Adaptive Tripp-Lite 1109502801 Replacing Manual Download Page 4

R

EPLACING

 

THE

 B

ILLBOARD

 UPS

4

PN 1109610110 

REV

. A

8.  Connect all previously removed cables.

Figure 6: UPS power and communication connections.

Plug the UPS power cord into the control cabinet’s AC receptacle.

9.  Power on the Billboard and the control cabinet on.

Power on the load center(s) on the back of the Billboard.

Power on the load center on the control cabinet.

Press and hold the UPS On/Off/Standby 

 button until the alarm beeps once 

indicating the UPS load output receptacles are now on.

A

B

C

D

E

F

* Critical components that may require power to be cycled on or off from a remote Internet connection.
** Critical components on dual billboard configurations only, that may require power to be cycled on or off from a remote Internet 
connection.

Item

Port

Component connection

* A

 Load 1

(2 switched outlets)

PC controller #1 power cord label ID #17.

DVI / fiber converter #1 power cord label ID #8.

** B

Load 2

(2 switched outlets)

PC controller #2 power cord label ID #22.

DVI / fiber converter #2 power cord label ID #9.

C

Load 3

(4 unswitched outlets)

For customer’s ISP (Internet Service Provider) equipment.

Y–type power cord label ID #7 connects both camera PoE power 
cords label ID #2 and if applicable #27 into one UPS receptacle.

Router power cord label ID #11.

KVM drawer power cord label ID #12.

E

Ethernet

Ethernet cable label ID #4 from router.

F

Envirosense

Environmental probe (Envirosense) cable label ID #19.

K

USB

PC controller #1 USB cable label ID #28.

Summary of Contents for Tripp-Lite 1109502801

Page 1: ...t surges The UPS resides inside the deluxe remote control cabinet and provides back up power for a limited time to all the components plugged into it The UPS software and SNMP Web card allows billboard operators to remotely monitor control cabinet equipment plugged into the UPS Power can be cycled on and off on two sets of UPS receptacles load 1 and 2 allowing for a remote reboot of critical compo...

Page 2: ... doors on the control cabinet If applicable remove the control cabinet s padlock Turn cabinet handle and pull open the control cabinet door 3 Disconnect all cables from the back of the UPS Note Single billboard configurations have fewer cables plugged into the UPS Figure 2 Rear view of a dual billboard UPS configuration WARNING Possible fall hazard When servicing billboard components service perso...

Page 3: ...t force the shelf all the way out otherwise power adapters tie wrapped to the shelf may become disconnected from their components Figure 4 UPS removal Remove the UPS from the control cabinet 5 Attach mounting brackets to both sides of the replacement UPS Figure 5 UPS mounting brackets 6 Set the replacement UPS on the sliding shelf and slide it into the control cabinet 7 With the previously removed...

Page 4: ...components on dual billboard configurations only that may require power to be cycled on or off from a remote Internet connection Item Port Component connection A Load 1 2 switched outlets PC controller 1 power cord label ID 17 DVI fiber converter 1 power cord label ID 8 B Load 2 2 switched outlets PC controller 2 power cord label ID 22 DVI fiber converter 2 power cord label ID 9 C Load 3 4 unswitc...

Page 5: ...ed UPS information A B D E C Item LED Normal indicating status A Power Continuous green LED B Voltage correction Green LED is either continuous blinking or not lit at all The UPS will also emit a slight clicking noise during voltage correction C Output load level Continuous green or yellow LED D Battery charge Continuous green LED full battery charge yellow LED half battery charge or red beginning...

Page 6: ...THIS PAGE INTENTIONALLY BLANK REPLACING THE BILLBOARD UPS 6 ...

Reviews: