background image

4

area where they will be shaded from the afternoon sun, when 

the heat load is greatest.

•  Consideration should also be given to availability of electric 

power, service access, noise, and shade.

•  The length of the supply and return ducts should be kept to 

a minimum with no sharp radius bends.

•  Overhead obstructions, poorly ventilated areas, and areas 

subject to accumulation of debris should be avoided. The 

hot condenser air must be discharged up and away from the 

home, and if possible, in a direction with the prevailing wind. 

Do not place the unit in a confined space. See 

Figure 9 (page 

17)

 for unit dimensions.

Minimum Clearances

Sufficient clearance for unobstructed airflow through the outdoor 

coil must be maintained in order to achieve rated performance 

(except on supply & return duct (rear) side). However, 36” inches 

from blower access panel, electrical panel, and compressor 

panel is highly recommended for servicing and maintenance. 

For minimum clearances to obstructions, see 

Figure 1

. DO 

NOT install unit in a confined or recessed area that will allow 

discharge air from the unit to re-circulate into the condenser air 

inlet, through the coil.
Service Access Clearance:

Blower and control access panels ............................. 24”

Compressor compartment access panel ................... 24”

Clearance from top of unit  ........................................ 72”

Clearance around condenser coil area to

Wall or shrubs (excludes duct panel side) ................. 12”

Clearances to Combustibles:

Combustible base - wood or Class A, B, or C

roof covering material ................................................. 0”

Supply & return air ducts ............................................ 0”

Duct connection side .................................................. 0”

REQUIREMENTS & CODES

•  All electrical wiring must be completed in accordance with 

local, state & national codes and regulations and with the 

National Electric Code (ANSI/NFPA 70) or in Canada the 

Canadian Electric Code Part 1 CSA C.22.1.

•  The installer must comply with all local codes and regulations 

which govern the installation of this type of equipment. 

Local codes and regulations take precedence over any 

recommendations contained in these instructions. Consult 

local building codes and the National Electrical Code (ANSI 

CI) for special installation requirements.

•  Air Ducts must be installed in accordance with the standards 

of the National Fire Protection Association “Standards for 

Installation of Air Conditioning and Ventilation Systems” (NFPA 

90A), “Standard for Installation of Residence Type Warm Air 

Heating and Air Conditioning Systems” (NFPA 90B), these 

instructions, and all applicable local codes.

• Consult 

Table 1 (page 9)

, and the rating plate for the 

proper circulating air flow and temperature rise. It is important 

that the duct system be designed to provide the correct flow 

rates and external pressure rise. An improperly designed 

duct system can result in nuisance shutdowns, and comfort 

or noise issues.

•  This unit is designed for outdoor installations only and should 

be positioned as described in Locating the Heat Pump.

GENERAL INFORMATION

This packaged heat pump is designed only for outdoor ground 

level installations and can be readily connected to the high static 

duct system of a home. This unit is completely assembled, wired, 

and run tested at the factory. The only connections needed 

for installation are the supply and return ducts, line voltage, 

thermostat wiring and the condensate drain.
This unit has been tested for capacity and efficiency in accordance 

with AHRI standards and will provide many years of safe and 

dependable comfort, providing it is properly installed and 

maintained. Use of components other than those specified may 

invalidate AHRI certification, Code Agency Listing, and limited 

warranty on the heat pump.

Before You Install this Unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. It is 

recommended that the area to be conditioned be completely 

insulated and vapor sealed.

 Check the electrical supply and verify the power supply is 

adequate for unit operation. If there is any question concerning 

the power supply, contact the local power company.

 All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins are 

straight. If necessary, comb fins to remove flattened or bent 

fins. Claims for damage should be filed immediately with the 

carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 
instructions before installing the unit.

Locating the Heat Pump

•  Survey the job site to determine the best location for mounting 

the outdoor unit. Select a solid, level position, preferably on 

a concrete slab, slightly above the grade level, and parallel 

to the home. If possible, select a site for the unit that is as 

close as possible to the proposed return grille location. 

DO 

NOT PLACE UNIT UNDER THE HOME.

•  The unit should be located with consideration of minimizing 

the length of the supply and return ducts with no sharp radius 

bends. If practical, place the heat pump and its ducts in an 

24"

12"

24"

72”

 CLEARANCE  FR

OM 

TO

P

OF UNIT

0"

Rear (Duct) Side

Front Side

Figure 1. Minimum Unit Clearances

Summary of Contents for Q7RE Series

Page 1: ...mportant role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result...

Page 2: ...Air Circulation 10 System Heating 10 System Cooling 10 Short Cycle Protection 10 Emergency Heat 10 Forced Defrost Mode Field Test 10 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 COMP...

Page 3: ...d any other flammable vapors and liquids in the vicinity of the unit CAUTION This unit uses R 410A refrigerant DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the...

Page 4: ...rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed to provide the correct flow rates and external pressure rise An improperly desig...

Page 5: ...insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements HEAT PUMP INSTALLATION Unpacking the Uni...

Page 6: ...or joists Care should be taken when cutting throughcarpetingtoavoidsnags NOTE Inmostinstallationsit will be necessary to cut a similar hole in the fiberboard directly under the hole in the floor Howev...

Page 7: ...rical box of the unit The installer should become familiar with the wiring diagram before making any electrical connections to the unit An electrical disconnect must be located within sight of and rea...

Page 8: ...her location where its operation may be adversely affected by radiant heat from fireplaces sunlight or lightingfixtures andconvectiveheatfromwarmairregistersor electrical appliances Refer to the therm...

Page 9: ...28 1084 29 1027 31 967 33 Tap T3 1266 25 1332 24 1291 24 1245 25 1192 27 1132 28 1067 30 995 32 Tap T4 1518 21 1481 21 1442 22 1400 23 1355 23 1307 24 1256 25 1202 26 Tap T5 1686 19 1644 19 1601 20 15...

Page 10: ...ting Set the thermostat system mode to HEAT and the fan mode to AUTO Change the thermostat temperature selector above the existing room temperature and check for the discharge of warm air at the suppl...

Page 11: ...to the System Heating section on page 10 Anti Short Cycle Timer Test The 5 minute time delay feature can be bypassed by shorting the TEST pins together Heating Mode WhentheTESTpinsareshortedtogetherfo...

Page 12: ...75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 238 135 137 239 139...

Page 13: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 26...

Page 14: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Page 15: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Page 16: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Page 17: ...ctric Heater Power Supply 1 125 Power Supply 0 875 Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Side View MODEL NU...

Page 18: ...connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Emp...

Page 19: ...servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant...

Page 20: ...1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105...

Page 21: ...nd stage outdoor thermostat is field supplied NOTE 2 HUD outdoor thermostat is not factory installed in all models For HUD applications Remove white wire between terminal W2 and W2 IN terminal C G O W...

Page 22: ...22...

Page 23: ...23...

Page 24: ...essure high side Stage 1 Suction Pressure low side FILTER SYSTEM Filter s secured in place YES NO Filter s clean YES NO 10331420 Replaces 10270500 INSTALLER PLEASE LEAVE THESE INSTRUCTIONS WITH THE OW...

Reviews: