background image

User manual and 

installation instruction

Control Panel for Fire Ventilation

SVM 24V-5A / SVM 24V-8A

Fire ventilation   

Comfort ventilation

24VDC max. 5A/8A 

1 fire ventilation group, 1 comfort group 

Connection for manual control points, wind- and rain sensor, comfort switches, smoke detectors

Possibility for bus connection of 35 control panels

#211731

Summary of Contents for SVM 24V-5A

Page 1: ...ation SVM 24V 5A SVM 24V 8A Fire ventilation Comfort ventilation 24VDC max 5A 8A 1 fire ventilation group 1 comfort group Connection for manual control points wind and rain sensor comfort switches smoke detectors Possibility for bus connection of 35 control panels 211731 ...

Page 2: ...__________________________________________________________________________________________________ Comfort control ___________________________________________________________________________________________________ Wind and rain sensor ___________________________________________________________________________________________________ 230V power supply from group ___________________________________...

Page 3: ...ain large amounts of energy which can be released as explosion in case of wrong handling the following safety rules must therefore always be observed Νever short circuit a back up battery Do not use external chargers on installed batteries If unauthorized chargers are used explosive gasses can be released from the battery Do not drop back up batteries as strong acids can be released if they are br...

Page 4: ...mmunication LD3 LD2 flashes for 5 sec when flatcable is connected LD1 power will illuminate when power is on If LD2 fireswitch illuminates linefault on fireswitch If LD3 fireclose illuminates linefault on fireclose Jumper J2 in pos Ext 3 wire Line monitoring between terminal 1 3 With jumper J3 actuator output it is chosen how many lines number of 27KΩ you wish to detect the same way as the motor l...

Page 5: ...re switch BVT No 1 Red LED Yellow LED Green LED 10 KΩ 2 2Ω 4 3 2 1 G nd 11 12 24V 10 13 6 J1 7 6 FIR E 15 R eset 14 2 1 Fit J1 in last 2 1 ON REV 2 OF 4 Denmark A4 SCALE SHEET DWG NO DRAWN BY PSP DATE 26 09 17 TITLE DK 9560 Hadsund Haandvaerkervej 2 1 1 211704_03 Actulux A S www actulux com SIZE Phone int 45 98 57 40 90 Fax int 45 96 15 28 00 e mail info actulux com ENGELSK Ω Ω 1 green LED OK ligh...

Page 6: ...END TERM A3 B1 B2 BUZZER B3 Serial O ut next unit Connection to 21 20 Gnd 23 22 Weather Gnd 24V A2 A1 Serial In Connection from Bus connection for serial connection up to 35 pcs control units of terminal 23 18 Up 17 Smoke 16 Gnd 19 Down 13 24V ALARM Fail 24V 12 11 FIRE Gnd 15 Reset 14 COM 7 NO NC 9 8 Failure Out Alarm Out NC 5 COM 4 NO 6 3 OK 24V 10 START TERM L1 Out L1 In No 1 L2 L1 In L2 Up 2 2K...

Page 7: ...rate a line error Fire switch active from 0 3KΩ A short circuit of the smoke detector input will generate alarm DIP 2 Failsafe No Line error on fire switch or detector puts the control in alarm Normal mode DIP 3 Temp Detekt No Line error on motor line upper resistor area alarm Normal mode DIP 4 Ser Yes Active Inactive DIP 5 Snitch No LED s remember errors line errors AC Batt error bus error The LE...

Page 8: ...tive weather sensor lights as long as input is active As long as the weather sensor is active motor inputs cannot be opened with comfort switches The weather sensor closes on all controls which are connected through bus connection On the input to weather station a weekly timer can be connected which makes sure that everything is closed e g by end of a working day Power Supply to terminal 22 and 23...

Page 9: ...ct cable types and sizes to make sure that the fire ventilation system meets the standards and works correct in an emergency The two most important factors are the ability of the cables to resist heat and to make sure that the voltage drop in the cables to the actuators do not exceed 15 at full load on the fire ventilation hatches Fire resistant cables according to IEC 60331 must be used for the f...

Page 10: ...e 75 degree Heat detector 75 degrees temperature activation 111741 Heat detector base 90 degree Heat detector 90 degrees temperature activation 111740 Smoke detector optical Optical smoke detector 111742 Smoke detector Ion detector Ion smoke detector for invisible smoke 111753 Comfort switch OPUS w housing Comfort switch Opus complete with housing 111758 Comfort switch FUGA w housing Comfort switc...

Page 11: ...nput 1 pcs with line detection Max power consumption for detectors 2 2 mA approx 22 pcs detectors Trigger point 30mA Weather sensor input close all Yes Yes Alarm output Yes potential free contact max 48V 0 5A Yes potential free contact max 48V 0 5A Failure output Yes potential free contact max 48V 0 5A Yes potential free contact max 48V 0 5A 24V DC for external use 24V DC max 0 5A at 230V operatio...

Reviews: