background image

5

TECHNICAL SPECIFICATION

MAXIMUM OPERATING CONDITIONS

Maximum service pressure 

(tank full of water)

- Primary circuit: 3 bar
- Secondary circuit: 10 bar

Test pressure 

(tank full of water)

- Primary circuit: 4.5 bar
- Secondary circuit: 13 bar

Operating temperature
- Maximum temperature: 90 °C

Water quality
• Chlorures: < 150 mg/l (304)

< 2000 mg/l (Duplex)

• 6 

ph

8

BURNER CHAMBER PLATE

The burner chamber plate has 4 threads (M 10 x 20) for attaching
the burner. It is protected from heat by a blanket insulation.

Ø130

Ø28

5xØ6.5(M8)

60

60

60

60

HM 60 N

HM 60 N

HM 70 N

HM 70 N

HM 100 N

HM 100 N

HM 150 

BM 101

BG 2000-S/60

BM 101

BG 2000-S/70

BM 101

BG 2000-S/100

JUMBO

Peak delivery at 40 °C

L/10’

474

474

646

646

905

905

1504

Peak delivery at 45 °C

L/10’

378

378

543

543

777

777

1289

Peak delivery at 60 °C

L/10’

245

245

346

346

514

514

870

Peak delivery at 70 °C

L/10’

193

193

268

268

343

343

700

Peak delivery at 80 °C

L/10’

135

135

207

207

258

258

540

Peak delivery at 40 °C

L/60’

1942

1942

2133

2133

3172

3172

4828

Peak delivery at 45 °C

L/60’

1656

1656

1794

1794

2680

2680

4138

Peak delivery at 60 °C

L/60’

1106

1106

1219

1219

1813

1813

2864

Peak delivery at 70 °C

L/60’

681

681

971

971

1226

1226

2131

Peak delivery at 80 °C

L/60’

499

499

636

636

893

893

1362

Continuous delivery at 40 °C

L/h

1835

1835

1835

1835

2776

2776

3989

Continuous delivery at 45 °C

L/h

1573

1573

1573

1573

2379

2379

3419

Continuous delivery at 60 °C

L/h

1101

1101

1067

1067

1665

1665

2393

Continuous delivery at 70 °C

L/h

791

791

918

918

1104

1104

1718

Continuous delivery at 80 °C

L/h

455

455

580

580

804

804

987

Reheat time at 60 °C

min

9

9

16

16

13

13

17

HM 60 N

HM 70 N

HM 100 N

HM 150

JUMBO

Maximum Input

kW

69.9

69.9

107.0

154.0

Maximum Output

kW

62.5

63.0

96.8

139.1

Maintenance loss at 60 °C as rated value

%

0.57

0.60

0.65

0.52

Total capacity

L

162

239

330

645

Primary circuit capacity

L

82

108

130

245

Heating connection

Ø

1

1/2

1

1/2

1

1/2

DN 50

Hot water connection

Ø

3/4”

1”

1”

2”

Hot water tank heat exchange surface

m

2

2.46

3.14

3.95

5.30

Weight empty

Kg

220

270

320

530

Pressure drop primary circuit

mbar

54

46

83

120

GENERAL FEATURES

DOMESTIC HOT WATER PERFORMANCES

Summary of Contents for HM 60 N

Page 1: ...and Servicing Instructions HM 60 N 70 N 100 N 150 JUMBO HM 60 N 70 N 100 N With ACV BG 2000 S premix gas burner HM 60 N 70 N 100 N With ACV BM 101 oil burner HM 150 JUMBO With ACV BM 151 oil burner He...

Page 2: ...specified by ACV Failure to observe instructions regarding tests and test procedures can result in personal injury or pollution risks Note ACV reserves the right to modify the technical specification...

Page 3: ...in conjunction with HR and Jumbo hot water storage tanks the Heatmaster can supply even the largest hot water requirement Standard equipment The HeatMaster 60 N 70 N 100 N and 150 Jumbo has the follow...

Page 4: ...pump Primary expansion vessel Heating circuit filling valve with removable hose and non return valve Automatic air vent Heating return Burner Tank in Tank heat exchanger Flue pipes and turbulators Flu...

Page 5: ...2 21 20 19 GRASSLIN GRASSLIN I O Manual reset high limit thermostat Burner lockout indicator Combined temperature and pressure gauge Time clock Servicing socket 230 V 50 Hz Control thermostat ON OFF s...

Page 6: ...942 2133 2133 3172 3172 4828 Peak delivery at 45 C L 60 1656 1656 1794 1794 2680 2680 4138 Peak delivery at 60 C L 60 1106 1106 1219 1219 1813 1813 2864 Peak delivery at 70 C L 60 681 681 971 971 1226...

Page 7: ...A C C 2 A mm B mm C mm D mm E mm F mm G mm H mm J mm K mm HM 60 N 1698 1583 538 625 540 390 150 1098 281 1665 HM 60 N BG 2000 S 60 1698 1583 538 801 540 390 150 1098 281 1665 HM 70 1743 1630 678 797...

Page 8: ...7 TECHNICAL SPECIFICATION D G F E J H B K A C D A C C 2 A K H J E C D F G 562 HeatMaster 150 Jumbo HeatMaster 70 N and HeatMaster 100 N Without burner With ACV BG 2000 S premix gas burner...