36
Marvair GAA A/C w/Gas Heat I&O Manual
06/2023 Rev.5
4.4 Equipment Inspection
Concealed Damage
Inspect all cartons and packages upon receipt for damage in transit. Remove cartons and check for
concealed damage. Important: Keep the unit upright at all times. Remove access panels and examine
component parts. ( Note: The top ( optional ) and bottom brackets are stored in the condenser air compart-
ment. Remove them before replacing the side screen ). Inspect refrigerant circuit for fractures or breaks.
The presence of refrigerant oil usually indicates a rupture. If damage is apparent, immediately file a claim
with the freight carrier.
Units that have been turned on their sides or tops may have concealed damage to compressor motor
mounts, to the oil system or to other components. If the unit is not upright, immediately file a claim for
concealed damages and follow these steps:
1. Set unit upright and allow to stand for 24 hours with primary power turned on.
2. Attempt to start the compressor after 24 hours.
3. If the compressor will not start, makes excessive noise, or will not operate, return the unit to the
freight carrier.
General
1. Inspect unit for completeness. Check for missing parts ( e.g. hardware ). Refer to the installation kit
information in section 5.6, Installation Kits.
2. Remove access panels and check for loose wires. Tighten screw connections.
3. Complete and mail the warranty registration card.
4.5 Clearances
The sides and front of the unit must be kept free of any obstructions or anything that impedes or restricts
the movement of intake or exhaust air. Follow local codes.
WARNING
CARBON MONOXIDE, FIRE OR EXPLOSION HAZARD
Failure to have the minimum clearances could result in severe personal injury or death.
AVERTISSEMENT
DANGER DE MONOXYDE DE CARBONE, D’INCENDIE OU D’EXPLOSION
Ne pas respecter les écartements minimum peut entraîner des blessures graves voire mortelles.
MODEL
Min.
Clearance
From the
Front
Min. Clearance
Around Both
Sides
Min. Clearance
Above the Unit
Min. Clearance
Below the Unit
Min.
Clearance Around the
Flue Vent or Pipe
GAA1024/1030/1036
36”
19”
2”
0”
18”
GAA1042/1048/1060
36”
19”
2”
0”
18”
Table 3. Minimum Clearances from Unprotected Combustible Material and For Service
After the unit has been installed, make sure that the unit is level.