VI Zero Calibration

1.Preparation

Before performing the hall sensor zero calibration, the hall sensor must be

removed from the power line to ensure the hall sensor is in an unload state.

Then tighten the screws, ensuring that the hall sensor corresponding to the

channel to be calibrated is in a normal working state.

2.Hall Sensor zero calibration

As shown in Figure 1, select the correct channel number according to the

corresponding channel of the Hall to be calibrated; for example, the hall sensor

corresponding to the terminal number 4 and 5 needs to be calibrated, select

"Channel 1", and then click “Zero Calibration" to enter the channel 1 zero point

calibration mode (as shown in Figure 3). If all channels need to be zeroed,

select "Channel All", and then click "Zero Calibration" to enter the zero point

calibration mode for all channels (as shown in Figure 3). When the pop-up

"Zero Calibration Failed" means the Hall zero calibration failed, when the

pop-up "Zero Calibration Successfully" means the Hall zero calibration was

successful;

Figure 1

Figure 2

Figure 3

Figure 4

This screw need to be
tighten.