20
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Manufacturer:
Actulux A/S
Håndværkervej 2
9560 Hadsund
Denmark
Tel.: +45 98 57 40 90
Fax: +45 96 15 28 00
e-mail: [email protected]
www.actulux.com
Technical specifications
SVM 24V-5A
SVM 24V-8A
Power supply
230V AC / max. 1.2A
230V AC / max. 1.7A
Output supply
24-28 VDC
24-28 VDC
Motor outputs
1 pcs. (line detecton: 1-4 lines)
1 pcs. (line detecton: 1-4 lines)
Max. load
5A
8A
Operation temperture
-15°C - +40°C
-15°C - +40°C
Density
IP 54
IP 54
Battery back-up (72h)
Yes
Yes
Batteries
2 pcs. 12V/7.2AH
2 pcs. 12V/7.2AH
Dimensions (WxDxH)
238 x 113 x 286 mm
238 x 113 x 286 mm
Weight incl. batteries
7,5 kgs.
7,5 kgs.
Colour
White front / Black indication label
White front / Black black indication label
Fire groups
1 pcs. with line detect. / Max. power consumption for fire switches (LED+buzzer) = 17.6mA=
approx. 8 fire switches
Comfort groups
1 pcs. unlimited number of comfort switches
Detector (smoke/heat) input
1 pcs. with line detection / Max. power consumption for detectors = 2.2 mA = approx. 22 pcs. detectors. Trigger point 30mA
Weather sensor input / close all
Yes
Yes
Alarm output
Yes - potential free contact, max. 48V / 0.5A
Yes - potential free contact, max. 48V / 0.5A
Failure output
Yes - potential free contact, max. 48V / 0.5A
Yes - potential free contact, max. 48V / 0.5A
24V DC for external use
24V DC / max. 0.5A - at 230V operation
24V DC / max. 0.5A - at 230V operation
Bus communication
Yes - connection of 2-35 pcs. control panels - line detection
Visual (LED) indication in front panel
“OK” / “AC fault” / “Low battery” / “Line fault” / “Alarm” / “Comfort open”
Dip switch features
“Service hours (LED’s flash in front panel)” / “Comfort opening interval” / “Temperature detection via motor output” /
“Extra line detection via 3 wire motor output” / Fail safe (alarm by line failure)” / “Sprinkler (close by alarm)” /
“Bus comm. settings (react on Bus comm.)” / “Potential free contact for comfort open”
Approvals / Conforms
EN12101-10:2005 approved and certified - class A (double supply)
- envir. class 1 (to -15°C). Conform EN12101-9.
Primary supply: 27-28.5V DC rippel 600mw P/P
Secondary supply: 20-27V DC
Interruption time: less than 1.5 sec.