background image

T E C H N I C A L   A N D   I N S T A L L A T I O N  

 

12

**Calculated values.

 

7.

 

MAINTENANCE 

 

ACV recommends that the cylinder is maintained by a competent person, this should be carried out every 
12 months. 
 
The safety valves must be manually operated at least once a year to check their operation and re-seating. 
Allow cylinder to cool before slowly twisting open the temperature and pressure relief valve. The water 
should flow freely through the tundish and discharge pipe work, check that the valve reseats when 
released.  
 

CAUTION: The water discharged may be very hot. 
 

Repeat the steps above for the expansion relief valve on the cold inlet pipe work. 
 
The pressure reducing valve (PRV) has a strainer that can be removed for inspection and if necessary 
cleaning. 

i.

 

Isolate the cold water inlet to the cylinder. 

ii.

 

Open the lowest hot tap to remove the pressure from the system. 

iii.

 

The plastic PRV cartridge can be unscrewed from the brass valve body, loosen using a suitable 
spanner (not stilsons or pump pliers) unscrew and pull the cartridge from the valve body, the 
strainer will be withdrawn with the cartridge. 

iv.

 

Remove the strainer from the cartridge and clean under running water if necessary. 

v.

 

Replace strainer and push cartridge into valve body, take care when screwing the cartridge in not 
to damage the threads. Do not over tighten. 

vi.

 

Close hot tap and slowly open the cold water isolating valve to the cylinder, check for any leaks.  

 
The primary tank should be checked for a build up of air, this can be purged using the primary air vent on 
the top of the cylinder. Check the primary system pressure gauge on the boiler or filling loop and recharge 
as necessary. 
 

IMPORTANT: If the primary system is being topped up on a regular basis there is a risk of corrosion 
damage to the cylinder. 

 
The tank must be fitted by means of screwed couplings or flanges to allow dismantling and removal of the 
unit. These should be fitted in such a way as to allow easy access. 

 

8.

 

PARTS LIST 

 

Description  

Code 

Description 

Code 

Control Thermostat 

54442045 

Cold Inlet Tube 130 

497B0003 

High Limit Thermostat 

54764020 

Cold Inlet Tube 160 

497B0005 

Manual Air Vent 

55445006 

Cold Inlet Tube 210+ 

497B0007 

Thermostat Dry Well 130 

39438027 

Cold Inlet Tube 240+ 

497B0009 

Thermostat Dry Well 160 

39438039 

Cold Inlet Tube 300+ 

497B0010 

Thermostat Dry Well 210+ 

 

 

39438046 

Complete Control Pod (stat to left) 

24614152 

Thermostat Dry Well 240+ 

39438047 

Complete Control Pod (stat in centre) 

24614114 

Thermostat Dry Well 300+ 

39438047 

3kW Immersion (Thermco) 

OI300 

Top Cover 

497B5010 

6kW Immersion Single Phase (ACV) 

10800083 

Summary of Contents for SLE Plus 210

Page 1: ...SLE130 160 SLE 210 240 300 ADDITIONAL INSTALLATION INSTRUCTION FOR UK KITS IMPORTANT DO NOT UNDER ANY CIRCUMSTANCES SWITCH ON THE IMMERSION HEATER BEFORE THE PRIMARY TANK IS FILLED SLE 040113...

Page 2: ...rk Dalgety Bay Fife KY11 9PF Scotland Further copies of instructions can be downloaded at www acv com Manufactured at ACV International Kerkplein 39 B 1601 Ruisbroek Belgium Telephone 0032 237 81235 e...

Page 3: ...rsion Heater 6 4 System Schematics Typical un vented 7 Typical open vented 7 Proposed SLE diverted primary 8 Proposed SLE radiators and UFH 8 Typical S Plan electrical 9 Typical Y Plan electrical 10 5...

Page 4: ...crushing damage to the domestic tank IMPORTANT ACV recommends the use of a corrosion inhibitor in the primary heating system The warranty will be invalidated if upon inspection it is found that a tan...

