Operating Instructions

DAP-311x0x0S

Direct current/ Direct voltage signals0- 0/4-20 mA, 0-10 VDC

User manual M3

Direct current / direct voltage signals 0-20 mA, 4-20 mA, 0-10 VDC

96x24

M3_31GB.pdf   update: 31.03.2015

Technical features:

• red display from -19999…99999 digits (optional green, orange, blue or tricolour display)
• installation depth: 120 mm without plug-in screw terminal
• multi voltage power supply unit 100-240 VAC, alternatively 10-40 VDC galvanic isolated
• adjustment via factory setting or directly on the sensor signal
• min/max-memory with adjustable permanent display
• 30 additional adjustable support points
• display flashing at threshold value exceedance / undercut 
• navigation keys for the triggering of Hold, Tara, display change, setpoint setting, alarm actuation
• flexible alarm system with adjustable delay times
• volume measurement (Totaliser)
• mathematical functions like reciprocal value, square root, square and rounding
• constant setting / setpoint setting
• sliding averaging
• brightness control via parameter or front keys
• programming interlock via access code
• protection class IP65 at the front
• plug-in screw terminal
• optional: 1 or 2 relay outputs
• optional: sensor supply
• optional: 1 independently scalable analog output
• optional: galv. isolated digital input for the triggering Tara, Hold, display change
• optional: interface RS232 or RS485
• accessories: pc-based configuration-kit PM-TOOL with CD & USB adapter
• on demand: devices for working temperatures of -25

°

C…60

°

C

User manual M3

Direct current / direct voltage signals 0-20 mA, 4-20 mA, 0-10 VDC

96x24

M3_31GB.pdf   update: 31.03.2015

Technical features:

• red display from -19999…99999 digits (optional green, orange, blue or tricolour display)
• installation depth: 120 mm without plug-in screw terminal
• multi voltage power supply unit 100-240 VAC, alternatively 10-40 VDC galvanic isolated
• adjustment via factory setting or directly on the sensor signal
• min/max-memory with adjustable permanent display
• 30 additional adjustable support points
• display flashing at threshold value exceedance / undercut 
• navigation keys for the triggering of Hold, Tara, display change, setpoint setting, alarm actuation
• flexible alarm system with adjustable delay times
• volume measurement (Totaliser)
• mathematical functions like reciprocal value, square root, square and rounding
• constant setting / setpoint setting
• sliding averaging
• brightness control via parameter or front keys
• programming interlock via access code
• protection class IP65 at the front
• plug-in screw terminal
• optional: 1 or 2 relay outputs
• optional: sensor supply
• optional: 1 independently scalable analog output
• optional: galv. isolated digital input for the triggering Tara, Hold, display change
• optional: interface RS232 or RS485
• accessories: pc-based configuration-kit PM-TOOL with CD & USB adapter
• on demand: devices for working temperatures of -25

°

C…60

°

C

Summary of Contents for DAP-311

Page 1: ...RS485 accessories pc based configuration kit PM TOOL with CD USB adapter on demand devices for working temperatures of 25 C 60 C User manual M3 Direct current direct voltage signals 0 20 mA 4 20 mA 0...

Page 2: ...C with sensor supply 24VDC 50mA and digital input 4 10 40VDC with sensor supply 24VDC 50mA and digital input Y others function input 0 0 4 20 mA 0 10V DC function output 0 no output A display with 2 r...

Page 3: ...a min max permanent setpoint value function nominal value function averaging brightness control as well as the control of the digital input and keyboard layout 5 4 3 Safety parameters COD 19 Assignmen...

Page 4: ...code Optional the following functions are available a supply for the sensor a digital input for triggering of Hold Tara one analog output and for further evaluating in the unit With help of the two ga...

Page 5: ...practical applications For devices with current inputs voltage inputs without sensor supply Type M3 3VR5B 0001 S70BD supply 100 240 VAC 50 60 Hz DC 10 Type M3 3VR5B 0001 W70BD supply 10 40 VDC galv i...

Page 6: ...cs controlsystem de 6 3 Electrical connection 4 M3 devices With current respectively voltage input in combination with a 24 VDC sensor supply DAP 311x0x0S with digital input in combination with 24 VDC...

Page 7: ...and parameterise uloc under menu item RUN Parameterisation level Parameter deposited in the menu item can here be parameterised Functions that can be changed or adjusted are always signalised by a fl...

Page 8: ...B interface Software Windows XP Windows VISTA With this tool the device configuration can be generated omitted and saved on the PC The parameters can be changed via the easy to handle program surface...

Page 9: ...ation without application of the sensor signal and SenSU voltage or SENSA current as sensor calibration with the sensor applied Confirm the selection with P and the display switches back to menu level...

Page 10: ...fault 4 20 Three output signals are available 0 10 VDC 0 20 mA and 4 20 mA with this function the demanded signal is selected Setting up the final value of the analog output Out En Default 10000 The f...

Page 11: ...long as the hysteresis is zero The same applies to LI 2 User code 4 digit number combination free available U CodE Default 0000 If this code was set 0000 all parameters are locked for the user if LOC...

Page 12: ...er this the display confirms the settings with and automatically switches to operating mode If Loc was selected the keyboard is locked To get back into the menu level press P for 3 seconds in operatin...

Page 13: ...nd value from the smallest to the highest digit with and confirm each digit with P A minus sign can only be parameterized on the highest value digit After the last digit the display switches back to t...

Page 14: ...000 With this function you can rescale the input value of e g 19 5 mA works setting without applying a measuring signal If sensor calibration has been selected these parameters are not available Resca...

Page 15: ...ised Only activated setpoint parameters are displayed Display values for setpoints dIS 01 dIS 30 Under this parameter setpoints are defined according to their value At the sensor calibration like at f...

Page 16: ...0 20 mA 4 20 mA or 0 10 VDC or via the digital signals of the interface M bus RS232 RS485 Modbus protocol With P the selection is confirmed and the device changes into menu level Back to menu group le...

Page 17: ...SEC and the averaged metering AVG With the selection of AVG in the menu level DISPL the result will be shown in the display and evaluated via the alarms Zero point slowdown ZErO Default 00 At the zer...

Page 18: ...avigation keys and confirmed digit per digit with P A minus sign can only be adjusted on the highest digit After the last digit the display changes back into menu level Display dISPL Default actua Wit...

Page 19: ...aved permanently as offset The device confirms the correct taring by showing ooooo in the display Set tA switches into the offset value and can be changed via the navigation keys Via totAL the current...

Page 20: ...ation keys the device acknowledges this with ooooo in the display The configuration of EHt rE deletes the min max memory If HOLD was selected the moment can be hold constant by triggering the digital...

Page 21: ...LE Default all Analog output parameter can be locked or released for the user En oF the initial or final value can be changed in operation mode Out EO the output signal can be changed from e g 0 20 m...

Page 22: ...t ascii There are two different types of operating modes ASCII and rtu Modbus transfers no binary cycle but the ASCII Code Thus it is directly readable however the data throughput is smaller in compar...

Page 23: ...eactivation of Hold With P the selection is confirmed and the device changes into menu level Selection analog output Out rA Default 4 20 Three output signals are available 0 10 VDC 0 20 mA and 4 20 mA...

Page 24: ...nalog output runs on the set limits e g 4 and 20 mA or to OFF input value smaller than initial value analog output switches on e g 4 mA to End higher than final value analog output switches on e g 20...

Page 25: ...n can only be used in accordance with the semi automatic calibration Chapter 9 Sensor alignment At Cal the relay switches during sensor calibration at cal of during offset calibration and at Cal en du...

Page 26: ...1 ALrM 1 Default actua The dependency of alarm 1 can be related to special functions in detail these are the current measurand the min value the max value the totaliser value sum value the sliding av...

Page 27: ...A limit value undercut is selected with Louu for LOW lower limit value a limit value exceedance with High for HIGH higher limit value If e g limit value 1 is on a threshold level of 100 and allocated...

Page 28: ...he constant storage STEAD the current sum value is saved at each totaliser reset Furthermore it is saved every 30 minutes in the not quick storage of the device If Off is selected the function is deac...

Page 29: ...l digital input Back to menu group level rEt With P the selection is confirmed and the device changes into menu group level tot To return the unit to a defined basic state a reset can be carried out t...

Page 30: ...ia the digital input Switching threshold Threshold limit value of the change over Hysteresis Broadness of the window between the switching thresholds Working principle Operating current quiescent curr...

Page 31: ...8 Interfaces The interface RS485 is connected via a screened data line with twisted wires Twisted Pair On each end of the bus segment a termination of the bus lines needs to be connected This is necce...

Page 32: ...connected manually However the calibration will be interrupted after 30 seconds Press actuator for minimum 3 seconds For minimum 1 measuring cycle minimum 1s or maximum per actuator Current measuring...

Page 33: ...al wire cross section up to 2 5 mm2 Display Digit height 14 mm Segment colour red optional green orange or blue Range of display 19999 to 99999 Setpoint one LED per setpoint Overflow horizontal bars a...

Page 34: ...e Protocol Modbus with ASCII or RTU protocol RS232 9 600 Baud no parity 8 Databit 1 Stopbit cable length max 3 m RS485 9 600 Baud no parity 8 Databit 1 Stopbit cable length max 1000 m Power supply 100...

Page 35: ...suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes Keep input output and supply lines separate from one another and do not lay them parallel with eac...

Page 36: ...ith a low voltage signal it is only connected on one side or the input is open Not all of the activated setpoints are parameterised Check if the relevant parameters are adjusted correctly 3 The word H...

Page 37: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 37...

Page 38: ...TROL SYSTEM GmbH Lauterbachstr 57 D 84307 Eggenfelden Tel 49 0 8721 9668 0 Fax 49 0 8721 9668 30 info acs controlsystem de www acs controlsystem de Wir erwarten Ihren Anruf F llstand Pegel Druck Tempe...

Reviews: