ACS ICE CEA1012A Installation & Operation Manual Download Page 27

ICE CEA/CGA1012–1060 Wall Mount AC I&O Manual 

12/2021 Rev.3

27

5.2 – Modulating Head Pressure Control 

A 10K Nominal NTC Thermistor is connected to the “P1” and “P2” inputs for circuit 1 and circuit 2 

respectively. When this sensor is connected, the “FCC IN” is ignored and the thermistor value is used 

as the process variable when controlling the head pressure. The controller modulates the Outdoor Fan 

Motor to maintain a 90ºF temperature setpoint. The controller will always use the greater value of P1 

and P2 input as the reference point. In the event that the Thermistor is disconnected, the controller 

reverts to the “FCC IN” input to control the Head Pressure of the system. 

5.3– Freeze Stat

A 10K Nominal NTC Thermistor is connected to the “FS1” input on the PCB. If the Thermistor is 

not connected, freeze protection will not be provided. If the Thermistor is connected, the control will 

provide the freeze protection by turning the compressor Off at a temperature of 35ºF (+/- 2ºF) on the 

Indoor Coil. The compressor will remain Off until the temperature measured is greater than 45ºF and 

the anti-short cycle time has elapsed. 

5.4– Onboard Thermostat

The Onboard Thermostat requires a 10K NTC thermistor to be connected to the “FS2” input. It also 

requires that the MODBUS functionality is enabled via MODBUS. The Heating Setpoint, Cooling 

Setpoint and Calibration of the sensor has to be configured via MODBUS. Once configuration is 

complete, the unit has the capability to function autonomously to maintain the space temperature. 

Discrete Registers:

Read with Function Code 02, Write to RW or WO registers with Function Code 05

ID

Description

Size

Data Format

R/W

1

Current Status of the Y1 Compressor Call

1 Bit

0 = no call, 1 = call

RW

2

Current Status of the Y2 Compressor Call

1 Bit

0 = no call, 1 = call

RW

3

Current Status of the Humidity Call

1 Bit

0 = no call, 1 = call

RW

4

Current Status of the G Fan Call

1 Bit

0 = no call, 1 = call

RW

5

Current Status of the W2 Electric Heating Call

1 Bit

0 = no call, 1 = call

RW

6

Current Status of the FCC Call

1 Bit

0 = no call, 1 = call

RO

7

High Pressure Switch 1 Status

1 Bit

0 = Open, 1 = Closed

RO

8

High Pressure Switch 2 Status

1 Bit

0 = Open, 1 = Closed

RO

9

Low Pressure Switch 1 Status

1 Bit

0 = Open, 1 = Closed

RO

10

Low Pressure Switch 2 Status

1 Bit

0 = Open, 1 = Closed

RO

11

OFM Mode Selection

1 Bit

0 = PWM, 1 = 0-10V

RO

12

IFM Mode Selectiion

1 Bit

0 = PWM, 1 = 0-10V

RO

13

Test Mode Status

1 Bit

0 = Normal Mode 

1 = Test Mode

RO

14

Status of Compressor 1 Relay Output

1 Bit

0 = Off, 1 = Energized

RO

15

Status of Compressor 2 Relay Output

1 Bit

0 = Off, 1 = Energized

RO

16

Status of RH RelayOutput

1 Bit

0 = Off, 1 = Energized

RO

17

Status of W2 RelayOutput

1 Bit

0 = Off, 1 = Energized

RO

18

Enables or Disables the internal Thermostat Functionality

1 Bit

0 = Off, 1 = Energized

RW

19

Enables or disables reading the thermostat inputs in Modbus 

mode

1 Bit

0 = Modbus only 

1 = Read thermostat Inputs 

Default is 0

RW

Table 7a. MODBUS Discrete Registers

Summary of Contents for ICE CEA1012A

Page 1: ...apter 3 Installation 29 Chapter 4 Start Up 40 Chapter 5 Troubleshooting 41 Chapter 6 Maintenance 44 Chapter 7 Warranty 45 Chapter 8 Start Up Checklist 46 Appendix A Fresh Air Damper Installation 50 In...

Page 2: ...wn on its side may cause oil to leave the compressor and breakage or damage to other components 3 TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or working on the equipment LIN...

Page 3: ...instructions on the inside of the building adjacent to the thermostat END USER Retain these instructions for future reference Table of Contents Chapter 1 Description Specifications 1 1 General Descrip...

Page 4: ...peed 20 Figure 6 Output Termination for Indoor Motor Control Signal 21 Figure 7 Outdoor Motor Speed Setting 21 Figure 8 Output Termination for Outdoor Motor Control Signal 21 Figure 9 Communications S...

Page 5: ...y The CEA CGA Product Data Sheets have detailed information on the capacities and efficiencies for each model See Appendix A for instructions on field installation of electric heat ICE CEA CGA air con...

Page 6: ...Start w Low Ambient CCH EFS W Low Ambient w CCH X Hot Gas Bypass Y Low Ambient w CCH FCC Z Low Ambient w CCH EFS 1 Low Ambient w FCC 2 Low Ambient w FCC EFS 3 CCH w Hot Gas Bypass None 17 Indoor Air Q...

Page 7: ...22 x 6 x 2 565 x 159 x 51 80172 1 8 CGA1012 With Economizer 12 x 25 x 1 305 x 635 x 25 93181 1 8 CEA CGA1020 1024 25 x 16 x 2 635 x 406 x 52 80137 1 8 CEA CGA1030 1036 30 x 16 x 2 762 x 406 x 52 8013...

Page 8: ...ortionally open and return air damper is proportionally closed to maintain between 50 F and 56 F 10 C to 13 C at the mixed discharge air sensor Integral pressure relief allows the indoor air to exit t...

Page 9: ...etin for details Electric Reheat Dehumidification Not available on the CEA1012 A humidity controller allows electric heat and cooling to operate simultaneously ICE air conditioners equipped with the d...

Page 10: ...filters with MERV ratings of 11 13 and 14 when tested to ASHRAE 52 2 Units with economizers have a pre filter on the outside air Lockable Disconnect Access Cover Plate The access plate to the service...

Page 11: ...d with a contactor controlled by a 24 VAC pilot signal Some compressors incorporate an internal PTC crankcase heater that functions as long as primary power is available The heater drives liquid refri...

Page 12: ...12 ICE CEA CGA1012 1060 Wall Mount AC I O Manual 12 2021 Rev 3 Figure 1a Typical Electrical Schematic CEA CGA Non Economizer...

Page 13: ...ICE CEA CGA1012 1060 Wall Mount AC I O Manual 12 2021 Rev 3 13 Figure 1b Typical Electrical Schematic CEA CGA Economizer...

Page 14: ...hangeover to outside air for free cooling The control board must be configured for proper operation of the economizer by selecting the desired changeover temperature The desired temperature is selecte...

Page 15: ...nimum Position Potentiometer W2 jumper The potentiometer controls the amount of outside air introduced in the building when the economizer damper closes or the air conditioner is Off or in Mechanical...

Page 16: ...ernative brands at a future date On all current air conditioners pins 1 2 are jumpered on W3 See item 4 in Figure 4 E N T H A L P I E B T U P A R L I V R E D A I R S E C H U M ID IT R E L A T IV E TEM...

Page 17: ...Potentiometer 0 to 100 Factory setting is 50 2 Field connection from CommStat 4 2 terminal 5 For Honeywell sensors 8 W2 Minimum Position Potentiometer Jumper Jumper Pins 1 2 to Disable Factory settin...

Page 18: ...ommunicatingvaluable information to the end user Special features include 2 Stage operation with varying speed control to optimize latent and sensible capacity built in remote communication MODBUS for...

Page 19: ...ssure Switch LP Low Pressure Switch Switch to Be Closed for Cooling Operation Switch to Be Connected to R Node 16 24 VAC Power Input to PCB 17 Digital Outputs 24 VAC The PCB Makes and Breaks R RH Rehe...

Page 20: ...signal terminations must be used This jumper will be factory installed In replacing the PCB verify the necessary signal and configure the board accordingly Only 2 of the 3 pins should be used for the...

Page 21: ...entiometer See figure below 3 1 2 1 Set for 0 10V Signal Jumper To Remain On The Appropriate Terminal For Correct Operation 2 Set For PWM Signal Jumper To Remain On The Appropriate Terminal For Correc...

Page 22: ...cond The board also allows 15 different MODBUS addresses based on the position of the NET ADDRESS DIP switches The Net Addresses are written in Binary see table below with switch 4 being the least sig...

Page 23: ...missioning startupsequence to ensure safety and system reliability This document is only valid if the system is used as intended This section defines the manner and method of control of the HVAC syste...

Page 24: ...llows 1 Stage 2 Cooling Request Y2 Input 2 Stage 1 Cooling Request Y1 Input 3 Electric Heat Request W2 Input 4 Dehumidification Request Hum Input 5 Indoor Fan Request G Input Note The priority list ab...

Page 25: ...Only CC1 output can achieve partial capacity Both CC1 and CC2 outputs are required to achieve full capacity Request Active Input Active Output Stage 1 Cooling 1 Fixed Compressor Y1 CC1 Partial Capaci...

Page 26: ...g operation In the event that the fault occurs a second time on the same call for cooling the system locks out To clear the fault the Cooling request must be cycled or the system must be power cycled...

Page 27: ...or has to be configured via MODBUS Once configuration is complete the unit has the capability to function autonomously to maintain the space temperature Discrete Registers Read with Function Code 02 W...

Page 28: ...g 16 Bit 1 60 default 25 represents minutes of allowed MODBUS inactivity before switching to onboard T Stat mode RW 10 Current OFM Speed 16 Bit 0 1023 RO 11 Current IFM Speed 16 Bit 0 1023 RO 12 Anti...

Page 29: ...l not start makes excessive noise or will not pump return the unit to the freight carrier 3 2 Installation Requirements General 1 Inspect unit for completeness Check for missing parts e g hardware Ref...

Page 30: ...inches 61 cm 6 inches 15 cm 20 24 30 inches 76 cm 18 inches 46 cm 24 inches 61 cm 6 inches 15 cm 30 36 30 inches 76 cm 18 inches 46 cm 24 inches 61 cm 6 inches 15 cm 42 48 60 30 inches 76 cm 30 inche...

Page 31: ...6 28 x 8 711 mm x 203 mm P N 80675 For CEA CGA1042 1048 1060 30 x 10 762 mm x 254 mm P N 80676 Return Grilles For CEA CGA1020 1024 20 x 12 508 mm x 305 mm P N 80677 For CEA CGA1030 1036 28 x 14 711 mm...

Page 32: ...miliar with all precautions and safety procedures required in such work and is equipped with the proper tools and test instruments 3 4 Porting and Duct Work General Information Note The following inst...

Page 33: ...nditioners Wall Sleeve for CEA1012 one ton air conditioners with an economizer A wall sleeve is required for all installations of the CEA1012 one ton air conditioner if equipped with an economizer The...

Page 34: ...t use duct liner on inside of supply duct within 4 feet 122cm of the unit Galvanized metal duct extensions should be used to simplify connections to duct work and grilles Use fabric boots to prevent t...

Page 35: ...wall You must stabilize the unit on the bracket with the lifting device or by some other means the bracket alone is not sufficient 3 Make sure that the duct flanges are properly aligned with the wall...

Page 36: ...property damage Turn off electrical power at fuse box or service panel BEFORE making any electrical connections and ensure a proper ground connection is made before connecting line voltage Important...

Page 37: ...ng Single Units The power supply should have the proper voltage phase and ampacity for the selected model 1 Refer to the electrical data on the data sticker on the unit for field wiring requirements o...

Page 38: ...he thermostat should be located so that the supply air from the unit does NOT blow directly on to the thermostat Connect the thermostat to the terminal block in the air conditioner as shown in Figures...

Page 39: ...er pour la pompe chaleur uniquement omettre avec les climatiseurs A Les bornes 5 et 7 sont des contacts secs normalement ouverts qui sont ferm s pour indiquer un verrouillage B Les bornes 6 et 7 sont...

Page 40: ...onomizer Equipped models only To check the system operation under different ambient conditions the air temperature and enthalpy sensors must be tricked When outdoor ambient condi tions are higher than...

Page 41: ...oting Start with a visual check are there loose wires crimped tubing missing parts etc Begin deeper analysis only after making this initial inspection The troubleshooting information in this manual is...

Page 42: ...n in refrigerant circuit 2 Check for blockage or restriction especially filter drier and capillary tube assembly 3 Refrigerant overcharge following field service 3 Evacuate and recharge to factory spe...

Page 43: ...and to each compressor terminal to test the motor windings A short circuit at high voltages indicates a motor defect Do not do this test under vacuum 5 On single phase models check the capacitor by su...

Page 44: ...ied before restarting Condenser Periodicallyinspecttheoutdoorcondensercoilandthecabinetairreliefsfordirtorobstructions Remove foreign objects such as leaves paper etc If the condenser coil is dirty it...

Page 45: ...r material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by operating or staging the unit in a corrosive environment 4 Damages caused...

Page 46: ..._____________ Address ________________________________________State________________________ City ___________________________________________ ICE Air conditioner Model No ______________________________...

Page 47: ...s L1 L2_______V L1 L3 ________V L2 L3______V L1 L2 L1 L3 L2 L3 3 Avg Voltage _______________ Max Deviation from avg voltage ______________volts Voltage imbalance 100 x Max Deviation avg Voltage ______...

Page 48: ...mp ________ ________ Evap Leaving Air WB Temp ________ ________ Heater Contactor Amps L1 ________ ________ Heater Contactor Amps L2 ________ ________ Heater Contactor Amps L3 ________ ________ E Cooli...

Page 49: ...essor Amps L3 ________ ________ Notes _________________________________________________________________________ _________________________________________________________________________ ______________...

Page 50: ...s of the supply outlet duct flange on the unit The 1 25 4 mm clearance must extend on all sides of the supply duct for the first 3 feet 1 meter from the unit IMPORTANT ICE requires a minimum of 1 25 4...

Page 51: ...ther heaters 6 Install the two No 10 screws in the heater assembly plate 7 Install wire harness in hole provided in drain pan and then through filter bracket and then into control box 8 Wire the heate...

Page 52: ...E DU CHAUFFAGE PLAQUE DE FINITION POUR ACC S AU CHAUFFAGE P A N N E A U A V A N T S U P R IE U R P A N N E A U A V A N T IN F R IE U R C O U V E R C L E D E L A B O T E D E C O M M A N D E L ASSEMBLAG...

Reviews: