Alarm input explains:
1) to make the alarm input effective, needs to set it in the event the
corresponding alarm open.
2) 8 road alarm input, input type unlimited, is often can open type or
closed type, when using, need to set the alarm polarity
corresponding types.
3) the police probe grounding termination this machine grounding end
(the police probe should by external power source supply).
Alarm output explains:
1) 2 "switch quantity alarm output (often on or closed), external alarm
equipment need to have power supply.
2) to avoid overload and damage the host, and please refer to the
connection of the table relay related parameters
Type
:
HRS1-S DC5V
Contact
material
AuAg
rating
(resistance
load)
Contact Rating
24VDC 2A, 120VAC 1A
Max-Switching
power
120VA 24W
Max-
switchingVoltage
30VAC/120VAC
Max-switching
Current
2A
Dielectric
Strength
Homo-polarity
1000 VAC, 1 min
Inhomo-polarity
1000VAC, 1 min