Acromag IntelliPack 841T User Manual Download Page 12

IntelliPack Series 841T Transmitter/Alarm User's Manual                                                                Frequency Input 
___________________________________________________________________________________________ 

 - 12 - 

 

SOFTWARE CONFIGURATION 

 

Units are fully reprogrammable via our user-friendly Windows 

95

 or NT

 IntelliPack Configuration Program (Model 5030-881).  

A cable (5030-902) and converter (5030-913) are required to 
complete the interface (Software Interface Package 800C-SIP).  
See Drawing 4501-643. 
 

The following transmitter and alarm attributes are selectable 

via the IntelliPack Configuration Software.  Refer to the 
IntelliPack Transmitter Configuration Manual (8500-570) for a 
detailed explanation of these attributes and their application.   
 

Input Configuration

 

Input - Range:  

This transmitter can be configured to accept 

any one of the input frequency range types described in 
the Input Specifications, or as an event counter, using the 
IntelliPack Configuration Program. 

Input - Samples (For Averaging Frequency Inputs Only):

  

Input averaging can be set to 1 (default), 2, 4, 8, or 16.  
The value selected indicates the number of input signal 
acquisitions used in computing a running average.  This 
is useful in helping to filter out transients.  Note the 
response time will be increased by the factor selected. 

Input - Resistor (Pullup/Pulldown):

  Utilize the optional on-

board pullup or pulldown circuits according to the input 
type. 

Input - Threshold (Bipolar/Unipolar): 

 Select either bipolar 

(zero crossing), or unipolar (non-zero crossing) input 
signal types.  Two levels of input threshold and hysteresis 
are available for each input type. 

Event Counter - Debounce (0-1000ms):

  0 (disabled) to 1 

second, configurable in 5ms increments.  You must 
select appropriately with respect to input signal 
bandwidth and characteristics.  Used to eliminate 
counting false pulses due to electro-mechanical relay 
contact bounce and other mechanical effects. 

Event Counter - Edge (Rising/Falling):

  Select either the 

rising edge (positive), or falling edge (negative) of the 
input pulses to be counted. 

Event Counter - Termination (Wrap, Auto-Reset, Latch):

  

Select none (wrap), auto-reset, or latching.  None will 
cause the counter to wrap around to zero from 65535.  
Auto-reset will cause the counter to be automatically 
reset to 0 when the value scaled to 100% is reached.  
Latching will cause the counter to latch at the value 
scaled to 100%.  Any counter can be reset to zero at any 
time by applying an active low counter reset signal to the 
CRST terminal, or by clicking on the “Reset Counter” 
button of the IntelliPack Configuration Software. 

Excitation Voltage:

  Use is optional.  Select 8.2V or 

+12V DC.  Internally limited to 24mA, typical.  Available 
at the EXC+ and EXC- terminals of the module. 

Input Calibration

:  The configuration software can be used 

to calibrate the input timing of this module. 

 

Analog Output Configuration 

Output - Range: 

 Unit can be configured for either a voltage 

or current output range.  A jumper must also be installed 
between the output “I+” and “JMP” terminals for voltage 
output (remove this jumper for current output). 

Voltage (Jumper Required):

 0 to 10V DC, 0 to 5V DC 

Current:

 0 to 20mA DC, 4 to 20mA DC, or 0 to 1mA DC 

 
Output -  Mode:

  Select a normal acting (ascending), or 

reverse acting (descending) output response. 

Output Calibration

:  The configuration software can be used 

to calibrate the output conditioning circuit of this module.

 

 
Transmitter Configuration 

Scaling:

  Enter an input value for 0% output and an input 

value for 100% output (these are also field adjustable).  
Scaling is performed after averaging and converts the 
engineering units of the input range (or a portion of the 
input range) to 0 to 100%.  That is, scaling allows virtually 
any part of the selected input range to be scaled to 0% 
and 100% at the output.  For event counters, the input 
value for 100% output is the maximum count value. 

Minimum Input Spans:  

10% of the selected input frequency 

range.  For pulse/event counting inputs, no minimum is 
imposed, but 1000 pulses is recommended to maintain 
reasonable output resolution. 

Transmitter Computation Function

:  This model provides 

proportional computation only and no optional 
computations are provided.  Each input sample is 
converted into a directly proportional output update. 

End Points Configuration:

  Transmitter: Zero/Full-Scale 

Input maps to Zero/Full-Scale Output.  Event counters 
always have a count of 0 as the “zero” input and the 
maximum count as the input for 100% output. 

 
Alarm Configuration (Model 841T-1500) 
 

The model 841T-1500 may be configured for simple limit 
alarms.  You may also refer to the IntelliPack 800A alarm 
family for dedicated alarm modules that support other 
operating functions. 
 

Limit Alarm - Input:

  The input signal range to the alarm is 

the full range for the configured input type, irregardless of 
the scaled range.  For example, if the 0 to 100.00Hz input 
range was selected using the configuration program, the 
alarm can be programmed to any setpoint from 0 to 
100Hz.  If input averaging is used (samples > 1), then the 
averaged input value will be used by the alarm. 

Limit Alarm - Mode:  

Select a High limit or Low limit for the 

limit alarm function of this model.  In this mode, the relay 
will enter the alarm state when either the user-defined 
high or low setpoint is exceeded for the specified amount 
of time (this allows input transients to be filtered).  Relay 
remains in the alarm state until the input signal has 
retreated past the defined setpoint, plus any deadband 
(frequency inputs only), for the specified amount of time.  
A high limit is assumed for the event counter input.

 

Limit Alarm - Setpoint:

  A high or low setpoint may be 

assigned to the relay and is programmable over the 
entire input range (this is also field adjustable).  The relay 
will trip on an increasing input signal for a high setpoint, 
and on a decreasing input signal for a low setpoint.  A 
high setpoint is assumed for the event counter input. 

Summary of Contents for IntelliPack 841T

Page 1: ...Frequency or Pulse Counting Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA D...

Page 2: ...T are registered trademarks of Microsoft Corp 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units w...

Page 3: ...lity of this device to be reprogrammed many times Convenient Field Reprogrammability Adjustment to transmitter zero and full scale plus alarm setpoint and deadband can be made via module push buttons...

Page 4: ...he common DB9P serial port connector of a host computer The adapter also has a 6 wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable described below Re...

Page 5: ...ages from the rail Electrical Connections Terminals can accommodate wire from 12 24 AWG stranded or solid copper Strip back wire insulation 1 4 inch on each lead before installing into the terminal bl...

Page 6: ...tage meter is required to monitor the output level This meter must be accurate beyond the module specifications for best results Note The module s input frequency range must already be set via the Int...

Page 7: ...d Configuration LED Program Indication LED INDICATOR Constant ON FLASHING Yellow Zero Full Scale labeled Z FS Zero Full Scale 841T 1500 Only Yellow Relay labeled RLY High or Low Setpoint High or Low D...

Page 8: ...rking and powered serial interface adapter Acromag s Application Engineers can provide further technical assistance if required When needed complete repair services are available from Acromag 6 0 SPEC...

Page 9: ...tion near the upper end of the range thus decreasing effective accuracy in this range Table 6 Input Measurement Alarm Accuracy Nominal Input Range Accuracy at 25 C Accuracy Over Temperature 0 to 100 0...

Page 10: ...tacts The relay operates as a limit alarm with control of deadband hysteresis latching non latching contacts failsafe non failsafe modes plus relay time delay SPDT Alarm Relay Specifications 841T 1500...

Page 11: ...static Discharge ESD Immunity Complies with IEC1000 4 2 Level 3 8KV 4KV air direct discharge to the enclosure port and European Norm EN50082 1 Surge Immunity Complies with IEC1000 4 5 Level 3 2 0KV an...

Page 12: ...t Range Unit can be configured for either a voltage or current output range A jumper must also be installed between the output I and JMP terminals for voltage output remove this jumper for current out...

Page 13: ...m state or non failsafe operation relay energized in alarm state Failsafe mode provides the same contact closure for alarm states as for power loss while non failsafe mode uses alarm contact closure o...

Page 14: ...SIENT SUPPRESSION DEVICES NOT SHOWN BRTN INP UT 2 3 2 2 FQ IN 5 V INPUT SIGNAL CONDITIONING HYSTERESIS DIV PD BIPO PUP COMPARATOR SERIES 841T SIMPLIFIED SCHEMATIC UNIP REF 1 5 V INPUT ISOL ATION MODE...

Page 15: ...ency Pulse Counting Counts Counts ANALOG INPUT MODEL 811T 1500 ONLY PV PV Percent SEN SOR INPUT BLOCK RANGE ADJUST BLOCK PV Transfer Function Linear Proportional Configuration Variables High or Low Li...

Page 16: ...IntelliPack Series 841T Transmitter Alarm User s Manual Frequency Input ___________________________________________________________________________________________ 16...

Page 17: ...0 T O 3 6 VDC REL AY CO NNECTIO NS Acromag GROUND T B4 M O D E RE L AY P WR 8 4 1 T 1 5 0 0 REMO TE EXTERNAL CO UNTER RESET SW I T CH OPEN COL L ECT OR SEE T B2 INPUT CONNECT IONS ON PAGE 2 PRACT ICES...

Page 18: ...T NOT E 2 T HIS GROUND CONNECT ION IS RECOMMENDED F OR BEST USE CAUT I ON AND AVOID MAKING ADDIT IONAL GROUND CONNECT IONS W HICH COUL D GENERAT E GROUND L OOPS AND MEASUREMENT ERROR T B2 E X C E X C...

Page 19: ...21 24 CONTACT FIGURE A 46 TB4 TB3 GROUND CONTACT FIGURE B RELAY 46 43 45 N O COM 35 42 JMP TB3 PWR 32 34 31 DC V DC 11 14 12 TB2 22 15 25 23 26 DIODE DC LOAD TB4 N C MOV AC LOAD TB4 N C SPDT CONTACTS...

Page 20: ...________________________________ 20 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4...

Page 21: ...______________________________________ 21 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 J CAP JAA...

Reviews: