background image

10

STARTUP & ADJUSTMENTS

Pre-Start Checklist

The following check list should be observed prior to starting 

the unit.

  Is the unit level? Unit should be level or slightly slanted toward 

the drain for proper condensate drainage.

 Is the unit installed with the proper clearances as listed on 

page 4

?

 Is the wiring correct according to the wiring diagram and 

electrical codes?

  Are all the wiring connections tight? Check the condenser fan 

to make sure it turns freely. 

  Is the overcurrent protection properly sized?

 Is the thermostat wired correctly? Is it installed in a proper 

location?

  To achieve rated capacity and efficiency the compressor must 

be exposed to refrigerant for at least 24 hours prior to running 

and then must be run for a minimum of 12 hours.

Start-Up Procedure

 CAUTION:

If the unit is equipped with a crankcase heater, 

allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. This warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

The control circuit consists of an anti-short cycle timer that will 

not let the compressor re-start before 5 minutes have elapsed.

1. Set the system mode to OFF and the temperature mode to 

its highest setting.

2. Turn power on at the disconnect switch.

3. Set the system mode to ON or COOL.

4. Set the temperature mode below room temperature. Verify 

that the indoor blower, outdoor fan, and compressor energize 

and the cooling function starts.

5. Verify the discharge air grilles are adjusted and the system 

air is balanced.

6. Verify the duct work has no air leaks.

7. Verify the condensate drain is installed correctly and functions 

properly.

8. Set the temperature mode above room temperature. The unit 

should stop.

9. Instruct the homeowner on unit and thermostat operation and 

filter servicing.

Air Circulation

Leave the thermostat system mode on OFF, and set the fan 

mode to ON. Blower should run continuously. Check the air 

delivery at the supply registers and adjust register openings for 

balanced air distribution. Examine ducts for leaks or obstruction 

if insufficient air is detected.
Set the thermostat fan mode to AUTO. The blower should stop 

running.
System Heating

Set the thermostat system mode to HEAT and the fan mode to 

AUTO. Change the thermostat temperature selector above the 

existing room temperature and check for the discharge of warm 

air at the supply registers.
System Cooling

Set the thermostat’s system mode to COOL and the fan mode to 

AUTO. Change the thermostat temperature selector below the 

existing room temperature. Allow the cooling system to operate 

for several minutes and check for the discharge of cool air at 

the supply registers.
Short Cycle Protection

The control circuit is equipped with a time-delay feature for 

protection against short cycling. With the system operating in 

the cooling mode, gradually raise the thermostat temperature 

setting until the whole system de-energizes. Immediately lower 

the thermostat temperature to the original setting and verify that 

the indoor blower is energized. After approximately 5 minutes 

the compressor and the outdoor fan will energize.
Emergency Heat
(Available only when Electric heat is supplied)

1. Set the thermostat’s system mode to EM HT and the fan 

mode to AUTO (intermittent air) or ON (continuous air).

2. Set the thermostat’s temperature selector above the existing 

room temperature and check the following:

•  The thermostat auxiliary heat is indicated as ON.

•  The compressor and the fan should not run; low voltage 

circuit remains energized.

•  The blower runs according to the thermostat’s fan mode 

setting.

Forced Defrost Mode (Field Test)

•  When the 

TEST

 terminals are shorted for more than 3 seconds, 

with the 

Y1

 input active and pressure switches closed, the 

ACST will be eliminated and the compressor contactor output 

energizes. The control will be placed into a forced defrost 

mode.

 

NOTE:

 The coil temperature sensor does not need to be cold 

when the unit is forced into defrost.

•  If the short across the TEST pins exist, the unit will stay 

in DEFROST as long as the short remains or until the 

TERMINATE TIME is reached (11 minutes). This will happen 

regardless of coil temperature.

Table 2. Control Board Status Indicators

STATUS

INDICATOR

STATUS

TYPE

DIAGNOSTIC 

DESCRIPTION

C1

Operating Status Cooling, 1st Stage

H1

Operating Status Heating, 1st Stage

SC

Operating Status Anti Short Cycle Timer

dF

Operating Status Defrost

_.

Operating Status Power on, no call for

operation

01

Fault

Pressure Switch, low

02

Fault

Pressure Switch, high

03

Fault

Temperature Sensor,

Ambient

04

Fault

Temperature Sensor, Coil

05

Fault

Board

dF 

(flashing)

Input Error

Forced defrost - test

short applied longer than

11 minutes

Summary of Contents for Q7RE Series

Page 1: ...mportant role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result...

Page 2: ...Air Circulation 10 System Heating 10 System Cooling 10 Short Cycle Protection 10 Emergency Heat 10 Forced Defrost Mode Field Test 10 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 COMP...

Page 3: ...d any other flammable vapors and liquids in the vicinity of the unit CAUTION This unit uses R 410A refrigerant DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the...

Page 4: ...rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed to provide the correct flow rates and external pressure rise An improperly desig...

Page 5: ...insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements HEAT PUMP INSTALLATION Unpacking the Uni...

Page 6: ...or joists Care should be taken when cutting throughcarpetingtoavoidsnags NOTE Inmostinstallationsit will be necessary to cut a similar hole in the fiberboard directly under the hole in the floor Howev...

Page 7: ...rical box of the unit The installer should become familiar with the wiring diagram before making any electrical connections to the unit An electrical disconnect must be located within sight of and rea...

Page 8: ...her location where its operation may be adversely affected by radiant heat from fireplaces sunlight or lightingfixtures andconvectiveheatfromwarmairregistersor electrical appliances Refer to the therm...

Page 9: ...28 1084 29 1027 31 967 33 Tap T3 1266 25 1332 24 1291 24 1245 25 1192 27 1132 28 1067 30 995 32 Tap T4 1518 21 1481 21 1442 22 1400 23 1355 23 1307 24 1256 25 1202 26 Tap T5 1686 19 1644 19 1601 20 15...

Page 10: ...ting Set the thermostat system mode to HEAT and the fan mode to AUTO Change the thermostat temperature selector above the existing room temperature and check for the discharge of warm air at the suppl...

Page 11: ...to the System Heating section on page 10 Anti Short Cycle Timer Test The 5 minute time delay feature can be bypassed by shorting the TEST pins together Heating Mode WhentheTESTpinsareshortedtogetherfo...

Page 12: ...75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 238 135 137 239 139...

Page 13: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 26...

Page 14: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Page 15: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Page 16: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Page 17: ...ctric Heater Power Supply 1 125 Power Supply 0 875 Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Side View MODEL NU...

Page 18: ...connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Emp...

Page 19: ...servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant...

Page 20: ...1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105...

Page 21: ...nd stage outdoor thermostat is field supplied NOTE 2 HUD outdoor thermostat is not factory installed in all models For HUD applications Remove white wire between terminal W2 and W2 IN terminal C G O W...

Page 22: ...22...

Page 23: ...23...

Page 24: ...essure high side Stage 1 Suction Pressure low side FILTER SYSTEM Filter s secured in place YES NO Filter s clean YES NO 10331420 Replaces 10270500 INSTALLER PLEASE LEAVE THESE INSTRUCTIONS WITH THE OW...

Reviews: