background image

14 

 
Reinstall  and  components  and  reset  all  switches  and  valves  for  automatic  operation.  
Place the unit back into operation beginning with the filter flush  and field flush start-up 
mode.  Inspect  for  leaks  and  proper  operation.  Check  against  the  original  flows  and 
pressures recorded during the initial system start-up.   

 
Maintenance:  Control Water Filters 
 
ACT 100S and C200S 

The ACT 100S and C200S use a small side-stream screen filter commonly referred to 

as a finger filter to protect the small solenoid orifice passages.  
These  filters  can  be  found  mounted  directly  into  side  outlet 
elbows  on  some  models  of  the  ACT  100S,  external  elbow 
fittings  on  the  100S  and  C200S  as  well  as  inline  couplers  on 
newer  100S  and  C200S  models.  The  small  screen  filter 
requires infrequent removal, but should be looked at least once 
every  six  months  on  continuously  operated  units  and  those 
filtering primary effluent.   
 
Disconnect the hydraulic tubing from the fitting attached to the 
finger  filter.    The  finger  filter  has  wrench  flats  which  can  be 

used  to  unscrew  the  unit  from  the  various  housings  used  to  contain  it.    Rinse  and 
examine the screen and examine it for clogging.  A high pressure sprayer can be used 
to  remove  stubborn  residues.    The  finger  filter  can  also  be  cleaned  by  soaking  it  in  a 
detergent  and  chlorine  combination  which  will  help  to  remove  and  oxidize  organic 
materials typical of primary effluent systems.   
 
Use Teflon tape to seal the threads on the finger filter and reinstall the unit.  Be sure to 
reconnect the control tubing. Re-pressurize filter and inspect the finger filter connections 
for leaks.   
 

Maintenance:  Miscellaneous  

 
Other components and subsystems may require occasional maintenance.  The potential 
presence  of  a  problem  can  be  found  at  times  by  simply  monitoring  the  unit  operating 
and while at rest.   
 
Pressure 

  System  pressure  and  pressure  across  the  filter  system  can  be  monitored  with 

simple  pressure  gages  equipped  with  a  tire  air  chuck  or  tire  pressure  gages 
capable  of  being  used  with  water  and  air.    Here  you  can  check  upstream  and 
downstream pressures across the filters and get a good read on how the pump is 
performing.  Pressure drops of 4 psi to 7 psi across a filter are a good indication 
of a dirty filter and should be either back flushed or removed for cleaning. 

  In  the  field  Schrader  valves  can  be  found  on  most  of  the  popular  air-vacuum 

relief valves and can be used to monitor field conditions.   
 
 
 

Control Water Filter 

Summary of Contents for ACT-100S

Page 1: ...ubsurface drip irrigation it is possible to quickly change dosing amounts in the controller if ponding occurs in any of the zones 5 No Size Limitation the size of standard absorption fields is limited by the need to increase depth of the lines for gravity flow ACT WFS installations are unlimited in size because pressure dosed effluent is applied uniformly throughout the dripper line matrix by pres...

Page 2: ...flow at pump start During back flushing filter valves are closed sequentially to back flush each element and the master valve is closed to concentrate all flow to the specific filter element being back flushed Drain field Equipment and Operation Equipment in the irrigated zones includes 1 2 diameter drip tubing buried 6 12 below grade PVC supply and return headers and mains one electric solenoid v...

Page 3: ...esidential and small commercial systems The ACT WFS Model ACT 100S is designed to protect subsurface drip tubing used for effluent dispersal by removing potential clogging agents The Bioline Dosing Management Controller monitors the system and regulates its operation The ACT Water Filtration System removes suspended solids so only those particles smaller than 100 micron may pass into the drip tubi...

Page 4: ...tling The ACT 200S head works include the same automatic back flushing filter as found in the ACT 100S but in multiples The primary difference between the multiple filter units is that there is no secondary flush only filter as found on the 100S The 200S filter systems use the additional filters as a source of back flush water ACT 100S and Major Accessories ...

Page 5: ...ter for the pre set back flush cycle During the back flush no water is allowed to discharge from the filter units unless equipped with a pressure sustaining valve pilot Operation ACT 100S Filtration Mode Refer to Single Filter Illustration Water enters the inlet fitting and moves through the normally open valve Water moves through the main ring disc filter and discharges through the normally open ...

Page 6: ...ment system Typical flushing events last from 30 seconds to 2 minutes Once the filter back flush is completed the controller turns off the 24 VAC signal and the filter system returns to the Filtration Mode Tank Return Field Flush Backflush Filter Filter ACT 100S Inlet Supply Valve N O Field Flush Valve N C ...

Page 7: ...ial applications where reliability is a must The filter is equipped in a modular design Each filter is independent with regards to filter back flush Each filter side is equipped with a normally open and normally closed valve that reverse during filter back flush In addition the 200S is equipped with a master valve that closes during back flush and does not permit effluent flow to the dispersal fie...

Page 8: ...nds about 2 from the edge of the platform Prepare the site for the head works platform The unit can be installed so that it sits on the ground surface is partially buried or fully buried DO NOT cover the top of the head works box The unit requires occasional maintenance and must be left at or above the finished grade Be careful to set the final grade of the top of box so that grass and surrounding...

Page 9: ...ened to the skid and not allowed to carry any unsupported piping or other loads such as pumps OPERATION Note The following describes startup using the ACT Bioline Dosing Management System IF you are using a different dosing and filter flush controller you must follow the controller manufacturer s recommendations for operation Startup Startup is a critical operation where the system is tested witne...

Page 10: ...e Alarm button for more than 5 seconds or the controller will enter the programming mode Release the button and the pump will start The pump will run for the programmed dosing time and then go into a rest mode until time to start the next scheduled dose The alarm float can be tested in two ways It is recommended the test be done by raising the high water float by hand or with another object The fl...

Page 11: ...rned off and on again in the dosing mode as described under Testing and Inspection MAINTENANCE The components making up the ACT WFS ACT 100S dispersal system require limited maintenance and inspection The operator and or maintenance provider should inspect the entire system for potential leaks and component deterioration a minimum of two times per year The following should be performed each time t...

Page 12: ...re that the gray stack base remains firmly set in the filter body Be careful not to loose the compression spring on top of the disc stack It has two parts the spring and alignment button Place the rings on a small rope or length of braded wire Clean the rings with detergents and treat with a chlorine solution such as household bleach Agitate aggressively and rinse Inspect the rings and insure that...

Page 13: ... filter flush Carefully remove the flush filter cover by unscrewing the top Open the filter carefully and expose the screen filter element This is a course filter 50 30 mesh so the openings will appear fairly large Grasp the filter element carefully and pull it out of the filter housing Be sure that the spinner plate is attached Remove the plate from the housing if it fails to remain with the filt...

Page 14: ...screen and examine it for clogging A high pressure sprayer can be used to remove stubborn residues The finger filter can also be cleaned by soaking it in a detergent and chlorine combination which will help to remove and oxidize organic materials typical of primary effluent systems Use Teflon tape to seal the threads on the finger filter and reinstall the unit Be sure to reconnect the control tubi...

Page 15: ...be removed and cleaned This may be necessary on an annual basis especially if sunlight is present and encourages algal growth The return valve and air vacuum relief valve typically require no annual maintenance but should be observed for leaks or other outward problems TROUBLE SHOOTING System problems can occur that may cause the DRIP TECH system not to function properly Always begin by servicing ...

Page 16: ... option to repair or replace part or all of a defective product or refund part or all of the original purchase price if any part proves to be defective in material or workmanship after return of such product at customer s expense and after such return has been authorized in writing by JNM Technologies Inc THIS BASIC MANUFACTURER S LIMITED WARRANTY IS SUBJECT TO THE TERMS AND PROVISIONS IN SUBSECTI...

Page 17: ...LAIMS JNM TECHNOLOGIES INC SHALL NOT BE RESPONSIBLE FOR THE AFORESAID DAMAGES CLAIMS OR LOSSES DUE TO LATE DELIVERY OR DELIVERY OR NON DELIVER OR OTHERWISE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION AS SET FORTH HEREIN IF JNM TECHNOLOGIES INC SHALL FURNISH TECHNICAL ADVICE OR ASSISTANCE WITH RESPECT TO THE PRODUCTS SOLD HEREUNDER IT SHALL BE GIVEN WITHOUT CHARGE TO BUYER AND SHALL...

Page 18: ...notice of claim offer JNM Technologies Inc in writing prompt opportunity to examine the defective product and correct the defect if possible This warranty shall be void unless buyer delivers the defective product to JNM Technologies Inc at buyer s sole cost and in accordance with JNM Technologies Inc s instructions ...

Reviews: