ACV Delta 25 Installation, Operating And Servicing Instructions Download Page 7

3.1

FILLING THE HEATING AND DOMESTIC
HOT WATER CIRCUITS

1. Fill the domestic hot water circuit and bring it up to pressure.

IMPORTANT
The hot water tank must be pressurised before the
heating circuit is filled.

2. Fill the heating circuit taking care not to exceed the 2 bar

pressure limit.

3. Bleed the air from the top of the boiler.
4. After bleeding the air out of the system, bring the pressure up to the

static pressure (height) plus 0.5 bar: 1.5 bar = 10 m – 2 bar = 15 m.

5. Check the power connection, the boiler room ventilation and ensure

that there are no leaks in the flue gas discharge pipes.

6. Set the thermostat (1) to between 60 and 90° C.

3 STARTING 

UP

4

SERVICING

Fig. 11: Control panel

7. Set the Summer/Winter selector switch (3) to the desired position.
8. Switch the on/off switch (2) to the ON position.
9. Check the pressure of the gas supply when starting up.

10. For the oil burner check the oil supply (and return).

Carry out any bleeding, measuring and adjustment work which
may be necessary.

3.2

TROUBLESHOOTING THE  BURNER

3.2.1

ACV BG 2000-S GAS BURNER

Please refer to the servicing and troubleshooting instructions for the
burner.

3.2.2

ACV OIL BURNER

Please refer to the servicing and troubleshooting instructions for the
burner.

Before carrying out any servicing or repair work, switch
the power off at the mains switch fitted in the boiler room
by the electrician.

2

1

3

4.1

RECOMMENDATION

ACV recommend that boilers should be serviced at least once a year.
The burner must be serviced and tested by a competent engineer.

4.2

SERVICING THE  BOILER

1 - Switch the power off at the mains switch outside the boiler and

close the gas tap.

2 - Set the on/off switch on the control panel to the OFF position.
3 - Release and remove the chimney flue (1) to free the top of the

boiler.

4 - Remove the jacket top (2) and lift off the flue reducer (3).
5 - Remove the baffles (4) from the flue pipes (5) for cleaning.

Replace them if they are in poor condition.

6 - Remove the chamber plate (6).
7 - Brush the flue pipes (5).
8 - Clean the burner chamber (7) and the burner (8).
9 - Check the insulation on the chamber plate (6)

1. Chimney flue
2. Jacket cover
3. Chimney flue reducer
4. Baffles
5. Flue pipes
6. Chamber plate
7. Combustion chamber
8. Burner

Fig. 12: Description of the main components

which require servicing.

4.3

SERVICING THE OIL BOILER

-

Switch the power off at the mains switch outside the boiler and
close the oil inlet.

-

Proceed following instructions 2 to 9 in paragraph (4.2 Servicing
the gas boiler).

4.4

SERVICING THE  SAFETY  DEVICES

-

Check that all thermostats and safety devices are working properly:
boiler thermostat, cut-off thermostat and manually reset safety
thermostat.

-

Check the safety valves on both the central heating and the hot
water circuits.

7

3

2

5

4

7

1

6

8

Summary of Contents for Delta 25

Page 1: ...Installation Operating and Servicing Instructions delta excellence in hot water delta performance performance 11 06 2004 66400000 Combination boiler 25 35 45 55 F25 F35 F45 F55 G25 G35 G45 G55 ...

Page 2: ...4 Servicing the burner 8 4 6 Emptying the boiler 8 4 7 Spare parts 8 5 DESCRIPTION 9 5 1 Overview 9 5 2 Description of operation 9 5 3 Build features 10 6 TECHNICAL SPECIFICATIONS 11 6 1 Effective dimensions 11 6 2 Maximum operating conditions 11 6 3 Domestic hot water performance 11 6 4 Boiler without burner 11 6 5 Boiler with ACV oil burner 12 6 6 Boiler with ACV BG 2000 S gas burner 13 7 USER G...

Page 3: ...n accordance with current local standards and regulations 2 2 2 CENTRAL HEATING CONNECTION 2 2 2 1 Examples of basic circuit configurations The drain cock and safety valve must be connected to the waste water disposal system 1 Motorised 3 way manual mixer valve 2 Safety valve preset to 3 bar with pressure gauge 3 Circulator 4 Non return valve 5 System filling valve 6 Expansion tank 7 Room thermost...

Page 4: ...egulations 2 2 3 3 Domestic hot water expansion tank Installing a hot water expansion tank avoids any risk of pressure surges due to waterhammer 2 2 3 4 Hot water circulation If the tank is located a long way from the point of use then installing a closed recirculation circuit ensures that a faster supply of hot water is always available 2 2 3 5 Description 1 Safety unit 2 Pressure reducer 3 Therm...

Page 5: ...d tank L1 L1 H H max 4m H max 4m L1 L m Ø int Ø int H m 8 mm 10 mm 0 5 10 20 1 20 40 1 5 40 80 2 60 100 L m Ø int Ø int H m 8 mm 10 mm 0 35 100 0 5 30 100 1 25 100 1 5 20 90 2 15 70 2 8 30 3 5 6 20 Fig 5b kit 1 Fig 5b kit 2 2 2 4 CONTROLLER KITS KIT 1 ACV 13 00 Basic Basic kit for regulating initial flow temperature according to weather conditions It comprises a temperature regulator with analogue...

Page 6: ... Fig 9 Control panel It is important to switch the boiler off before carrying out any work 2 4 1 3 5 1 Boiler thermostat 60 90 C 2 On off switch 3 Summer Winter selector switch 4 Thermometer 5 Controller optional 6 Safety thermostat 95 C max 7 Safety thermostat 103 C max 8 Plug for power and control 9 Central heating circulator connection 10 Burner connection 11 Room thermostat M Brown O Orange N ...

Page 7: ... repair work switch the power off at the mains switch fitted in the boiler room by the electrician 2 1 3 4 1 RECOMMENDATION ACV recommend that boilers should be serviced at least once a year The burner must be serviced and tested by a competent engineer 4 2 SERVICING THE BOILER 1 Switch the power off at the mains switch outside the boiler and close the gas tap 2 Set the on off switch on the contro...

Page 8: ...e the boiler system s isolating valves 1 3 Connect a hose to the drain cock 2 Make sure that it is properly attached 4 Open the drain cock and let the hot water drain out 5 When the boiler is empty return the valves to their initial positions 4 6 2 EMPTYING THE DOMESTIC HOT WATER TANK 1 Switch the mains power to the boiler off at the external switch installed by the electrician 2 Remove the pressu...

Reviews: