Actulux HCV Series Instructions Manual Download Page 4

4

HCVA/HCVAR

 

- Microprocessor controlled Bus synchronization.

- HCVAR is incl. remote control

- Max. 4 pcs. drives can be synchronized. 

  (1 pcs. HCVAR can be synchronized with up to 3 pcs. HCVA, but max. 1 pcs. HCVAR per   

  synchro set)

- Push / Pulling, Opening / Closing Speed and Stroke length can be programmed.

- Electronic overload protection.

- Reduced speed and force during the last 50 mm of closing (“Soft-close”).

- Drive is supplied with 2.5 m silicone cable.

- Different types of brackets can be mounted, depending on the window and kind of mounting.

- Tested in accordance with EN 12101-2, EN 50130-4.

- Power supply: 190-250 VAC / 50 Hz Max 10A  

- Protective class: IP32 

- Consumption: 0.5A/230 VAC 

 

 

 

- Temperature range: -25°C ~ +75°C

- Inrush current: 45A/230 VAC 

 

 

 

- Locking force: 2000 N 

- Leakage current: <0,25mA / 240 VAC   

 

- Lifecycle: >11000 double strokes 

- Speed open/close: 7 mm/s 

 

 

 

- Duty cycle: 30% at 10 min. running time 

- Soft close speed: 5 mm/s 

- Soft close distance: 50 mm 

- Soft close force: 200 N

  Length of antenna (HCVAR) 35 mm

Features

Technical data

Type

Voltage /  

Current

Pushing  

force

Pulling  

force

Stroke 

length

Speed 

Natural comfort

HCVA/R  500/350

230VAC/25W

500N

500N

350 mm

7 mm/s

HCVA/R  500/600

230VAC/30W

500N

500N

600 mm

7 mm/s

HCVA/R  500/800

230VAC/30W

500N

500N

800 mm

10 mm/s

HCVA/R  500/1000

230VAC/30W

500N

500N

1000 mm

10 mm/s

Dimensions for type

 HCVA

Stroke

Lenght L

350 mm

586 mm

600 mm

711 mm

800 mm

811 mm

1000 mm

916 mm

Summary of Contents for HCV Series

Page 1: ...Instruction Chain drive series HCV Type HCVA 230VAC Type HCVAR 230VAC 211830 Actulux A S Haandvaerkervej 2 DK 9560 Hadsund DENMARK www actulux com ...

Page 2: ...Connection for type HCVA in synchro mode and Wind rain sensor 6 Connection for type HCVAR in synchro mode 7 Mounting instruction 8 Choice of brackets 8 HMB HCV 01 Outwards opening window top hung 8 HMB HCV 02 Inwards opening window bottom and side hung 9 HMB HCV 03 Skylight 10 Function of remote control for HCVAR 11 Pairing HCVAR with remote control 11 Pairing HCVAR with wireless wind rain sensor ...

Page 3: ...operation area of the drives Danger of violent pressure in accessible area Use only in dry rooms For opening and closing of facade and roof windows Maximum pressure force of the chain depends on the length the push force is always the value specified on the drive Application area Stroke pushing force diagram Safety Notes Stroke mm Max Pushing force mm ...

Page 4: ... 250 VAC 50 Hz Max 10A Protective class IP32 Consumption 0 5A 230 VAC Temperature range 25 C 75 C Inrush current 45A 230 VAC Locking force 2000 N Leakage current 0 25mA 240 VAC Lifecycle 11000 double strokes Speed open close 7 mm s Duty cycle 30 at 10 min running time Soft close speed 5 mm s Soft close distance 50 mm Soft close force 200 N Length of antenna HCVAR 35 mm Features Technical data Type...

Page 5: ...or changing parameters Parameter change can only be made by Actulux or an authorized service and sales partner by Actulux Note Do not connect the white and grey wires to 230V Do not use wired comfort switch for HCVAR Use only wireless OPUS switch 111900 Connection for type HCVA in single mode Connection for type HCVAR in single mode L N PE L N PE 230VAC 50Hz black brown blue yellow green white gre...

Page 6: ... blue yellow green white grey grey white black brown blue yellow green Caution The white and gray wire are used for change parameters or for bus communication for synchro mode Parameter change can only be done by Actulux or by an authorized Actulux service and sales partner Note Do not connect white and grey wire to 230V ...

Page 7: ...rameters or for bus communication for synchro mode Parameter change can only be done by Actulux or by an authorized Actulux service and sales partner Note Do not connect white and grey wire to 230V Do not use wired comfort switch for HCVAR Use only wireless OPUS switch 111900 Connection for type HCVAR in synchro mode black brown blue yellow green white grey grey white yellow green blue brown black...

Page 8: ...s application is 600 mm Mounting instructions Application Bracket set Item no Screws Outwards opening window top hung HMB HCV 01 390000 No Inwards opening window bottom and side hung HMB HCV 02 390120 No Skylight HMB HCV 03 390130 No Stroke Y 350 mm 227 mm 600 mm 352 mm Bracket set HMB HCV 01 for top hung 390000 ...

Page 9: ...9 HCVA HCVAR Bracket set HMB HCV 02 for bottom and side hung 390120 Stroke X 350 mm 215 mm 600 mm 340 mm 800 mm 440 mm 1000 mm 545 mm ...

Page 10: ...cified Phone int 45 98 57 40 90 2 3 4 3 2 5 C D 4 6 7 8 A B 5 6 7 8 F 31010100_33010102 E 1 OF 1 HCV 500 350 24 36 48VDC A3 DATE 15 10 19 w Bracket Set 33010102 1 2 0 863 KG REV Fax int 45 96 15 28 00 e mail info actulux com WEIGHT DRAWN BY GS SURFACE TREATMENT FINISH www actulux com DWG NO SCALE SIZE TITLE MATERIAL Actulux A S Haandvaerkervej 2 DK 9560 Hadsund Denmark Stroke X 350 mm 227 mm 600 m...

Page 11: ...l and its LED indicator lights up 3 The LED Buzzer indicator in the chain drive turns off after one flash beep the remote control and chain drive are now paired If you need to remove one remote you have to delete all of them by pressing the Program button for more than 3 seconds until the LED Buzzer indicator has been switched on and off again Now all remote controls are deleted and you need to pa...

Page 12: ... 96 EG about waste electrical and electronic equipment and its implementation into national law useless electrical and electronic equipment must be separately collected and recycled for environment protection Actulux A S Haandvaerkervej 2 9560 Hadsund Denmark Tel 45 98 57 40 90 Fax 45 96 15 28 00 e mail info actulux com www actulux com 2017 Actulux A S Revision B07 211830 16 10 2019 Rights to tech...

Reviews: