![Acuity Brands HOLOPHANE CORTEZ CZQ2L Manual Download Page 3](http://html1.mh-extra.com/html/acuity-brands/holophane-cortez-czq2l/holophane-cortez-czq2l_manual_2844473003.webp)
IMPORTANT:
Provide each unit with a single-phase AC un-switched power supply from a circuit used for normal lighting. Operating voltage
shown on table on page 3.
PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
NOTE:
The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the battery
is connected longer than 24 hours without continuous AC power provided.
See also “
Important Battery Information
”, page 4.
NOTE:
The maximum mounting height of CZQ2L from ground is 11.7 feet, to meet the minimum illumination requirements of NFPA 101
(current Life Safety Code).
NOTE:
Do not connect battery or power unit until
units (if applicable) are fully connected and wires are isolated from other potentials
(i.e. wires shall be isolated from earth ground).
JUNCTION BOX MOUNTING
-Some details shown below may vary-
On the mounting plate, remove the
round center knockout and the
desired pair of keyhole knockouts
from junction box.
Mounting Plate:
Locate three or two-wire input harness,
make the branch circuit connection
with a UL Listed connector.
NOTE:
Unused input wire should be capped.
Tuck excess wires into the junction
box and push the connector through
the mounting plate knockout ensuring
that enough is sticking out to make the
connection as shown in “Final
Assembly” step 5, page 3.
Junction boxes accommodated:
4” Square
4” Octagon
3-
1/2” Round or Octagon
Single Gang Box
Mount the mounting plate to the
junction box. Prevent the wires from
pinching between the plate and wall.
NOTE: Do not overtighten the
mounting screws. The backplate
must remain flat for the housing
snap features to engage properly.
CONDUIT SURFACE MOUNTING
NOTE: to avoid interference with components in the housing, use the most compact wire connectors appropriate to the wire gauge.
At
upper center of the mounting
plate, remove the conduit connection
knockout. Remove required keyhole
slots from mounting plate to support
the product on the given wall type.
See Wiring Diagram, page 3. Make
code-approved wire connections to the
branch circuit and lamps (if
applicable). Dress wires into slots so
that the connectors are secured as
shown in Figure 2 or Figure 3.
Remove U-shaped knockout from
top center of housing.
Hint:
Use a
pair of wire cutters first to start a cut
in the thick portion at each side of
the knockout, then finish breaking it
out with pliers.
After knockout
removal
1
2
3
1
2
3
Orient conduit fitting so that
all portions of it clear the
edge of the knockout
page 2
INSTALLATION and WIRING
Cut
Figure-2
Figure-3
Battery
Washer
Use washer (Grainger #4DAX6) between
conduit fitting and rear housing if conduit
fitting interferes with battery.
Secure wire connectors near the centre or
near the upper latches.
AVOID grouping
wires and wire nuts in the area of the PCB
and the battery as this may limit engagement
of connector to PCB.