Ada ADA-7240 User Manual Download Page 9

3.4. POWER SUPPLY CONNECTION

The power supply to the ADA-7240 converter should be DC (regulated) from 10 V= to 30V=. Nominal power is typically 2W, e.g. ZS-

12/250 or DR-15-24. Power cable from DC power supplies to device must not be longer than 3m. 

Observe the polarity, connect positive (+) of DC power supplies to V+ and negative (-) end to V- screw terminal block.  ADA-7240 has

the protection from opposite connection power supply. If after power, on the front panel is not lit green LED PWR, check the power

connection (polarity).

4. CONFIGURATION

The operating mode of the ADA-7240 converter is set by the use 6-position SW1 switch. This switch is located near the Fibre-Optic

connectors (see Fig.1). To set the SW1 should remove the terminal cover and using small, flat screwdriver make correct setting.

4.1. OPERATING MODE SETTING

All available operating modes are shows in table below. 

If there are any additional questions, please contact with technical support: [email protected] or on the phone: +48 41 362-12-46.

Table 1. RS422 or RS485 operating mode.

SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6

Description

Operating mode

OFF

OFF

OFF

OFF

OFF

OFF

RS-422 bus

4-wire RS422 network. 

Full duplex or half duplex transmission.

ON

ON

ON

ON

ON

ON

RS-485 bus, 

automatic data flow control

 2-wire and 4-wire RS485 network.

Full duplex or half duplex transmission.

4.2. DEFAULT SETTING

The ADA-7240 converter is being set in RS485 mode during production as in the table below.

Table 2.

SW1-1 SW1-2 SW1-3 SW1-4 SW1-5

SW1-6

ON

ON

ON

ON

ON

ON

5. ACIVATION

The converter can be power on after properly connection according to section above.

If   after   connection   power   supply   on   front   panel   will   not   light   green   led   PWR,   check   correctness   of   power   supply   connecting

(polarization). When data is present the LEDs Tx and Rx should blink.

5.1. DESCRIPTION OF SIGNALLING LEDS 

LED

Description

PWR Signalling of Power Supply
RX

Signalling of data receiving through ADA-7240 from RS485/RS422 port

TX

Signalling of data transmitting from ADA-7240 through RS485/RS422 port

ATTENTION!

AT BAUD RATE ABOVE 38.4 KBPS THE LED'S TX, RX WILL LIGHT WEAKLY DURING DATA TRANSMISSION

5.2. TROUBLESHOOTING

Problem

Solutions

PWR LED is not light

Check polarization and parameters of connected power supply.

Rx LED lights continuously

RS485(4W) /422 network. Wrong polarization on terminals: Rx+, Rx-; change polarization.

RS485(2W) network. Wrong polarization on terminals: Tx+/A, Tx-/B; change polarization.

No transmission

Tx LED is blinking

RS485(4W)   /   RS422   network.   Check   correctness   of   connection   to   terminals   Tx,   Rx;

according to point 3.

RS485(2W) network.  Check correctness of  configuration setting  according to point 4.

9

ADA-7240

Summary of Contents for ADA-7240

Page 1: ...User manual ADA 7240 RS 485 RS 422 to Multidrop Fiber Optic Converter 1 ADA 7240 Copyright 2001 2017 CEL MAR sp j io_ada 7240_en_v3 22...

Page 2: ...RS422 BUS 5 3 2 1 CONNECTION TO 4 WIRE RS422 BUS 5 3 2 2 CONNECTION TO 4 WIRE RS485 BUS 6 3 2 3 CONNECTION TO 2 WIRE RS485 BUS 6 3 2 4 LINE TERMINATION Rt ON RS485 RS422 BUS 6 3 3 CONNECTION FIBRE OP...

Page 3: ...sable from the supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This may result to short circuit...

Page 4: ...isolation between connected devices and resistance to interference on the transmission bus Fiber optic connection is made by the use of two fibres ADA 7240 can be use also for extend the fiber optic b...

Page 5: ...talled within a single object not supply converter from power circuit device that generates large impulse interference such as transmitters contactors 3 1 ASSEMBLING The ADA 7240 converter case is ada...

Page 6: ...not needed below 9600Bd should be used the Line Termination resistor if the distance is over 1000m 9600Bd or 700m 19200Bd transmission Example connection of Rt are shown on Fig 3 4 5 Two resistors Rt...

Page 7: ...NTION The device is equipped in the laser transmitter The radiation emitted by the laser transmitter is harmful to the eyes Under no circumstances should never look to at the uncovered slot to which i...

Page 8: ...ctor TX RX RX DSR DTR RTS CTS TX V V PC RS232 connector RX DSR DTR RTS CTS TX ADA 7020 Current loop connector FO Conn TX RX V TX TX RX RX V Controller Current loop connector V TX TX RX RX V ADA 7240 R...

Page 9: ...s automatic data flow control 2 wire and 4 wire RS485 network Full duplex or half duplex transmission 4 2 DEFAULT SETTING The ADA 7240 converter is being set in RS485 mode during production as in the...

Page 10: ...and receiver for an optical wavelength from 640nm to 675nm Screw terminal wire max 2 5mm2 Line length up to 2000m for fibre type 50 125 mm up to 2500m for fibre type 62 5 125 mm up to 2000m for fibre...

Page 11: ...onmental Parameters Operating temperature Standard version S 0 C 23 C 50 C Extended version E 30 C 23 C 60 C Humidity 5 95 non condensing Storage temperature 40 70 C Casing Dimensions 71 x 90 x 58 mm...

Page 12: ...transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy you p...

Reviews: