STARTING UP

STARTING UP THE BOILER

Set-up conditions

• 

All connections made

• 

External power supply enabled

• 

Oil supply open and circuit tight

• 

DHW  (if any) and heating circuits full of water

Procedure

1. 

Set the boiler thermostat between 60 and 90°C.

2. 

Put the summer/winter switch on "Winter".

3. 

Put the ON/OFF master switch on "ON".

4. 

Check with your hand (motor vibrations) that the heating pump of the system is not blocked and 

unblock it if required. 

Follow-on tasks

• 

Adjust the combustion, see opposite.

COMBUSTION ADJUSTMENT

Set-up conditions

• 

Operating boiler

Procedure

1. 

Refer to the Initial Operation instructions detailed in the technical manual of your burner.

2. 

Adjust CO

2

 according to the values provided in the basic adjustment table below and by setting 

the oil pressure as well as the air flap as described in the Initial Operation paragraph of the burner 

manual.

3. 

Check the flue temperature and CO values according to the combustion characteristics (refer to 

“Combustion characteristics” on page 9.

Follow-on tasks

• 

Bleed the heating circuit again to restore a 1.5 bar pressure.

• 

Repeat the sequence until complete evacuation of the air contained in the circuit.

Basic Adjustment table

Boiler/

Burner 

model

Burner 

Output

Oil 

mass flow

Oil 

nozzle

Oil 

pressure

Fan 

pressure

Air flap 

scale

Baffle 

plate 

scale

kW

kg/h

Usgal/h

bar

mbar

%

mm

N1 eco/

BMV3

25

2.11

0.60

60°H

10.0

2.5

30

6

N2 eco/

BMV4

32

2.70

0.60

60°H

14.5

2.5

32

9

N3 eco/

BMV5

43

3.63

1.00

45°H

12.0

2.5

46

10

Summary of Contents for N1 ECO

Page 1: ...A1005170 664Y7700 B EN FR NL ES IT DE PL RU INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS for the Installer and the User eco N1 N2 N3...

Page 2: ...NSTALLATION 14 Safety Instructions for the Installation 14 Package contents 14 Tools Required for the Installation 14 Burner installation 15 Oil Connection 15 Electrical Connection 16 Recommendations...

Page 3: ...replaced by genuine factory parts General remarks The availability of certain models as well as their accessories may vary according to markets The manufacturer reserves the right to change the techn...

Page 4: ...electrical safety electrical hazard Essential recommendation for the correct operation of the appliance or the system General remark Safety valve connected to the sewage system Connection to the sewag...

Page 5: ...n 5 USER S GUIDE The part number Code and serial number N of the appliance are indicated on its rating plate and must be provided to ACV in case of warranty claim Failure to do so will make the claim...

Page 6: ...x position WHAT TO CHECK ON A REGULAR BASIS Essential recommendations for the correct operation of the appliance ACV recommends to check the system at least every 6 months as follows Check that the sy...

Page 7: ...at the rear of the boiler and preset at 45 C delays the heating pump activation This prevents the risks of corrosion of the combustion chamber Production of domestic hot water The N eco boilers can be...

Page 8: ...ation with very low emissions Refer to the burner technical manual for installation operation and maintenance instructions and for the technical characteristics Key 1 Motor 2 Oil pump with filter 3 Ph...

Page 9: ...t PCI max kW 25 6 31 3 45 1 Output at 100 80 60 C kW 24 7 30 3 43 4 Efficiency at 100 80 60 C 96 5 96 7 96 2 Efficiency at 30 load EN677 98 5 97 9 97 2 NOx Class 5 Weighted mg kWh 110 110 110 CO Max o...

Page 10: ...it is recommended to install a hydrocyclone or magnetic filter on the installation side 2 Limit the fill frequency Limit fill operations In order to check the quantity of water that has been added int...

Page 11: ...up the boiler and check regularly the water level Fill with water as necessary It is mandatory to ventilate the boiler room The high or low air vent opening dimensions depend on the boiler power and...

Page 12: ...nt opening dimensions depend on the boiler power and the boiler room size Refer to the local regulations in force B23 E A B F C D FLUE PIPE CONNECTION TYPES It is mandatory to use ACV flue systems to...

Page 13: ...6 8 9 L1 T2 T1 N PE M Br B Bk G G Br Bk G Bk B Y Gr B R G B Y Gr G V W B Y Gr Y Gr Br Y Gr B Bk G L1 T1 T2 S3 B4 N 10 T1 T2 S3 B4 Boiler N1 N2 N3 eco boiler wiring diagram 1 ON OFF master switch 2 Mi...

Page 14: ...and knowledge unless supervised or unless they have been given instruction concerning the use of the appliance by a person responsible for their safety Essential recommendations for the correct opera...

Page 15: ...rsonal injury or death Essential recommendations for the correct operation of the appliance Bleed the oil duct and check thoroughly if all the boiler tubes both internal and external are tight Control...

Page 16: ...B en 16 EN FR NL ES IT DE PL RU INSTALLATION ELECTRICAL CONNECTION T2 S3 T1 N L1 B4 T2 S3 T1 N L1 B4 2 M N PE 230 V 50HZ L1 t 1 3 1 Room thermostat 2 System heating pump 3 Bridge to be removed before...

Page 17: ...ircuit which is adapted to the boiler power size and the type of system General remark The circuit illustrations are basic principle diagrams only HEATING CONNECTION Typical connection high temperatur...

Page 18: ...first put the DHW circuit under pressure before pressurizing the heating primary circuit Refer to the hot water preparation tank manual for more information Set up conditions External power supply is...

Page 19: ...ctions detailed in the technical manual of your burner 2 Adjust CO2 according to the values provided in the basic adjustment table below and by setting the oil pressure as well as the air flap as desc...

Page 20: ...nd user perform the periodic checks mentioned in the Safety section of this manual Control the tightness of the hydraulic circuit connections N1 N2 N3 eco A1005170 664Y7700 B en 20 EN FR NL ES IT DE P...

Page 21: ...ter N1 N2 N3 eco A1005170 664Y7700 B EN FR NL ES IT DE PL RU en 21 MAINTENANCE CLEANING THE COMBUSTION CHAMBER Set up conditions Boiler shut down External power supply isolated Oil supply closed Front...

Page 22: ...N1 N2 N3 eco A1005170 664Y7700 B en 22 EN FR NL ES IT DE PL RU SERVICE LOG Service date CO2 Flue gas T Efficiency Remarks Name Signature SERVICE LOG...

Page 23: ...heat output at 30 of rated heat output P1 kW 9 04 10 80 16 10 at rated output and high temp regime P4 kW 24 65 30 3 43 42 Useful efficiency at 30 of rated heat output 1 98 47 97 93 97 66 at rated outp...

Page 24: ...application Low Temperature Low Temperature Low Temperature declared load profile for water heating Seasonal space heating energy efficiency class B B B Water heating efficiency class rated heat outp...

Reviews: