Control for Fire and Comfort Ventilation Type SVM 24V-5A  /  SVM 24V-8A

                                                           

   Control for Fire and Comfort Ventilation Type SVM 24V-5A  /  SVM 24V-8A

The Manual Control Point will generally contain the following:

• 

Breakable glass window and red control button is activated by 

pressure - this puts the control panel in ALARM condition, by 

which the motor output is activated (for normal service and testing 

the lid can be opened with a key).

• 

RESET button which brings the control panel out of the alarm 

condition and starts the closing sequence for about 180 seconds. 

Please note that RESET does not cancel errors on the system, e.g. 

line errors etc. These must be found and corrected.

• 

RED LED indicates that the control panel is in ALARM condition 

and that the motor output either is or has been activated.

• 

YELLOW LED indicates faults on the system - please call for a 

service technician.

• 

GREEN LED indicates that the system is in normal operation 

condition without errors.

CONNECTION of the fire switch is made as shown on the drawing.

The installation with fire switches must be terminated with a 10KΩ or 

27KΩ resistor in the last switch in order to establish the line monitoring 

correctly – this can either be done by moving the factory mounted resistor 

from the terminal strip to the last fire switch or connect 

jumper J1

 in 

the fire switch type BVT is mounted (by this a 10KΩ resistor is also 

connected). 

By means of DIP switches the control panel has different possibilities of 

settings for the input to the fire switch:

DIP 1

 (Conf. firesw.):

On = ALARM condition from 500-3K

Ω

, (indication of line error by direct 

short circuit or open circuit).

Off = ALARM condition from 0-3K

Ω

 (indication of line error by open 

circuit). 

DIP 2

 (Failsafe):

On = Any line error on fire switch or smoke detector puts the control panel 

in ALARM condition. This function can be used if cables to fire switches 

and smoke detectors are not fireproof.

Off = An error condition does not report ALARM condition.

BVT

Operation and connection of Manual Control Points

DIP NO

FA

IL 

S

A

FE

OFF

Fai

l. 

24V

AL

ARM

O

K

 24V

7

4

3

 

Fire switch type BVT 

C

on

. F

ire

. S

w

BVT for line monitoring

2,2Ω

10 KΩ

4

3

2

1

J1

6

7

Fire switch BVT No. 1

R

ed

 L

ED

Yel

lo

w

 L

ED

 

G

re

en

 L

ED

 

10 KΩ

2,2Ω

4

3

2

1

G

nd

11 12

24V

10

13

6

J1

7 6

FI

R

E

15

R

es

et

14

2

1

Fit J1 in last 

2

1

ON

 

REV:

 2 OF 4

Denmark

A4

SCALE:

SHEET: 

DWG NO.:

DRAWN BY: PSP

DATE: 26-09-17

TITLE:

DK 9560 Hadsund 

Haandvaerkervej 2 

1:1

211704_03

Actulux A/S 

www.actulux.com

SIZE:

Phone int.:  +45 98 57 40 90

Fax int.:      +45 96 15 28 00

e-mail: info@actulux.com 

ENGELSK

















































1 green LED OK (lights when OK and while closing)

2 yellow LED (lights on error)

3 red LED alarm (emergency opening)

4 ground (-)

5 not used

6 fire switch reset

7 fire switch emergency opening

Jumper J1 must only be set in the last or only fire switch

Smoke- and heat detectors are connected as shown.
Line monitoring: Correct line monitoring can only be guaranteed with detectors 

delivered from the supplier. Other detectors may have different internal resistances 

and stand by power consumption.

 

Comfort ventilation – Connection and settings

The motor output can be controlled separately with a comfort switch.

For comfort ventilation there are the following possibilities:

 

Potentiometer in Puls pos.: 

It is possible to press the »up« button 3 times, which each gives 6 seconds of opening 

time - after that nothing happens

 – 

Continuous »up« signal gives

 

3x6 sec.=18 sec

One press on »down«

 

closes the actuator completely for a period which is 18 sec. 

longer than the complete opening time - In order to avoid »actuator pumping«

 

max. 3 

successive closing attempts will be allowed.

Potentiometer in Const. pos.:

As long as »up« signal

 

or »down« signal

 

are given, the actuators are running

 

Potentiometer in Puls variable pos.:

The time on the above mentioned pulse opening can be adjusted from 0-60 sec. on the 

potentiometre.
When moving the potentiometer into the different positions the LED batt low will 

flash for about 4 sec. to indicate when in puls mode. LED line fail flashes 4 sec. when 

in constant and AC fail flashes when in puls varaiable.

Connection of smoke-/heat detectors

L1 Out

17

10 

K

Ω

S

m

ok

or

 heat

 s

ens

or

s

L1 Out

L2

Nr.2-20

L1 In

G

nd

16

L1 In

Nr.1

L2

S

m

ok

e

(Only last sensor)

A4

REV:

1:1

DWG NO.:

Denmark

SHEET: 

DRAWN BY: PSP

DATE: 26-09-17

TITLE:

SCALE:

DK 9560 Hadsund 

Haandvaerkervej 2 

211704_04

Actulux A/S 

www.actulux.com

SIZE:

 2 OF 3

Phone int.:  +45 98 57 40 90

Fax int.:      +45 96 15 28 00

e-mail: info@actulux.com 

ENGELSK/TYSK

20

G

nd

18

Up

19

Do

wn

Up

Down

C

om

fo

rt 

Sw

itc

h C

h 1

 

Pu

ls

vari

able

Min

Co

ns

t.

Potmeter for 

comfort feature

Max.

Pu

ls

YEL

YEL

YEL

AC FAIL

LINE FAIL

BATT LOW

Actulux A/S 

211704_05

1:1

 1 OF 2

SCALE:

DWG NO.:

Denmark

DRAWN BY: PSP

DATE: 26-09-17

TITLE:

DK 9560 Hadsund 

Haandvaerkervej 2 

www.actulux.com

SIZE:

SHEET: 

REV:

A4

Phone int.:  +45 98 57 40 90

Fax int.:      +45 96 15 28 00

e-mail: info@actulux.com 

DANSK/ENGELSK/TYSK

Room thermostats, weekly timers, CCS and 

other external control equipment for comfort 

ventilation can be connected on the input of the 

comfort control.

Summary of Contents for SVM 24V-5A

Page 1: ...ation SVM 24V 5A SVM 24V 8A Fire ventilation Comfort ventilation 24VDC max 5A 8A 1 fire ventilation group 1 comfort group Connection for manual control points wind and rain sensor comfort switches smoke detectors Possibility for bus connection of 35 control panels 211731 ...

Page 2: ...__________________________________________________________________________________________________ Comfort control ___________________________________________________________________________________________________ Wind and rain sensor ___________________________________________________________________________________________________ 230V power supply from group ___________________________________...

Page 3: ...ain large amounts of energy which can be released as explosion in case of wrong handling the following safety rules must therefore always be observed Νever short circuit a back up battery Do not use external chargers on installed batteries If unauthorized chargers are used explosive gasses can be released from the battery Do not drop back up batteries as strong acids can be released if they are br...

Page 4: ...mmunication LD3 LD2 flashes for 5 sec when flatcable is connected LD1 power will illuminate when power is on If LD2 fireswitch illuminates linefault on fireswitch If LD3 fireclose illuminates linefault on fireclose Jumper J2 in pos Ext 3 wire Line monitoring between terminal 1 3 With jumper J3 actuator output it is chosen how many lines number of 27KΩ you wish to detect the same way as the motor l...

Page 5: ...re switch BVT No 1 Red LED Yellow LED Green LED 10 KΩ 2 2Ω 4 3 2 1 G nd 11 12 24V 10 13 6 J1 7 6 FIR E 15 R eset 14 2 1 Fit J1 in last 2 1 ON REV 2 OF 4 Denmark A4 SCALE SHEET DWG NO DRAWN BY PSP DATE 26 09 17 TITLE DK 9560 Hadsund Haandvaerkervej 2 1 1 211704_03 Actulux A S www actulux com SIZE Phone int 45 98 57 40 90 Fax int 45 96 15 28 00 e mail info actulux com ENGELSK Ω Ω 1 green LED OK ligh...

Page 6: ...END TERM A3 B1 B2 BUZZER B3 Serial O ut next unit Connection to 21 20 Gnd 23 22 Weather Gnd 24V A2 A1 Serial In Connection from Bus connection for serial connection up to 35 pcs control units of terminal 23 18 Up 17 Smoke 16 Gnd 19 Down 13 24V ALARM Fail 24V 12 11 FIRE Gnd 15 Reset 14 COM 7 NO NC 9 8 Failure Out Alarm Out NC 5 COM 4 NO 6 3 OK 24V 10 START TERM L1 Out L1 In No 1 L2 L1 In L2 Up 2 2K...

Page 7: ...rate a line error Fire switch active from 0 3KΩ A short circuit of the smoke detector input will generate alarm DIP 2 Failsafe No Line error on fire switch or detector puts the control in alarm Normal mode DIP 3 Temp Detekt No Line error on motor line upper resistor area alarm Normal mode DIP 4 Ser Yes Active Inactive DIP 5 Snitch No LED s remember errors line errors AC Batt error bus error The LE...

Page 8: ...tive weather sensor lights as long as input is active As long as the weather sensor is active motor inputs cannot be opened with comfort switches The weather sensor closes on all controls which are connected through bus connection On the input to weather station a weekly timer can be connected which makes sure that everything is closed e g by end of a working day Power Supply to terminal 22 and 23...

Page 9: ...ct cable types and sizes to make sure that the fire ventilation system meets the standards and works correct in an emergency The two most important factors are the ability of the cables to resist heat and to make sure that the voltage drop in the cables to the actuators do not exceed 15 at full load on the fire ventilation hatches Fire resistant cables according to IEC 60331 must be used for the f...

Page 10: ...e 75 degree Heat detector 75 degrees temperature activation 111741 Heat detector base 90 degree Heat detector 90 degrees temperature activation 111740 Smoke detector optical Optical smoke detector 111742 Smoke detector Ion detector Ion smoke detector for invisible smoke 111753 Comfort switch OPUS w housing Comfort switch Opus complete with housing 111758 Comfort switch FUGA w housing Comfort switc...

Page 11: ...nput 1 pcs with line detection Max power consumption for detectors 2 2 mA approx 22 pcs detectors Trigger point 30mA Weather sensor input close all Yes Yes Alarm output Yes potential free contact max 48V 0 5A Yes potential free contact max 48V 0 5A Failure output Yes potential free contact max 48V 0 5A Yes potential free contact max 48V 0 5A 24V DC for external use 24V DC max 0 5A at 230V operatio...

Reviews: