The isolation of the electrode rod may not be damaged resp. removed excepted at the electrode tip. 

 

The electrode rods can be cut arbitrarily by a tong or a saw. After cutting the electrode rod, remove 10 mm of 
the isolation. The electrode may not be mechanically forced at the cutting, to avoid damaging the isolation.  
 

Installation notes

  

 

 

Drive the system pressure free prior installation resp. deinstallation of the device and avoid high temperatures 
to avoid injuries. 

 

Consider enough installation space outside the container, to insert the electrode probe into the plant without the 
use of force. 

 

Install the device if necessary into a bypass if dense heavy foam, wild turbulences or foamed liquids can occur. 

 

Install the electrode probe in such a position in the container, where no strong forces to the side, like e.g. by 
mixer or near fill-in openings, can have an effect to the electrode rods. 
This is especially important for especially long electrode rods. 

 

The non-isolated electrode tips, when mounted, may not make a contact to the wall of the container, if this is 
made of metal or electrically conductive plastic. 

 

Electrode rods longer than 0,5 m must be stabilized among each other or against the wall of the container, 
especially if the filling material is strongly fluctuating.  
Use for the stabilization suitable isolating spacers. 
The distance between the spaces should be not more than 0,5 m. 

 

At horizontal side mounting into a container or also into a pipe for stability reasons the length 
of the electrode rods should be not more than 200 mm. 
At wider electrode rods (8 mm) the length can be longer.  
At a horizontal mounting the electrode rods should be installed at an angel with the  
electrode rod tip below (approx. 20°), to allow an easier flow-off of filling material  
residues and by this to avoid the coat-forming. 
 
 
At horizontal pipelines the length of the electrodes is limited by that way, that in a empty  
pipe, also in the case of liquid residues, the electrically conductive liquid connection  
between the two electrode rods can disconnect.  
Otherwise and empty pipe can be detected as filled. 

 

The tightening of the process connection may only be done at the hexagon by a suitable spanner. The 
maximum permitted torque strength is 100 Nm. 
The screw in of the process connection by using the connection housing is not permitted. 

 
 

Maintenance

 

 

The device is free of maintenance. 

 

The isolation of the electrodes should be checked regularly and also a possible coating at the electrode tips 
should be removed. 

 

A non-conductive coating at the metallic electrode tip can effect error behaviour because no current can flow 
although the electrically conductive filling material makes a connection. 

 

Summary of Contents for SAT

Page 1: ...position control of pumps Wide application range for conductivities higher than 1 S cm for process temperatures from 15 C to 150 C for process pressures from 1 bar to 10 bar materials also for aggres...

Page 2: ...SAT page 2 of 9 Index Application field 3 Function 3 Safety notes 3 Installation 4 Maintenance 4 Repair 5 Electrical connection 5...

Page 3: ...trode probe is mounted directly in the wall of the container or of the pipe by using the respective process connection or installed over the filling material by using a suitable mount The alternating...

Page 4: ...ce is installed and operated in explosive hazardous areas the general Ex construction standards EN IEC 60079 14 VDE 0165 these safety notes and the enclosed EC conformity certificate must be observed...

Page 5: ...y if the filling material is strongly fluctuating Use for the stabilization suitable isolating spacers The distance between the spaces should be not more than 0 5 m At horizontal side mounting into a...

Page 6: ...parated from power leading wires At strong electromagnetic irradiation use principally a cable with shield Connect the cable shield only at one side to earth A suitable evaluation device must by conne...

Page 7: ...5 C Limitation by material Environmental temperature range Terminal enclosure PP 5 100 C Process temperature maximum 15 C 150 C observe limitations Limitation by variant Process temperature range ATEX...

Page 8: ...rocess connection G15 G 1 Process connection G20 G 2 Process connection G10 G 1 Process connection G12 G Terminal enclosure 60mm only with material POM Terminal enclosure 40mm with terminal enclosure...

Page 9: ...others on request Material process connection terminal enclosure D POM 40mm for G G 1 resp 80mm for G 1 G 2 E POM 60mm for G G 1 P PP 40mm for process connection G G 1 M PP 80mm for process connection...

Reviews: