Acqua GY-NE42RFS Service Manual Download Page 22

 

 

21 

C. much noise, sounds like “ZZZZZ”, comes 
from outlet of capillary. 
d. the temperature fell down very slowly. 

possible that leakage point is there. 

2)The quantity of Gas is 

too much 

If too much Gas was charged into the cycle 
system, the extra gas will occupy some space 
of evaporator, so that the area of heat 
exchange becomes less, unit will work not well. 
Phenomenon of failure: 
a, higher pressure of liquid cycle system than 
norm. 
b, higher temperature of condenser. 
c, larger electric current of compressor 
d, there maybe ice on the suction tube. 
e, when gas is too much, some gas liquid might 
goes back into compressor, compressor will be 
damaged by liquid. 

First stop unit for several minutes, 
and then open charging tube, 
discharge all of gas. Change a new 
filter, and then recharge gas, finally 
sealed the system. 
 

3) There is air in the 
liquid cycle system 

The air in system will cause lower efficiency of 
cooling. 
Phenomenon of failure: 
a, higher pressure of liquid cycle system than 
norm, but the pressure is not over the limit. 
b, higher temperature of discharging tube. 
C, much noise 

First stop unit for several minutes, 
and then open charging tube, 
discharge all of gas. Change a new 
filter, and then recharge gas, finally 
sealed the system. 

4)Low working 
efficiency of 
compressor 

General when a compressor works for many 
years, some parts of compressor were wear, so 
that compressor discharge less gas out, unit 
does not work strongly. 
Phenomenon of failure: 
a, lower pressure of discharging, check the 
pressure of system with pressure meter to see 
if it is normal. 
b, higher temperature of compressor surface. 
C, cut off the discharging tube, to see if you can 
block the gas coming out of the tube when 
compressor is working. 

Change a new compressor. 

5) There is something 
that blocked the liquid 
cycle system 

Some time there is something blocked the 
filter of liquid cycle system, so that unit is not 
cold. 
Phenomenon of failure: 
a, lower pressure of discharging 
b, lower temperature of discharging. 

Change a new filter 

2.NO COOL 
(Popular failure reasons are below): 

Reason 

analysis 

Solutions: 

1) Leakage of gas 

Phenomenon of failure: 

First find out the point of leaking on tube, and 

Summary of Contents for GY-NE42RFS

Page 1: ...GY NE42RFW GY NE42RFS FROST FREE REFRIGERATOR SERVICE MANUAL Refrigerator Service manual NO FROST Model RS 42WL BC 325WY NOTE product specifications are subject to change...

Page 2: ...replacing the main board 11 The instruction of of replacing fan motor 12 The instruction of replacing temperature sensor 13 The instruction of replacing evaporator temperature sensor and temperature f...

Page 3: ...6 Use standard electrical components when replacing them 7 Make sure the hook is correctly engaged Remove dust and foreign materials from the housing and connecting parts 8 Do not fray damage machine...

Page 4: ...3 Parts Description...

Page 5: ......

Page 6: ......

Page 7: ...6 Display controls...

Page 8: ...7...

Page 9: ...ould be about 2kohm and every with the temperature decreases 1 the corresponding resistor value would increase about 45ohm If the measured value is not within the normal scope the sensor is bad and ne...

Page 10: ...e resistance between C S M S and M C Normal range of M S About 36 Normal range of C S About 50 Normal range of M C About 85 If the test result is not in this range then it means the inner coil has som...

Page 11: ...ow If there show0 0 or almost 0 then it is OK If there is no response then it is broken Compressor PTC starter test Use a multi meter to test the resistance between the two end as the pic show If ther...

Page 12: ...s Under compulsory defrosting process displaying b area displays from 99 to 00 After exiting the entire compulsory defrosting process it reverts to normal operation and display The guide for Disassemb...

Page 13: ...7 Take out the main board The instruction of of replacing fan motor 1 Remove the refrigerator compartment Accessories 2 Remove the air duct cover screws 3 Remove the air duct Board 4 Open air duct Boa...

Page 14: ...s 6 Take out fan motor The instruction of replacing temperature sensor Open air duct Board And take out sensor The instruction of replacing evaporator temperature sensor and temperature fuse and heate...

Page 15: ...14 2 Take out the temperature fuse 3 Remove evaporator fixing screws 4 Take out the evaporator 5 Use a screwdriver or pliers to pry open the receiving tank retaining tabs 6 Take out the water drain...

Page 16: ...o cut the Heater cable fixing bolt 9 Take out the heater The instruction of replacing PTC Starting relay and Overload protector 1 The location of the PTC Starting relay and Overload protector 2 Discon...

Page 17: ...uction of replacing Door switch Using a screwdriver to pry the upper cover plate Take out the magnetron switch The instruction of replacing Display board 1 in the display panel Paste tape Prevent scra...

Page 18: ...rd buckle 3 Unplug the display board wires andTake out display board The instruction of of replacing LED Light 1 The location of the LED Light 2 Unplug the electrical wires and remove the screws fixin...

Page 19: ...1 The Refrigerator chamber Tem Sensor is open circuit or short circuit 2 The Refrigerator chamber Tem Sensor is bad 3 The control PCB is bad 1 Using a Multimeter with the ohm switch to measure the res...

Page 20: ...tor of sensor normally at surrounding 25 the resistor should be about 2kohm and every with the temperature decreases 1 the corresponding resistor value would increase about 45ohm If the measured value...

Page 21: ...ing sound in the cabinet when the cabinet or cabinet accessory contracting or expanding this sound will be made which is normal 5 8 The motor operation sound in the compressor is appears to be louder...

Page 22: ...but the pressure is not over the limit b higher temperature of discharging tube C much noise First stop unit for several minutes and then open charging tube discharge all of gas Change a new filter a...

Page 23: ...ck ice blocking Warm the capillary with a hot towel after a while the ice in the capillary melt you can hear a sound of gas flow comes from the capillary abruptly The pressure of absorbing becomes hig...

Page 24: ...o much food in the refrigerator Please put the food properly 5 Wind door is broken Replace wind door 6 Fan motor is broken Replace fan motor NOTE Before doi ng these operati onsabove di sconnectthe ma...

Page 25: ...GY NE42RFW RFS Exploded view...

Page 26: ...GY NE42RFW RFS Exploded view...

Page 27: ...575878 36 upper shelf 1575868 37 self tapping screw 1099081 38 power board part 1609111 39 connecting tube 1051128 40 dry filter 1355795 41 compressor base part 1468187 42 special flange self tapping...

Reviews: