97
Operation
LipuSmart-P
EN
Menu items
(2nd line)
Settings
(3rd +4th line)
Explanation
Gr
ease separ
ator menu
Max. current P1
0 – 12 A
Maximum power consumption for the inner
cleaning HP pump.
Automatic switching off of the inner cleaning
HP pump if the set power consumption is
exceeded.
Max. current P2
0 – 12 A
Maximum power consumption for the disposal
pump.
Automatic switching off of the disposal pump if
the set power consumption is exceeded.
Inspection every
ÏÏORÏÏ
days
3PECIlEDÏMAINTENANCEÏINTERVALS
Lifting plant menu
Level
0 – 200 cm
Current water level in the lifting plant
Baseload ON
0 – 200 cm
!CTIVATIONÏPOINTÏFORÏlRSTÏPUMPÏ
Baseload OFF
0 – 200 cm
3WITCHOFFÏPOINTÏFORÏlRSTÏPUMPÏ
0EAKÏLOADÏ/.
0 – 200 cm
Activation point for additional pump
0EAKÏLOADÏ/&&
0 – 200 cm
3WITCHOFFÏPOINTÏFORÏADDITIONALÏPUMP
High water level
0 – 200 cm
High water level alarm if exceeded
Run time altern.
deactivated
1 – 60 min
The pump changeover is after the set time
in the basic load mode. After three changes
without interruption the High water level alarm
ISÏALSOÏTRIGGEREDÏANDÏTHEÏ@3TOPÏDELAYÏMESSAGEÏ
appears in the display.
Run. Time max.
0 – 60 min
6ALUEÏ@ÏDEACTIVATESÏTHEÏFUNCTIONÏ)FÏTHEÏPUMPÏISÏ
OPERATEDÏWITHOUTÏINTERRUPTIONÏTHEÏSYSTEMÏSHUTSÏ
down automatically after the set Stop delay.
The pump does not start up again until the
DEFECTÏHASÏBEENÏACKNOWLEDGED
Stop delay
0 – 60 s
3TOPÏDELAYÏPERIODÏOFÏTHEÏPUMPÏAFTERÏTHEÏSWITCH
off point.