4) Installation 

 
 
 
 
 
 
 
 
 
 

 
 
Fig 3  Fixing hole locations

 

 

IS-D105 sounders should only be installed by trained 
competent personnel. 

 
4.1 Mounting 

 
The IS-D105 sounder may be secured to any flat surface 
using the two M6, 147.0mm pitch fixing centres. The 
enclosure provides IP66 protection and is suitable for 
installation in exterior locations providing it is positioned so 
that water cannot collect in the horn, and the cable entry is 
sealed. 

 
4.2  Installation procedure 

 

a.  Secure the IS-D105 sounder to a flat surface via the 

two M6, 147.0mm pitch fixing centres in the mounting 

feet. 

 

b.  Remove the front of the sounder by unscrewing the 

four captive screws and pulling the front away from 

the enclosure.  

 

c.  Remove the PVC grommet and fit a 20mm cable 

gland or conduit entry into the hole in the enclosure 

and connect the field wiring to the appropriate sounder 

terminals as shown in section 6 and fig 2 of this 

manual. The power supply ter and - are 

duplicated so that sounders may be connected in 

parallel, or an end of line monitoring resistor may be 

fitted. 

 

d.  Select the required output tone by positioning the 6-

way DIP switch as shown in Table 1.0 and Fig 2.  

 

e.  Apply power to the sounder and adjust the internal 

volume control to provide the required sound level. 

 

f.  Replace the front of the sounder and tighten the four 

captive cover screws. 

 

 

5)  Electrical System Design For Installation In 

Hazardous Areas Using Zener Barriers 

 

5.1  Single stage alarm  
 

If the control switch is in the positive supply, or the power 
supply is being turned on and off, only a single channel Zener 
barrier is required as shown in Fig 3. This circuit may also be 
used if the sounder is being controlled by a mechanically 
activated switch on the hazardous area side of the barrier.  
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Fig 4  Single stage alarm using single channel barrier. 
 
If the control switch must be in the negative supply, the circuit 
shown in Fig 4 may be used. Any diode return barrier certified 
Ex ia by a EC Notified Body may be used, providing its 
voltage drop is less than 0.9V.  
 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
Fig 5  Single stage alarm using two channel barrier. 
 

5.2  Multi-stage alarm 
 

Connecting terminal S2 to 0V activates the second stage 
alarm, and similarly terminal S3 for the third stage alarm. Fig 
5 shows how the diode return barriers may be used. If only 
two stages of alarm are required the third stage barrier 
should be omitted, the 28V 93mA barrier and the single diode 
return channel may then be contained in one package. 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 
Fig 6  Multi stage alarm using Zener barriers. 
 
 
 
 

 
 

Barrier 

Power 
Supply 

28V 93mA 
Positive 

Safe Area 

Hazardous Area 

IS-D105 Sounder 
Terminals

On/Off*

0V

To a 
maximum 
of 2 other 
sounders

Barrier 

Power 
Supply 

28V 93mA 
Positive 

Safe Area 

Hazardous Area 

IS-D105 Sounder 
Terminals 

On/Off*

0V

Barrier 

Power 
Supply 

28V 93mA 
Positive 

Safe Area 

Hazardous Area 

IS-D105 Sounder 
Terminals 

On/Off*

Diode Return 
Barrier 

Diode Return 
Barrier 

Diode Return 
Barrier 

3

rd

 Stage* 

2

nd

 Stage* 

0V

To a 
maximum 
of 2 other 
sounders 

To a 
maximum 
of 2 other 
sounders 

Detail of Fixing 
Points 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for IS-D105

Page 1: ...ated device as referred to by Directive 94 9 EC Annex II clause 1 5 3 Installation of this equipment shall be carried out by suitably trained personnel in accordance with the applicable code of practice 4 Repair of this equipment shall only be carried out by the manufacturer or in accordance with the applicable code of practice 5 The certification of this equipment relies on the following material...

Page 2: ...pply voltage is available 3 2 Terminals S2 and S3 When terminals S2 or S3 are connected to 0V terminal the sounder output tone changes to the second or third stage alarm respectively The input safety parameters for these terminals are Ui 28V Ii 0mA Because the permitted input current is zero these terminals may only be connected to a diode return barrier an intrinsically safe relay or a galvanic i...

Page 3: ...Single stage alarm If the control switch is in the positive supply or the power supply is being turned on and off only a single channel Zener barrier is required as shown in Fig 3 This circuit may also be used if the sounder is being controlled by a mechanically activated switch on the hazardous area side of the barrier Fig 4 Single stage alarm using single channel barrier If the control switch mu...

Page 4: ...S D105 sounder second and third stages may be activated by using Galvanically Isolated Relays that have output parameters within the limits specified in section 4 4 which have been certified Ex ia by an EC Notified Body Fig 8 Multi stage alarm using galvanic isolated relays 7 Cable Parameters The maximum permitted cable parameters are as specified on the certificate of the Zener barrier or galvani...

Page 5: ...en Slow rise to 2400Hz Intermittent 1000Hz 1s ON 1s OFF Sawtooth 1200 500Hz 1Hz D I N PFEER P T A P Intermittent 1000Hz 1s ON 1s OFF PFEER General Alarm 420Hz 0 625s Australian Alert 500 1200Hz 3 75s 0 25s Australian Evacuate 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 1 1 0 0 0 0 0 0 1 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 ...

Reviews: