1-10
Model
7 m
10 m
15 m
20 m
CC 10C
30
75
–
–
CC 15C
30
75
–
–
CC 20C
30
75
150
–
CC 25C
76
190
380
–
CC 28C / CC 30C
100
250
500
750
CC 38C / CC 40C
100
250
500
750
CC 50C
100
250
500
750
CC 60C
100
250
500
750
ADDITIONAL CHARGE
The refrigerant is pre-charged in the outdoor unit. If the
piping length is less than 5 m, additional charge after vacu-
uming is not necessary. When the piping length is more than
5 m, use the table below.
Additional Charge Operation
This operation must be done by using gas cylinder and a
precise weighing machine obligatorily. The additional charge
is top up into the outdoor unit by suction valve via service
port.
• Remove the service valve plug.
• Connect the low pressure manifold to the suction service
port, center manifold to the cylinder tank and close the
high pressure manifold (see figure below).
Purge all the flexible hose with refrigerant gas.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure manifold valve.
• When the required refrigerant quantity is pumped in the
unit, close the low pressure manifold and the gas cylinder
valve.
• Disconnect the manometer and the gas cylinder. Place back
the service port cap.
Additional Charge in Gram (Cooling Only Unit) (R22/R407C)
Vacuum Pump
Flexible Hose
High Pressure Gauge
Manifold
Low Side
Pressure Gauge
Gas Valve
Refrigerant Piping
Indoor Unit
Outdoor Unit
Liquid Valve
Model
7 m
10 m
15 m
20 m
CC 10CR
40
100
–
–
CC 15CR
40
100
–
–
CC 20CR
50
125
250
–
CC 25CR
100
250
500
–
CC 28CR / CC 30CR
100
250
500
750
CC 38CR / CC 40CR
100
250
500
750
CC 50CR
100
250
500
750
CC 60CR
100
250
500
750
Additional Charge in Gram (Heat Pump Unit) (R22/R407C)
Model
7 m
10 m
15 m
20 m
CC 10C
27
67
–
–
CC 15C
27
67
–
–
CC 20C
27
67
135
–
CC 25C
68
171
342
–
CC 28C / CC 30C
90
225
450
675
CC 38C / CC 40C
90
225
450
675
CC 50C
90
225
450
675
CC 60C
90
225
450
675
Additional Charge in Gram (Cooling Only Unit) (R410A)
Model
7 m
10 m
15 m
20 m
CC 10CR
36
90
–
–
CC 15CR
36
90
–
–
CC 20CR
45
112
225
–
CC 25CR
90
225
450
–
CC 28CR / CC 30CR
90
225
450
675
CC 38CR / CC 40CR
90
225
450
675
CC 50CR
90
225
450
675
CC 60CR
90
225
450
675
Additional Charge in Gram (Heat Pump Unit) (R410A)
Summary of Contents for 4SL10B
Page 2: ......
Page 78: ...6 2 i iv 2 3 3 4 4 5 R410A 9 R407C 9 9 10 Copeland 11 12 12 13 13 14...
Page 89: ...6 13 1 40 2 3 1 40 2 1 1 1 2 1 2 1 1 1 2 2 3 2 2 6...
Page 90: ...6 14 3 4 1 3 2 3 4 5 6 7 8...
Page 91: ......
Page 93: ...d IM CCC 0501 ACSON nI wH WOHI u WHOJ wH uM s s e s q K C VO d VO...
Page 94: ......
Page 98: ...iv tO M tO M tO M tO M tO M d d U V w WM U l u w WH K D U U U s U _ cN UJ s VM...