TECHNICAL PARAMETERS
Power supply: 15V ±10% DC
Power consumption in standby mode: ~2.8W
Power consumption of FAM-PV-2NPZS ACC panel: max. 350mA, without E-lock
Number of proximity key fobs (version with built-in ACC): 192 key fobs
Permitted load on E-lock output: 1A
Front: stainless steel; mounted with 3mm Allen (hexagon) screws
Required space for flush-mounted panel: 286 x 90 mm
Hole size for flush-mounted box (ABS): 269 x 73 x 32mm
Size of the optional PNT2-FAM-PRO/PV surface-mounted box (to be purchased separately):
288.4x92.4x(53/39)
PANEL INSTALLATION AND CONNECTION
The panel should be assembled so as to minimise the impact of adverse weather conditions, in particular water. Make sure that the
camera is installed at the desired height. Typically, that height is 1.60 m from the ground. For optimal field of view of the camera,
verify the installation location and position of the panel by trial and error. Avoid locations where the camera lens may be exposed to
direct, perpendicular, light (from the sun, streetlamps, etc.). Install the flush-mounted back box (or flush-mounted adapted) in the
appropriate wall opening, using holes
5
and raw plugs (or screws) as well as gypsum; make sure that the back side of the box flange
A
is flush with the mounting surface. When mounting on a steel pole (similar structure with a maximum wall thickness of 32 mm), use
an additional set of gaskets and screws 3 - available as an option. Run the wires through hole
1
in the box base (cut out the cap if
larger hole is needed). Use additional holes
4
for makeshift installation with nails etc. when mounting the unit in soft materials such
as polystyrene. Holes
4
also make installation easier when using mounting foam. The cover cap
2
should be cut out in order to
install the add-on module in its place. For the best possible tightness, cut out only those holes that are necessary to install the panel.
Check the condition of the gasket on box
B
. Cracks, deformations and soiling of the gasket may lead to loss of tightness.
Connect 15V DC power supply voltage to "+DC" and "GND" terminals of the panel. Connect the E-lock, no specific polarity to be
observed, to "ELOCK" terminals. When using a reversible E-lock, change the panel settings and insert jumper Z1 (can be found
under panel terminals). When using a reversible E-lock, voltage appears at the "ELOCK" output depending on the power supply of
the panel: 15VDC - use suitable reversible E-lock. It is also possible to use the MOD-DC-12V module for 12VDC power supply of
reversible E-lock if the door entry unit is supplied by a 15VDC power supply. Connect the monitor bus (UTP) to relevant panel
terminals, as per the wiring diagram and UTP colours (T568B standard). Before turning the power on, check for possible short circuits
between the wires and make sure that the wires conduct current and are properly connected to RJ45.
Note!
To ensure proper functioning and safety of the door entry unit, connect the grounding
terminal on the metal frame with relevant
protective installation (PE). (ground) with a suitable protective installation (PE).
Allen wrench
3 mm