exactly.

• GAS MODELS – Check to ensure that the dryer is

connected to the type of heat/gas indicated on the dryer
data label.

• GAS MODELS – Be sure that all gas shutoff valves are

in the open position.

• Be sure all back panels (guards) and electric box

covers are in place.

• Be sure the service doors are closed and securely in

place.

• Be sure the lint door/drawer is securely in place.
• Rotate the tumbler (drum) by hand to be sure it moves

freely.

• Check bolts, nuts, screws, terminals, and fittings for

tightness and security.

• Check that the vent is connected to the dryer and is

exhausted to the outdoors.

Preoperational Test __________________

All dryers are thoroughly tested and inspected before leaving
the factory.  However, a preoperational test should be
performed before the dryer is publicly used.  It is possible
that adjustments have changed in transit or due to marginal
location (installation) conditions.  Installer must instruct the
user on how to correctly operate the dryer before leaving.
Turn on electric power to the dryer.
Refer to the Operating Instructions for starting your particular
model dryer.

Gas Dryers

Open all shutoff valves.
When a gas dryer is first started (during initial start-up), it
has a tendency not to ignite on the first ignition attempt.
This is because the gas supply piping is filled with air, so it
may take a few minutes for the air to be purged from the
lines.

NOTE: 

During the purging period, check to be sure that

all gas shutoff valves are open.

A gas pressure test should be taken at the gas valve
pressure tap of each dryer to ensure that the water column
pressure is correct and consistent.

NOTE: 

Water column pressure requirements (measured

at the pressure tap of the gas valve body) must be
verified.

IMPORTANT: 

In most cases there is no regulator provided

in an L.P. dryer.  The water column pressure must be
regulated at the source (L.P. tank), or an external regulator
must be added to each dryer.

Summary of Contents for AD222

Page 1: ...n et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion and to prevent property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appl...

Page 2: ...r order is processed accurately and promptly These instructions are only valid if the following country code is on the appliance If this code is not present on the appliance it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of the appliance to the condition of use for the country In accordance with EN ISO 3166 1 the name...

Page 3: ... that the local distribution conditions nature of gas and pressure and adjustment of the appliances are compatible CAUTION Dryer s should never be left unattended while in operation Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper operation Attention Au moment de l entretien des commandes étiquetez tous les fils avant de les débrancher Des err...

Page 4: ...l constitute a fire hazard and should not be placed in a tumble dryer Do not dry mop heads Contamination by wax or flammable solvents will create a fire hazard WARNING Do not use heat for drying articles that contain plastic foam sponge rubber or similarly textured rubber materials Drying in a heated tumbler may damage plastics or rubber and also may be a fire hazard The possible presence of resid...

Page 5: ...________________________________ ____________________________________________________________ IMPORTANT The dryer must be installed in a location environment which the ambient temperature remains between 40 F 4 44 C and 130 F 54 44 C The operation of this appliance may affect the operation of other types of gas appliances which take their air for safe combustion from the same room If in doubt cons...

Page 6: ...MPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T VOLTAGE AVAILABLE 208 240V 1ø 50 60 Hz APPROXIMATE NET WEIGHT 302 lb 136 98 kg APPROXIMATE SHIPPING WEIGHT 342 lb 155 12 kg AIRFLOW PER POCKET 220 cfm 6 23 cmm EXHAUST CONNECTION DIAMETER PER POCKET 4 10 16 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE PER POCKET kW Btu hr kcal...

Page 7: ...dclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Page 8: ...fer to Exhaust Requirements section The dryer must be located in an area where correct exhaust venting can be achieved as noted in this manual refer to Exhaust Requirements section IMPORTANT The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber CAUTION This dryer produ...

Page 9: ... be made for remote or constricting passageways or where dryers are located at high altitudes or predominantly low pressure areas IMPORTANT Make up air must be free of dry cleaning solvent fumes Make up air that is contaminated by dry cleaning solvent fumes will result in irreparable damage to the motors and other dryer components NOTE Component failure due to dry cleaning solvent fumes will void ...

Page 10: ...efore each individual duct is added The minimum diameter of the individual ductwork must be at least 8 inches 20 32 cm IMPORTANT No more than four dryers should be connected to one main common duct The illustration below shows the minimum cross sectional area for multiple dryer round or square venting These figures must be increased if the main duct run from the last dryer to where it exhausts to ...

Page 11: ...s of the data label exactly The wire size must be properly sized to handle the related current WARNING 208 VAC and 230 240 VAC are not the same Any damage done to dryer components due to improper voltage connections will automatically void the warranty TERM LINE VOLTAGE 50 Hz 60 Hz HIGH 260 226 283 249 MED 239 208 260 230 LOW 217 189 236 208 Electrical Service Specifications Gas Models Only Check ...

Page 12: ... 16 20 240 3ø 3 5 4 16 20 230 3ø 3 5 17 30 240 3ø 3 5 4 17 30 380 3ø 4 4 5 11 15 400 3ø 4 5 11 15 416 3ø 4 5 4 11 15 If local codes permit power to the dryer can be made by the use of a flexible UL listed power cord pigtail wire size must conform to rating of dryer or the dryer can be hard wired directly to the service breaker panel In both cases a strain relief must be installed where the wiring ...

Page 13: ... for the appliance category in accordance with national installation regulations of the country of destination and if in doubt the installer must contact the supplier The manufacturer of this appliance does not recommend the use of flexible gas supply line hose An external gas supply shutoff must be provided WARNING CE Dryers Only This appliance must only be operated with the gas type indicated on...

Page 14: ...Injector Data For Non CE European and Non AGA Australia Models Only Shaded areas are stated in metric equivalents Gas valve s internal regulator disabled Information is per pocket tumbler Consult factory for elevations over 2 000 feet 610 meters for correct orifice size Parts Required for Conversion Description ADC P N Qty Unregulated Gas Conversion Kit 140414 2 OR Regulated L P Gas Conversion Kit...

Page 15: ... power to the dryer Close all shutoff valves for both top and bottom tumbler in dryer s gas supply line IMPORTANT The following procedures must be performed on both top and bottom tumblers Open the panels located just below each loading door Locate the gas train and disconnect the union three electrical plugs and the gas train mounting screws from the burner Carefully slide the gas train out of th...

Page 16: ...refer to Gas Pressure Adjustment on this page Once test is complete turn gas cock to OFF position Remove manometer Tighten screw inside the pressure tap or install plug Turn gas cock to ON position and check for leaks with soap solution with main burner ON Preparation for Operation Start Up__ The following items should be checked before attempting to operate the dryer Read all CAUTION WARNING and ...

Page 17: ...he remaining time NOTE The dryer can be stopped at any time by opening the main door or the lint door When the programmed drying time has expired the non coin microprocessor controller computer will proceed into the Cool Down Cycle Shutdown Instructions _______________ If the dryer is to be shutdown taken out of service for a period of time the following must be performed Discontinue power to the ...

Page 18: ...f delivery can be obtained by the sender Shipping charges are not the responsibility of ADC All returns should be prepaid to the factory Any C O D or COLLECT returns will not be accepted IMPORTANT No replacements credits or refunds will be issued if the claim cannot be processed due to insufficient information The party filing the claim will be notified in writing either by FAX or CERTIFIED MAIL R...

Page 19: ...e cleaning of appliances is recommended 7 Days After Installation and Every 12 Months Thereafter A competent professional should inspect bolts nuts screws setscrews grounding connections and nonpermanent gas connections unions shutoff valves and orifices Belts should be examined Cracked or seriously frayed belts should be replaced Complete an operational check of controls and valves Complete an op...

Page 20: ...ADC Part No 112217 4 05 05 15 ...

Reviews: