Troubleshooting Guide - Advance Split Ducted Unit
Doc. 9590-2015-03 Ver. 3 221111
Troubleshooting Guide
Advance Split Ducted Unit
Fault Code
Description
Possible Causes
Remedies
E88 VSD Micro
Electronic or
EEPROM Error
Microelectronic Fault / EEPROM fault.
DSP self-check error.
Drive configure issue.
Restart the drive and fault
should go away.
Faulty drive.
Replace the drive.
E90 VSD
Compressor
Model
Configuration
Error
Compressor Model Configuration Error
Drive configuration issue.
Replace the drive.
E95 VSD Power
Module Temp
Low or Sensor
(Open or short
circuit)
Power Module Temp. Low or Sensor Open
fault
Verify proper airflow over
the heat-sink of the drive.
Remove any obstructions.
Check if the compressor is
operating within specified
pressure limits.
Find the root cause for not
operating the compressor in
the specified limits.
Check the mounting screws
on the drive, If the problem,
still persists replace the
drive.
Make sure they are tight.