Technical Manual

A5VR 

CAREFREE SERIES

A5VR030DRM

A5VR035DRM

• 

A5VR040DRM

A5VR050DRM

  

A5VR060DRM

A5VR065DRM

• 

A5VR070DRM

A5VR080DRM

Summary of Contents for A5VCC-V Series

Page 1: ...Technical Manual A5VR CAREFREE SERIES A5VR030DRM A5VR035DRM A5VR040DRM A5VR050DRM A5VR060DRM A5VR065DRM A5VR070DRM A5VR080DRM...

Page 2: ...N P5 2 1 REFRIGERANT CIRCUIT DIAGRAM P5 2 2 INSTALLATION GUIDELINE P6 3 0 ENGINEERING PHYSICAL DATA P18 4 0 PERFORMANCE CURVE P23 4 1 CAPACITY DROP DIAGRAM P23 5 0 OUTLINE DIMENSION P27 6 0 WIRING DIA...

Page 3: ...frigerant 5 R410A V Design for AVR ModelCC Ceiling Concealed Capacity 022 2200W Series V V series Type of additional heater 10 10X100W electric heater Omitted no additional heater Description of the u...

Page 4: ...r 07 07X100W electric heater Omitted no additional heater Series V V series Cooling capacity 028 2800W Model CK Ceiling casette V Design for AVR Refrigerant 5 R410A Brand A Acson Wall Mounted Indoor U...

Page 5: ...del CM Ceiling Mounted V Design for AVR Refrigerant 5 R410A Brand A Acson Ducted Blower Indoors Units A5VDB V Series Product Range A5VDB125V A5VDB140V A5VDB224V Feature Installed above ceiling with ai...

Page 6: ...geration and heating systems Filter Filter Filter Electronic expansion valve Heat exchanger Service valve Service valve Compressor Oil separator Four way valve Low pressor sensor Hairline tube Shut of...

Page 7: ...nstallation Only one obstacle exists at the air intake side see Figure 1 Obstacles exist at the both sides see Figure 2 b Group units installation more than two units Obstacles exist at the both sides...

Page 8: ...bstacle exists at upper side a Single unit installation see Figure 7 b Group units installation more than two units see Figure 8 Obstacle exists at upper side a Single unit installation see Figure 9 F...

Page 9: ...aust and intake side Model 1 The height of obstacle at intake side is absolute when the obstacle at exhaust side is higher than units No obstacle exists at upper side a Single unit installation see Fi...

Page 10: ...l the bottom of foundation to prevent the exhausted air from crossing the unit b Group units installation more than two units see Figure 14 The relation of H A L is as follows L A L H 0 L 1 2H 1000 1...

Page 11: ...it installation see Figure 15 L H b Group units installation more than two units see Figure 16 The relation of H A L is as follows L A 0 L 1 2H 250 1 2H L H 300 Obstacles exist at upper side a Single...

Page 12: ...annot be directly drained to the outdoor unit at the lower layer The overlaid units cannot exceed 2 An obstacle exists at the air intake side see Figure 20 Seal opening A to prevent the exhausted air...

Page 13: ...Multi lined single installation see Figure 21 Multi lined group installation more than two units a group see Figure 22 The relation of H A L is as follows L A L H 0 L 1 2H 250 1 2H L H 300 H L Can no...

Page 14: ...luenced by radiation temperature length etc please adjust it according to the related electric manual Ceiling Concealed Indoor Units Model A5VCC 022V A5VCC025V A5VCC028V A5VCC032V A5VCC036V A5VCC040V...

Page 15: ...ibration and rodents All above intersection surface of power wires are minimum requirements The actual specifications Influenced by radiation temperature length etc please adjust it according to the r...

Page 16: ...Influenced by radiation temperature length etc please adjust it according to the related electric manual Ceiling Mounted Indoor Units Model A5VCM056V A5VCM071V A5VCM112V A5VCM125V Power Supply 220V 50...

Page 17: ...L1 L2 Li i A5VR040 A5VR080DRM 75m Equivalent length A5VR030DRM 60m A5VR040 A5VR080DRM 85m Equivalent length from first bifurcation refnet to furthest piping section 20m L2 Li i Height difference Maxi...

Page 18: ...5 22 23 0 40 41 3 0 70 25 4 0 45 Note The equivalent length of elbow in the table above aims to fulfill installation standards the pipe bending radius of curvature is R 3 5D D for the pipe diameter ab...

Page 19: ...Ampere in heating A 11 8 13 0 16 1 20 6 7 6 24 0 7 8 26 3 10 1 10 5 Max indoors quantity 5 6 6 8 9 11 11 13 Refrigerant R410A Connecting Pipe gas expanded copper tube liquid expanded copper tube Liqu...

Page 20: ...nded copper tube Liquid mm in 6 35 1 4 Gas mm in 9 52 3 8 12 7 1 2 Model A5VCC 063V A5VCC 071V A5VCC 080V A5VCC 090V A5VCC 100V A5VCC 112V A5VCC 125V A5VCC 140V A5VCC 160V Cooling capacity kW 6300 710...

Page 21: ...verheat Connecting Pipe gas expanded copper tube liquid expanded copper tube Liquid mm in 6 35 1 4 9 52 3 8 Gas mm in 9 52 3 8 12 7 4 8 15 88 5 8 Model A5VCK 080V A5VCK 090V A5VCK 100V A5VCK 112V A5VC...

Page 22: ...operation the noise level may be a little higher influenced by the environment Wall Mounted Indoor Units Model A5VWM 022W A5VWM 028W A5VWM 036W A5VWM 045W A5VWM 056W A5VWM 071W Cooling capacity W 2200...

Page 23: ...opper tube liquid expanded copper tube Liquid mm in 6 35 1 4 9 52 3 8 Gas mm in 12 7 1 2 15 88 5 8 Model of AEX AEX 18 2SAP C AEX 22 3SAP C Note 1 Cooling condition Indoor D W bulb Temp 27 19 C outdoo...

Page 24: ...y Drop Piping diagram A5VR035DRM Cooling Capacity Drop Piping diagram A5VR040DRM Cooling Capacity Drop Piping diagram Elevation difference m Elevation difference m Elevation difference m Equivalent pi...

Page 25: ...g Capacity Drop Piping diagram Bifurcation Refnet increase by one size A5VR060DRM Cooling Capacity Drop Piping diagram Elevation difference m Elevation difference m Elevation difference m Equivalent p...

Page 26: ...t increase by one size A5VR065DRM Cooling Capacity Drop Piping diagram A5VR070DRM Cooling Capacity Drop Piping diagram Equivalent piping length m Elevation difference m Elevation difference m Elevatio...

Page 27: ...6 A5VR080DRM Cooling Capacity Drop Piping diagram A5VR030 080DRM Heating Capacity Drop Piping diagram Equivalent piping length m Equivalent piping length m Elevation difference m Elevation difference...

Page 28: ...30 035DRM 756 782 900 380 350 320 138 624 4 R7 5 A5VR040 050 060 065 070 080DRM Model A B C D E F G H I A5VR040 050 060DRM 1196 1222 900 380 350 320 138 624 4 R7 5 A5VR065 070 080DRM 1328 1354 900 380...

Page 29: ...036 040 045 050 056 063 071V Ultra Thin Model A B C D E F G H I J K Fan Amount A5VCC022V 661 900 599 199 962 150 940 412 169 794 163 2 A5VCC025 028 032 036V 763 5 900 599 199 962 150 940 412 169 794 1...

Page 30: ...J K L M N Fan Amount A5VCC080V 950 981 1314 1005 250 151 490 246 187 964 550 208 530 208 2 A5VCC090 100 112 125V 1300 1331 1664 1355 250 151 490 246 187 1314 550 208 530 208 3 A5VCC140 160V 1560 1591...

Page 31: ...30 Bottom air return plenum Free stream air return plenum Air Outet Air Inlet...

Page 32: ...D E Fan Amount A5VDB125V 950 1004 1044 1078 1227 2 A5VDB140V 1150 1204 1244 1278 1427 2 A5VDB224V Model A B C D E Fan Amount A5VDB224V 1681 1399 687 515 1760 2 E 350 251 165 75 830 D C B A 350 696 29...

Page 33: ...4 221 A5VCM056 071 112 125V Model A B C D E F G H J K L M N A5VCM056V 1174 75 1082 68 58 156 1214 57 670 216 319 879 517 A5VCM071V 1174 75 1082 68 93 156 1214 57 670 216 319 879 517 A5VCM112 125V 1674...

Page 34: ...33 EXV BOX OF INDOOR UNITS Model AEX 15 2SAP C D AEX 18 2SAP C D AEX 22 3SAP C D AEX 24 3SAP C OD I mm inch 6 35 1 4 9 52 3 8...

Page 35: ...34 WIRING DIAGRAM...

Page 36: ...35...

Page 37: ...36...

Page 38: ...37...

Page 39: ...r for the condensing water flow out 3 Pay attention to dustproof anti blocking when the pump is connected and it needs cleaning on time to keep smooth flow 3 Evaporator 1 Clean the dirt of fins 2 Clea...

Page 40: ...Content 1 NULL The outdoor unit is in the standby status 2 REST The outdoor unit is in the reset status 3 CST The outdoor unit is in the cooling start process 4 COOL The outdoor indoor unit is in the...

Page 41: ...ery unavailable unit 26 FSPD Choose proper fan gear table 15 30 27 STPR Set static pressure 28 HSRC Set heat pump or cool only 29 FRAL Whether the fire alarm is enabled 30 FRTP Select the type of anti...

Page 42: ...idity too high Dehumidify Setting temperature too low Set up the higher indoor temperature If user unable to fix the problem please contact the local service agent for assistance meanwhile record the...

Page 43: ...ds fresh air unit s allowable range Off Blinking Blinking Fault codes of the wired controller part 1 NB Keypad malfunction of Wired controller 2 NF Wired controller and indoor unit communication malfu...

Page 44: ...linking Off 25 E5 Communication malfunction of household billing system and outdoor units Blinking Blinking Off 26 E6 The indoor capacity exceeds outdoor s maximum allowable range Off Off Blinking 27...

Page 45: ...ressure sensor malfunction Blinking Off Blinking 55 HA High pressure switch disconnection Blinking Off Blinking 56 HB Low pressure over low malfunction Blinking Off Off 57 HC Low pressure sensor malfu...

Page 46: ...80 U6 FAN2 Hall signal malfunction Blinking Blinking Blinking 81 U7 FAN2 Hardware malfunction Blinking Blinking Blinking 82 U8 FAN2 DC busbar under voltage Blinking Blinking Blinking 83 U9 FAN2 IPM o...

Page 47: ...t Dry Timing Fan Sleep LED Green Red Yellow Red A5VCM Silk screen Mode Cool Dry Timing Fan Sleep Heat LED Green Red The following symptoms are not faults of the units Sometimes odorous gases blow out...

Page 48: ...A5VR DRM www acson com my ACSON MALAYSIA SALES SERVICE SDN BHD 129688 D a member of DAIKIN group Lot 4 Lorong 19 1A Seksyen 19 46300 Petaling Jaya Selangor Darul Ehsan MALAYSIA Tel 603 7964 8200 Sales...