Installation 

Wireless sensors should be installed within 200 to 300 feet of the receiver.  RR2552 signal repeaters can be 
installed as to increase transmission distance between sensors and receivers. 

 
          

CAUTION 

Observe battery polarity when installing battery. 

 
To select the proper sensor location, 

first install and power the receiver

.  

To activate the sensor insert the 

battery observing the polarity.

 The mesh networked Series 2000 system does not require any additional wireless 

equipment to determine the proper location of the sensors. 

While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times every 
10 seconds.  Once a connection has been established the Data-Link LED will blink once to indicate the data 
transmission has been received successfully.  The Data-Link LED will continue to blink once for every data 
transmission.  The data transmission rate is programmed into the sensor (normally 1 minute intervals).  To 
manually initiate a data transmission press the push button switch located by the negative terminal of the battery. 

Once the sensor location has been determined mount the sub-base on an inside wall approximately 4.5 feet from 
the floor (or in the specified location) to allow exposure to the average zone temperature using two #8 screws, 
Velcro™ or double sided tape. 

Locate and record the sensor ID numbers located on a label inside the unit prior to mounting 

Do not mount the sensors on an outside wall, on a wall containing water pipes or near air ducts.  Avoid locations 
that are exposed to discharge air from registers or radiation from lights, appliances, or the sun. 

Attach the wall sensor to the sub-base by tightening the two locking screws at the bottom of the sub-base. 

NOTE:

 The locking screw must be installed for a secure installation.  The screws are turned counter-clockwise 

to secure the cover. 

The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low.  A low 
battery signal is also sent to the receiver for remote indication that the battery should be replaced.  If the battery 
is not replaced in approximately 2 months the battery voltage will become so low that the Low Battery and Data-
Link LEDs will not blink.  Replace the battery and the Data-Link LED will start blinking while the sensor is re-
establishing communications with the receiver. 
 

 

PRECAUTIONS 

S

ENSORS

,

 REPEATERS AND RECEIVERS SHOULD 

NOT

 BE INSTALLED IN THE FOLLOWING AREAS

 

I

NSIDE METAL ENCLOSURE 

/

 PANEL 

 

 

INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT 

/

 ELEVATOR BANKS

 

 

IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER

 

T

RANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED

 

 

CAUTION 

DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS

 

WHERE HUMAN LIFE MAY BE AFFECTED

 

 

!

!

!