TECHNICAL SPECIFICATIONS 

Power supply battery specifications 

6LR61 type, 9 V 

Operating temperature range 

from -30°C to +70°C 

Maximum tolerated relative humidity 

95% RH (no condensation) 

Weight 

200 grams 

Device’s type indication 

Refers to... 

Photo 

Analogue and enhanced conventional smoke detector 

PhtTherm 

Analogue and enhanced conventional smoke and thermal detector 

Thermal 

Analogue and enhanced conventional thermal detector 

I Module 

Analogue input module or channel 

O Module 

Analogue relay output module or channel 

OModSup 

Analogue supervised output module or channel 

Multiple 

Analogue multiple input / output channels device or analogue multi-
module 

CallPnt 

Analogue call point 

Sounder 

Analogue sounder (wall or base) 

Beacon 

Analogue beacon 

Sound B 

Analogue sounder beacon 

Conv Zon 

Conventional zone module 

Remote I 

Analogue remote indicator lamp 

Special 

An analogue device that is not in this list 

Programming unit message 

Meaning 

Ent Test 
Error! 

This message is given when the enter test, made for the enhanced conven-
tional detector, failed 

Ent Test 
Ok 

This message is given when the enter test, made for the enhanced conven-
tional detector, succeeded 

Fatal Error! 

An irreversible error; if this occurs, the detector is compromised, must not be 
used and needs to be substituted 

Storing 

Indicates that the device is being programmed with the selected parameter 

Stored 

Indicates that the device has been successfully programmed with the selected 
parameter 

Reading 

Indicates that the device is being queried for a parameter value 

Read 

Indicates that the device has been successfully queried for a parameter value 

Failed 

The performed reading or storing operation just failed 

Miss Dev 

No device is connected to the programming unit 

BlankDev 

The connected device has no firmware programmed 

No Addr 

The connected device has no analogue address 

Low batt 

Programming unit battery needs to be changed 

Unspec 

Customer security code is not specified 

IDENTIFIYNG THE DEVICE 

 
Under the 

DevType

 and 

Addr

 captions on the programming unit’s display, the connected analogue devices are visualized as per the follow-

ing table: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

SETTING THE THERMAL OPERATING MODE 

 
Having a detector with a thermal sensing feature connected to the programming unit, while visualizing 

ThrTyp

 on the main menu, press the 

WRITE

 key: 

SelTyp

 (select type) caption will be displayed, and under it will be indicated either 

Std

 (standard ROR mode) or 

High°C

 (high 

temperature mode) depending on the actual thermal operating mode of the detector; if you want to change the thermal mode just press 

UP

 

or 

DOWN 

to select the desired one, then press the 

WRITE

 key. 

You can return to the main menu, if you decided not to change nothing, by pressing on the 

READ

 key. 

 

SETTING THE OPERATING MODE VALUE 

 
While in 

Set Mod / Set Op

 press the 

WRITE

 key. The 

Sel Op

 sub-menu and caption will appear on display: beneath it, three digits will 

indicate the actual programmed operating mode value for the connected device that can be changed by pressing the 

UP

 or 

DOWN

 keys; 

after the value has been chosen, just press 

WRITE

 to memorize it on the connected device. 

You can return to the main menu, if you decided not to change nothing, by pressing on the 

READ

 key. 

 

MESSAGES 

 
The following table illustrates the most common messages given by the programming unit and their meaning: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

POWER OFF 

 
The programming unit switches off by itself after 30 seconds of inactivity. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

WARNINGS AND LIMITATIONS

 

 
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However, 
after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced performance caused by 
external factors. Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced and 
maintained on a regular basis to confirm correct operation. 
 
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice should be sought for special risks. 
Sensors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental condi-
tions. 
 
Refer to and follow national codes of practice and other internationally recognized fire engineering standards. 
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically. 
 

WARRANTY

 

 
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manufacturing defects, effective from the 
production date indicated on each product. 
 
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage. 
Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified. 
 
Full details on our warranty and product return policy can be obtained upon request. 

 