Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
CH1 Setpoint
82°C
20°C
87°C
CH2 Setpoint
60°C
20°C
87°C
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
0 - 10V Modulation Signal
- This option allows the HeatMaster firing rate to be controlled by an external control system.
Refer to the Installer’s Handbook, Volume 1, for more information.
CH1 Setpoint
prompts to enter the fixed setpoint for a CH1 heating call when a
Setpoint option is chosen in Select CH Demand. Press on
LEFT
or
RIGHT
button
to adjust the required temperature setpoint then press
OK
to store the setting.
The
CH2 Setpoint
screen appears.
CH2 Setpoint
prompts to enter the fixed setpoint for a CH2 heating call when a
Setpoint option is chosen in Select CH Demand. Press on
LEFT
or
RIGHT
button
to adjust the required temperature setpoint then press
OK
to store the setting
and complete the Heating setting.
CH1 Default: 82°C
.
CH2 Default: 60°C
Select CH Demand
prompts the installer to select how a CH Demand is generated. There are three Select CH Demand options,
among which the installer must make a selection.
Thermostat & Setpoint
- This option is only displayed when no outdoor temperature sensor is connected. A central heating call from
a thermostat or zone panel will enable the HeatMaster and the setpoint will be fixed for central heating calls. When Thermostat &
Setpoint is selected, the CH1 Setpoint screen appears.
Constant & Setpoint
- The HeatMaster will maintain setpoint without an external CH call from a thermostat or zone panel. The set-
point will be fixed for CH calls. When Constant & Setpoint is selected, the CH1 Setpoint screen appears.
EZ Setup
Heating Easy setup (no outdoor sensor connected)
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Heating EZ Setup
•
To navigate on the screen, use the
UP
,
DOWN
,
LEFT
and
RIGHT
keys,
OK
•
Use the
OK
key to validate a selection.
•
To increase/decrease values, use the
UP
and
DOWN
keys, or
LEFT
and
RIGHT
, according to the situation