Page 5: ...c water for use at the sanitary hot water outlets The exterior tank B is manufactured from STW 22 carbon steel this tank holds the primary heating fluid which is circulated from the boiler as the prim...

Page 6: ...olyurethane foam 50mm thick Containing no CFC s having a GWP 0 00025 and ODP 0 Jacket The tank is covered in a co polymer polypropylene jacket this is a plastic material that offers a high resistance...

Page 7: ...k plastic plug from Check Expansion valve and fit Expansion Vessel seal with PTFE tape 7 Connect Temperature and Pressure relief valve to 1 2 connection and orientate into position Do not run drain di...

Page 8: ...ages 12 13 ACV recommends that the cylinder is electrically cross bonded to earth Primary system connections The primary flow and return connections to the tank should be made using the appropriate si...

Page 9: ...roperty 4 Check for possible leakage before wiring 5 Wire the heater in accordance with the diagram below The heater should be wired through a double pole isolating switch or controller having contact...

Page 10: ...T E C H N I C A L A N D I N S T A L L A T I O N 7 Typical open vented application Proposed SLE schematics...

Page 11: ...d Primary Flow SLE Radiators and Under floor Typical S Plan schematic At high DHW demand or DHW charging Heat Pump can operate at elevated temperature 45 55 C and flow is diverted to top inlet During...

Page 12: ...TIONS SUPPLIED WITH YOUR CONTROL PACKAGE EARTH CONNECTION IS NOT REQUIRED WITH MYSON ZONE VALVE FITTING INSTRUCTIONS INCLUDED WITH VALVE THIS DIAGRAM IS FOR GUIDANCE ONLY ACV ACCEPT NO LIABILITY FOR D...

Page 13: ...TERMINAL NUMBERING MAY DIFFER FROM THOSE SHOWN ALWAYS WITH YOUR CONTROL PACKAGE EARTH CONNECTION IS NOT REQUIRED WITH MYSON ZONE VALVE FITTING INSTRUCTIONS INCLUDED WITH VALVE THIS DIAGRAM IS FOR GUI...

Page 14: ...recommends the use of a corrosion inhibitor in the primary heating system The warranty will be invalidated if upon inspection it is found that a tank has failed due to corrosion caused by the lack of...

Page 15: ...v Replace strainer and push cartridge into valve body take care when screwing the cartridge in not to damage the threads Do not over tighten vi Close hot tap and slowly open the cold water isolating v...

Page 16: ...r connection 1 BSP 1 BSP Primary fluid connections 1 BSP 1 BSP Domestic water connections BSP BSP Dimension A mm 1024 1222 B mm 234 234 C mm 759 959 D mm 234 234 Mains kit will add approximately 500mm...

Page 17: ...r 37 45 51 Immersion heater connection 1 BSP 1 BSP 1 BSP Primary fluid connections 1 BSP 1 BSP 1 BSP Domestic water connections BSP BSP BSP Dimension A mm 1493 1741 2046 B mm 1230 1477 1783 C mm 937 1...

Page 18: ...EQUIREMENT there shall be precautions to ensure that the hot water discharged from safety devices is safely conveyed to where it is visible but will not cause danger to persons in or about the buildin...

Page 19: ...levant part of BS 7291 3 58 The discharge pipe D2 should be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds tha...

Page 20: ...e below a fixed grating and above the water seal c downward discharges at low level i e up to 100mm above external surfaces such as car parks hard standings grassed areas etc are acceptable providing...

Page 21: ...p to 27m 0 8m 1 0m 1 4m G 22mm 28mm 35mm 42mm Up to 9m Up to 8m Up to 27m 1 0m 1 4m 1 7m G1 28mm 35mm 42mm 54mm Up to 9m Up to 8m Up to 27m 1 4m 1 7m 2 3m Worked example of discharge pipe sizing Fig 5...

Page 22: ...ength of 28mm pipe D2 from a G1 2 temperature relief valves equates to 18m Subtract the resistance of 4 No 28mm elbows at 1 0m each 4 0m Therefore the maximum permitted length equates to 14m As the ac...

Page 23: ...T E C H N I C A L A N D I N S T A L L A T I O N 20...

Reviews: