PROBLEM
No Output or Output Signal Reading Low:
Output Signal is Inaccurate:
SOLUTION(S)
•
Confirm the DC supply voltage is:
•
0.5 to 4.5 VDC Output Only: 5.00 VDC +/- 0.500 VDC.
•
4 to 20 mA and 1 to 5 VDC Outputs Only: +8 to 30 VDC (No
Load).
•
4-20 mA Output: 250 Ohm Load: +13 to 30 VDC | 500 Ohm Load:
+18 to 30 VDC.
•
Disconnect the sensor from the line to ensure No debris or sediment
is blocking the inlet port of the transducer.
•
If a clear vent tube is present (I24 models only), confirm that the tube
is not kinked or has been removed.
•
Determine that the proper output is being transmitted based on the
predetermined span. Measure the output of the transmitter with a
handheld multimeter and compare the measured output to calculate
output.