PRODUCT SPECIFICATIONS
0.5 to 4.5 VDC Output Only:
5.00 VDC +/- 0.500 VDC
4 to 20 mA
and
1 to 5 VDC Outputs Only:
+8 to 30 VDC (No Load)
4-20 mA Output:
250 Ohm Load: +13 to 30 VDC | 500 Ohm Load: +18 to
30 VDC
4 to 20 mA:
25 mA minimum | 0.5 to 4.5 VDC: < 3 mA | 1 to 5 VDC: < 5 mA
4 to 20 mA (2-Wire, Loop Powered); 0.5 to 4.5 VDC (3-Wires); 1 to 5 VDC
(3-Wires)
15 to 300 PSIG/PSIS:
3x FS | 15 to 300 PSIG/PSIS: 3x FS
15 to 3000 PSIA:
3x FS |
15 to 3000 PSIA:
10x FS or 15,000 PSI
(whichever is less)
500 to 750 PSIS:
3x FS | 500 to 750 PSIS: 3x FS
1000 to 3000 PSIS:
3x FS | 1000 to 3000 PSIS: 10x FS or 20,000 PSI
(whichever is less)
15 to 60 PSIG/PSIS:
< +/- 1.0% FS;
75 to 300 PSIG/PSIS:
< +/- 0.5% FS
500 to 750 PSIS
3
:
< +/- 0.5% FS;
1000 to 5000 PSIS
3
:
< +/- 1% FS
15 to 200 PSIA:
< +/- 0.5% FS;
300 to 750 PSIA:
< +/- 0.5% FS;
1000 to
3000 PSIA:
< +/- 1% FS
15 to 60 PSIG/PSIS:
< +/- 1.0% FS;
75 to 300 PSIG/PSIS:
< +/- 0.5% FS
500 to 750 PSIS:
< +/- 0.5% FS;
1000 to 3000 PSIS:
< +/- 1% FS
15 to 200 PSIA:
< +/- 0.5% FS;
300 to 750 PSIA:
< +/- 0.5% FS;
1000 to
3000 PSIA:
< +/- 1% FS
+/- 0.03% FS @ 0 PSIG; +/- 0.12% FS @ 1000 PSIG
-40 to 221ºF (-40 to 105ºC) | -40 to 176ºF (-40 to 80ºC)
304L or 316L Stainless Steel | See Datasheet for more details
0 to 95% RH, non-condensing
Any gas or liquid compatible with 304L or 316L Stainless Steel
All Ports except “U” and “Y”: 150 lbs-in (16.95 Nm); Ports “U” and “Y”: 120
lbs-in (13.56 Nm)
Packard Connector (Cables ordered separately per “Ordering Grid” on back
of data sheet)
“-124” (24 Lead Length):
PVC Jacketed Cable 18 (0.823 mm
2
) or 24 AWG
(0.2047 mm
2
)
“-MD” Din 43650:
Hirschman® Connector with 90º Mating Connector
SENSOR NON-SPECIFIC INFORMATION
Supple Voltage:
Supply Current:
Output Signal:
Proof Pressure | Burst Pressure:
Accuracy @ 22°C (71.6°F):
*Accuracy includes Hysteresis,
Repeatability, and Non-linearity (BFSL)
Thermal Error (-40° to 105°C):
*Additional error over temperature
range
Stability (250 Hours @ 225°F (125°C)):
Operating | Storage Temperature
Ranges:
Process Fitting Material | Thread Size:
Operating Humidity Range:
Media Types:
Recommended Torque Specifications:
Wiring Connections:
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone:
1-888-967-5224 |
Website:
workaci.com
Page 5
Version: 3.0
I0000792
Note 1:
PSIS transducers are not vented to atmosphere, but are calibrated to have 0.5 VDC, 1 VDC or 4 mA at +14.5 PSIG