INstallatIoN
InstallatIon of a sIngle HeatIng
cIrcuIt regulated bY an acV 22 room
tHermostat
SCHEMATIC DIAGRAM
The heating system is controlled by an On/Off room thermostat.
In this configuration, the boiler constantly adapts its operation (minimum
temperature =60C) to the outdoor temperature, if an outside temperature
sensor is connected.
The circulator is triggered as soon as the room thermostat generates a heat
demand.
Advantages for the user:
- Comfort
- Maximum output
- Simplicity of the system
$)
$&9
Before the boiler’s start up, an “Auto Set” is necessary so that the boiler
detects the DHW sensor.
To do this, turn the right button to “RESET” then start up the boiler by
pressing on the ON/OFF switch.
From the time that the display shows “SET” the “RESET” button can be
released.
A. - Heating temperature setting guidelines without external sensor
- Maximum heating temperature limit with external sensor
- The thermostat is positioned on , the heating circuit is deactivated
and the boiler is then in summer mode.
B. - Domestic hot water temperature setting.
optional equipment
code
description
10800018
ACV 22 Room thermostat
10510100
Outside temperature sensor, 12kΩ — AF120
10510900
Safety thermostat RAM 5109:
Mandatory to protect all floor heating circuits.