background image

 

AUTOMATION COMPONENTS, INC                                                                                                                                             Version : 1.0  
2305 Pleasant View Road                                                                                                                                                                         I0000684   
Middleton, Wisconsin 53562                                             

Page 2 of 4                                       

www.workaci.com

  (888) 967-5224                                                                                                                                            

 

General Description 

The mesh network Series 2000 SST2630 is a battery operated spread spectrum wireless remote/strap-on 
temperature sensor. 

The  sensor is encapsulated in a 0.25” O.D. 304 stainless steel probe (2” probe length) for single point pipe 
temperature monitoring. 

ACI’s mesh network Series 2000 wireless sensors utilize reliable Spread Spectrum Radio technology.  They can 
be installed easily in minutes eliminating hundreds of feet of wire and saving installation cost while reducing 
installation labor risks. 

The Series 2000 sensor Data-Link LED confirms the data transmission was received by the receiver for fast and 
reliable positioning of the sensor during installation.  

There is no need for special wireless installation equipment 

or tool.

 

Together with the ACI Series 2000 receivers and controllers, the ACI wireless sensors can be used with any 
LON, BacNet, MODbus, or DDC control system or panel. 

The maximum radio transmission distance is dependent on the building type.  The maximum open air 
transmission distance is one mile.  In a typical commercial building with steel I-Beam construction, concrete 
floors with reinforcing rod, and metal stud walls, it can be expected that transmissions will penetrate vertically 
through floors and horizontally through 200 to 500 feet of walls, furniture and air. 

Installation 

Wireless remote/strap-on sensors should be installed within 200 to 500 feet of the receiver.  RR2552 signal 
repeaters can be installed as needed to increase transmission distance between sensors and receivers. 

 
          

CAUTION 

Observe battery polarity when installing battery. 

 
To select the proper sensor location, 

first install and power the receiver

.  

To activate the sensor insert the 

battery observing the polarity.

 The mesh networked Series 2000 system does not require any additional wireless 

equipment to determine the proper location of the sensors. 

While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times every 
10 seconds.  Once a connection has been established, the Data-Link LED will blink once to indicate the data 
transmission has been received successfully.  The Data-Link LED will continue to blink once for every data 
transmission.  The data transmission rate is programmed into the sensor (normally 1 minute intervals).  To 
manually initiate a data transmission press the push button switch located by the negative terminal of the battery. 

The sensor probe should be mounted under any insulation in direct contact with the pipe using metal pipe straps.  
For proper measurement of temperature, thermal conductive compound should be used in between the sensor 
probe and the pipe.  The installation should be wrapped with insulation to reduce the effect of ambient air.  The 
plastic housing of the sensor can either be mounted on the pipe with metal pipe strap or wall mounted.   

Locate and record the sensor ID numbers located on a label inside the unit prior to mounting. 

The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low.  A low 
battery signal is also sent to the receiver for remote indication that the battery should be replaced.  If the battery 
is not replaced in approximately 2 months,  the battery voltage will become so low that the Low Battery and 
Data-Link LEDs will not blink.  Replace the battery and the Data-Link LED will start blinking while the sensor 
is re-establishing communications with the receiver. 
 
Then attach the cover of the sensor by installing the four screws. 
 

!

Reviews: