2-2
Unpacking and Initial Setup
Rackmounting Recommendations
To ensure the safe and efficient operation of the RAIDStation7 Ultra160 SCSI
rackmount Storage Array it is essential that you comply with the following guide-
lines. Adaptec’s rackmount systems may be installed in closed or open rackmount
cabinets by observing the environmental, electrical and mechanical precautions
listed in the following sections.
Ambient Temperature
Installation of rackmount systems in standard 19 in. cabinets may lead to a differ-
ential between the room ambient temperature and the internal ambient tempera-
ture of the rack environment. The normal operating temperature of the
RAIDStation7 Ultra160 SCSI Storage Array is between 5
o
C and 30
o
C (between
41
o
F and 86
o
F). The maximum operating temperature of the RAIDStation7
Ultra160 SCSI Storage Array is 40 degrees centigrade (104 degrees fahrenheit).
However, it is not recommended that the system be continuously run at this ele-
vated temperature. Room ambient temperature must be compatible with this rec-
ommendation.
Air Flow
To ensure that the RAIDStation7’s internal heat build-up is adequately dissipated
into the room environment, the Storage Array’s air flow must not be restricted.
No air vents should be blocked. The Storage Array must be a minimum of 1 meter
away from a solid surface such as a wall or partition. Air flow through the
RAIDStation7 Ultra160 SCSI Storage Array is from front to rear.
Mechanical Stability
Consideration should be given to the loading of the cabinet. To maintain a low
center of gravity (thus reducing the likelihood of instability and equipment tip-
ping) rackmount Storage Arrays should be installed (where possible) from the
bottom of the cabinet upwards. This is recommended to ensure personal safety.